HomeMy WebLinkAboutTURNAGAIN BLK 3 LT 4O/(x-I q ,lS,'o°
MUNICIPALITY OF ANCHORAGE
DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTECTION
ENVIRONMENTAL ENGINEERING DIVISION
825 L Street- Anchorage, Alaska 99501 Telephone 264-4720
ON-SITE SEWAGE DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT
NAME
John Lowe
~AILINGADDRESS
8620 Jade Street, Anchora?; Alaska Qq~fl?
LEGAL DESCRIPTION
iht 4: Rln£k 3 , Turnagain Subdivision
LOCATION
Broadus Street
Sunset Plastl cs
2500 I IF HOMEMADE:
DISTANCE TO: Well
Manufacturer . IWell NDt In
5 ft.
PHONE [~NEW
243-5547 []]UPGRADE
Absorption area
17 ft.
Insidelength
Dwelling
DweUing 1 5 ft.
Width
Material
Foundation Nearest lot
line
50 ft. Trench w dl0 ft.
Total length of lines
50 ft. inches
Material beneath tile
+~" screened qravel 7 ft. inches
Depth
NO. OF BEDROOMS
~]ex-8 bdrms,
PERMIT NO.
780902
Liquid depth
PERMIT NO.
Liquid capacity in gallons
PERMIT NO.
780902
Distance between lines
Total effective absorption area
700 sq. ft.
PERMIT NO.
Crib depth Total effective absorption area
Building foundation Nearest lot line
Driller Distance to lot line PERMIT NO.
Sewer line Septic tank Absorption area(s)
OTHER
PIPE MATERIALS
Pln~t~c AgTM D-3Q34
Sb ~ L~'~EST RATING
85
INSTALLER
C & O Excavating
REMARKS
.=~8 3:00 p.m.
1st Inspection o ~
2nd Inspection 9-29 9:30 a,m.
3rd Inspection 9-29 3:30 p.m.
~%~ ~o. 1783-[ ..~
~AIAL
~)~,~°G-GREY & ASSOCIATES, INC. D~-T2~9-78 LEGAL
By: Alvin R. Zeman, P,E.
72-013 (Rev. 3/78)
PERMIT NO.
r-luN I C I ~ AL I TY OF ANCH,~RA*~E
DEPARTMENT OF HEALTH 8ND ENVIRONMENTAL PROTECTION
825 'L' STREET, ANCHORAGE, AK. 9950i
264-4?20
WELL A~4D O~4--~SITE SEWER PEAr4 IT
( 780902 >
APPLICANT
LOCATION
LEGAL
JOHN LOWE
BROADDUS
L 4 BLK ~
8620 JADE ST
LOT SIZE
24~ 5547
14400 SQUARE FEET
TYPE OF SOIL 8BSORATION SYSTEM IS: TRENCH
MAXIMUM NUMBER OF BEDROOMS = 8
SOIL RRTING (SQ FT?BR>= 85
THE REQUIRED SIZE OF THE SOIL ABSORPTION SYSTEM IS:
DEPTH= ii LENGTH= 49 GRAVEL DEPTH= 7
THE LENGTH DIMENSION IS THE LENGTH (IN FEET> OF THE TRENCH OR DRAINFIELD.
THE DEPTH OF A TRENCH OR PIT IS THE DISTANCE BETWEEN THE SURFACE OF THE
GROUND AND THE BOTTOM OF THE EXCAVATION <IN FEET>~
THERE IS NO SET WIDTH FOR TRENCHES.
THE GRAVEL DEPTH IS THE MINIMUM DEPTH OF GRRV~ BETWEEN THE OUTFALL PIPE
AND THE BOTTOM OF THE EXCAVATION (IN FEET>.
RE~'-.!~J I RED SEPT I C TANK S I ~'E= 2250
PERMIT APPLICANT MAS THE RESPONSIBILITY TO INFORM THI~ DEPARTMENT DURING THE
INSTALLATION INSPECTIONS OF ANY WELLS MDJACENT TO THIS PROPERTY 8ND THE
NUMBER OF RESIDENCES THAT THE WELL WILL SERVE.
T~O (~ 2 ) I N~PECT I OFIS ARE REQU I RED
BACKFILLING OF 8N¥ SYSTEM WITHOUT FINAL INSPECTION AND APPROVAL BY THIS
DEPARTMENT WILL BE SUBJECT TO PROSECUTION.
MINIMUM DISTfNCE BETWEEN 8 WELL AND ANY ON-SITE SEWAGE DISPOSAL SYSTEM IS
100 FEET FOR 8 PRIVATE WELL) OR
150 TO ~00 FEET FROM 8 PUBLIC WELL DEPENDING UPON THE TYPE OF PUBLIC WELL.
WELL LOGS ARE REQUIRED AND MUST BE RETURNED TO THE DEPARTMENT WITHIN ~0 DAYS
OF THE WELL CGMPLETION.
OTHER REQUIREMENTS MAY APPLY, !SPECIFICATIONS AND CONSTRUCTION DIAGRAMS 8RE
AVAILABLE TO INSURE PROPER INSTALLATION.
PERM I T EXP I R~S DECEMBER --~l.. i~78
I C£RTIF~ THAT
i: I AM F~MILIAR WITH THE REQUIREMENTS FOR ON-SITE SEWE~ AND WELLS AS SET
FORTH BY THE MUNICIPALITY OF ANCHORAGE, '
2: I WILL INST~LL THE S~STEM IN 8CCORD~NCE wITH THE OODES~
~: I UNDERSTAND THAT THE ON-SITE SEWER S~STEM M8~ REQUIRE ENLARGEMENT
RESIDENCE IS REMODELED TO INCLUDE MORE THAN 8 BEDROOMS.
.....
8P~ JOHN LO~
IF THE
V-~. 2
MUNICIPALITY OF ANCHORAGE
DEPARTMENT OF HEALTH AND ENVIRONMENTAL PROTECTION
Pouch 6-E50, Anchorage, Alaska 99502 276-2221
SOILS LOG - PERCOLATION TEST
[] SOILS LOG
[] PERCOLATION
TEST
PERFORMED FOR:
DATE PERFORMED:
LEGAL DESCRIPTION:
7-
8-
9-
10-
11
12
13
14
15
16
17
18
19-
20-
SLOPE
WAS GROUND WATER
ENCOUNTERED?
SITE PLAN
IF YES, AT WHAT
DEPTH?
Gross Net Depth to Net
Reading Date Time Time Water Drop
PERCOLATION RATE
(minutes/inch)
COMMENTS
TEST RUN BETINEEN FT AND FT
PERFORMED BY:
72-008 (7/76)
CERTIFIED BY: /"[O~'---N~,q~,-- ~.~.V ~
DEPT. OF ENVIRONMENTAL CONSERVATION
SOUTHCE~TRAL REGIONAL OFFICE / ~3~ DE~ALI STRE~
/ Ma~Y BUILDINg, ROOM 1~
A~CHO~E
September 21, 1978
Buster Newton
Newton Investment Company
411 E. 36th Avenue
.Anchorage, AK 99503
Subject: L4, B3 Turnagain Subd.
Dear Mr. Newton:
We have received and reviewed the plot plan of the subject
lot showing the proposed well and septic system locations.
As discussed, the horizontal separation between the well
and septic system will be 164 feet. Thus, the project is
hereby approved for the features with which this department
is concerned. The results of a bacteriological analysis of
the well water should be submitted to this office as soon
as possible upon completion of well construction.
Sincerely,
~Ja~/~s O.~ Star~
Environmental Engineer
cc: DHEP
gml
POUCh 6-650
ANCHORAGE, ALASKA 99502
(907) 264-4111
GEORGE M. SULLIVAN,
MA YOR
DEPARTMENT OF HEALTH AND ENVIRONMENTAL PROTECTION
(825 "L' Street)
October 12, 1978
John Lowe
8630 Jade Street
Anchorage, Alaska
99502
Subject: Four-plex on Lot 4 Block 3 Turnagain Subdivision
This department can not approve the sewer installation
on the subject property.
The leaching trench is placed in the right-of-way
easement.
In order for you to get final approval,.you will need
to move the leaching trench within the lot lines on
the subject lot or get an easement waiver from the owner
of the easement.
If there are any further questions, please contact this
office at 264-4720.
Sincerely,~
Robert C./~r/a~[, R.S.
Associate Specialist
RCP/ljw
October 12~ 1978
J~% Starr
State of Alaska
Department of E4%vironmental Conservation
¥~c Kay Building
338 Denali Street
Anchorage, Alaska 9950].
Subject~ F0ur-plex Located On
Lot 4 Block 3 Turnagain Subdivision
Enclosed is a copy of a letter sent to Buster Newton.
~lis department has received numerous complaints re~arding
the protective radius between the subject well and ?
neighboring private sewer systems.
After investigating the complaints, I'found the following:
(1) The four-plex well is one-hundred thirty five(135)
feet from the seepage pit standpipe located on
Lot 5 Block 3 Turnagain Subdivision, and one-h~%dred
nineteen(il9) feet from the septic tank standpipe
located on Lot 2 Block 3 Turnagain Subdivision.
(2) The four-plex's well is one-hundred forty-flve(145)
feet from the septic tank serving the subject property.
If there are any questions, please contact me at 264-4720.
Sincerely,
Robert C. Pratt~ ~
Associate Specialist
RCP/ljw
co: File
MUNICIPALITY OF ANCHORAGE
DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTECTI~t~/IRONMENI'AL ~,,; ~.CTION ~
825 L Street - Anchorage, Alaska 99501
ENVIRONMENTAL ENGINEERING DIVISION APR 9 ~979
Te,ep.o.e 2B4-472o R E CcE, j_ygsD
REQUEST FOR APPROVAL OF INDIVIDUAL WATER AND SEWER FA I
MUNICIPALITY OF A~FIOP~G~
DEPT. O; ~4SALTH & / , ~ ~'
DIRECTIONS: Complete all parts on page 1: Incomplete requests will not be processed, Please allow ten (10) days for processing~
PHONE
1. PROPERTY OWNER
MAILING ADDRESS
PROPERTY RESIDENT (If different from above) PHONE
PHONE
2, BUYER
PHONE
MAI LING A DDR ESS
PHONE
3. LENDING INSTITUTION
MAILING ADDRESS~
4. R E~T~O R/AG ENT
STREET LOCATION
B. TYPE OF RESIDENCE NUMBER OF BEDROOMS (-~/
[] One [] Four ~ Other
[] SINGLE FAMILY [] Two [] Five
~' MULTIPLE FAMILY [] Three [] Six
7. WATER SUPPLY
INDIVIDUAL*
[] COMMUNITY
[] PUBLIC UTI LITY
8. SEWAGE DISPOSAL SYSTEM P~ INDIVI DUAL/ON-SITE**
[] PUBLIC UTILITY
* ATTACH WELL LOG. A well log is required for all wells drilled
since June 1975. For wells drilled prior t~that date, give well
depth (attach iog if availabJe.) ~ ,,~.
**1 f individual/on-site, give installation date
If system is over two (2) years old an adequacy test is required
by this Department.
NOTE: THE INSPECTION FEE MUST AccoMPANY EACH REQUEST BEFORE PROCESSING CAN BE INITIATED.
THIS SIDE FOR OFFICIAL USE ONLY
DATE RECEIVED
INSPECTION APPOINTMENTS
TIME TIME TIME
DATE DATE DATE
INSPECTOR INSPECTOR INSPECTOR
1. TYPE OF RESIDENCE NUMBER OF BEDROOMS
[] SINGLE FAMILY [] ONE [] THREE [] FIVE [] OTHER
[] MULTIPLE FAMILY [] TWO [] FOUR [] SIX
PERMIT NUMBER
2. WATER SUPPLY
[] INDIVIDUAL DEPTH OF WELL
[] COMMUNITY
DATE DRILLED
[] PUBLIC UTI LITY
Connection Verified LOG RECEIVED
3. SEWAGE DISPOSAL SYSTEM PERMIT NUMBER
L~INDIVIDUAL/ON -SITE DATE INSTALLED
E3PUBLIC UTILITY
Connection Verified iNSTALLER
[]Septic Tank or [] Ho]ding Tank
Size: If Tank is homemade SOILS RATING
give dimensions:
TYPE OF TTANK MANUFACTURER
TOTA L~-BSOR PTION AREA MATERIAL
4. DISTANCESwELL TO: Beptic/HoJding Tank Absorption Area Sewer Line Nearest Lot Line
~bsorption Area to nearest Lot Line
5. COMMENTS
~PPROVED FOR ~ BEDROOMS
[] CONDITIONAL APPROVAL (letter must accompany certificate)
[] DISAPPROVED
~ATE BY (Titl
LEGAl_ DESCRIPTION
72-010 (Rev, 3/78)
ROOM 1208
RECEIVED
Howard Grey
Moening - Grey & Associates
715 L Street, Suite 8
Anchorage, Alaska 99501
Subject: L4, B3 Turnagain Subdivision
Dear Mr. Grey:
We Have received and reviewed your request for a waiver of the
separation distance requirements pertaining to the class C well
drilled on the subject lot. The waiver is hereby approved pro-
viding the well casing is grouted down to the clayey sand layer
(33 feet). This office should be notified when the grouting
operation is arranged as we will need to inspect the process.
I have not beenlable to locate a copy ef the drilleris log in
· · Please
our file so I~apprecmate it mf you would send us a copy.
feel free to contact me if you have any questions regarding the
conditions of this waiver.
Sincerely,
James O. Start
Environmental Engineer
cc: DHEP - Bob Pratt
llm
18-O6LH
DEPT. OF ENVIRONMENTAL CONSERVATION
338 DENALI SREET
MACKA Y BUILDING, ROOM 1206
ANCHORAGE, ALASKA 99501
April 13, 1979
Howard J. Grey
Morning-Grey & Associates
715 L Street, Suite 8
Anchorage, Alaska 99501
'MUNIcIpALITy OF ANCFIORAGE
EI'~VIRoh '~ : F NT,~j. . CT/ ON
RECEIVED
Subject: L4, B3 Turnagain Subdivision
Dear Mr. Grey:
At your request we have reexamined our conditional approval
of the separation distance waiver for the class C Well lo-
cated on the subject lot. It is our feeling that the poten-
tial for contamination is sufficient in this case to justify
grouting of the upper soil strata. If this was a flowing
artesian well, we agree that contamination from the surface
would be highly improbable. This, however, is not the case
as the static water level is about 50 feet below the ground
surface. In addition, I feel we were misled when the case
was first presented for construe-ion a~since the in-
formation regarding the neighboring septic systems was not
furnished. This res~ulted in the well being drilled before
we l~~_~he >s~p_a~ation ~c~u~b~- IS'~AC/80.020
~ not be satisfied. ~o~r-~h~asons~We~ar~nq ¥~r
~equest t~at grouting of the upper 33 feet ofithe well not be
requi~ed.~-~n--~the-r~words, the conditional a~proval contained
in my April 6, 1979 letter remains in effect..
If you still feel justified in seeking an unconditional
waiver, you do have a right to an adjudicatory hearing to con-
test the department's denial. A request for an adjudicatory
hearing must be made within 30 days of receipt of this letter
by mailing or delivering a statement of issues to the Alaska
Department of Environmental Conservation, Pouch O, Juneau,
Alaska, 99811. The statement of issues must state the basis
18-O6LH
Howard J Grey
Page 2 James O. Starr
for the hearing request and otherwise conform With AS 4~62.370.
A failure to request a hearing within 30 days of receipt of
this letter constitutes a waiver of your right to administra-
tive or judicial review of this action.
Please feel free to contact me at 274-5527 if you have any
questions regarding the contents of this letter.
Sincerely,
James O. Starr
Environmental Engineer
,~/cc: DHEP - Bob Pratt
ANCHORAGE, ALASKA 99502
(907) 279 2511
GEORGE M. SULLIVAN,
MAYOR
DEPARTMENTOF HEALTNAND ENVIRONMENTAL PROTECTION
(825 "L" Street}
April 11, 1979
Henry T. Newton/John Lowe
411 East 36th Avenue
Anchorage, Alaska 99503
Subject: Lot 4 Block 3 Turnagain Subdivision
Approval for your individual sewer and water facilities
will not be granted until the following items have been.
completed:
(1)
The top of the well casing is sealed with a sanitary
seal so that it is air tight.
(2) The water analysis report be delivered to this office
from Chem Lab, 5633 B Street, for our review.
(3) See the attached letter.
Notify this department for a re-inspection whe~ descrepancies
have been corrected. If there are any further questions,
please contact this office at 264-4720.
Sincerely,
Robert C. Pratt, R.S.
Associate Specialist
RCP/ljw
CC:
Security National Bank
Mortgage Loan Department
880 H Street 99501
MOENING-GREY ~ ASSOCIATES, INC.
GEOLOGISTS AND ENGINEERS
April 19, 1979
James O. Starr
Environmental Engineer
State of Alaska
Department of Environemtnal Conservation
Southcentral Regional Office
338 Denali Street
McKay Building, Room 1206
Anchorage, Alaska 99501
Re: Lot 4, Block 3, Turnagain Subdivision
Dear Jim:
In accordance with your letter of April 13th, the periphery of
the well casing for the Lot 4 water supply well was grouted'.
This was accomplished by jetting grout pipes to the pre-
determined 33 foot elevation,.and withdrawing these as the
grout was pumped under pressure. 2~wo grout pipes were inserted
for this purpose in order to provide an uninterrupted curtain
around the well casing. The grout pump has a maximum pressure
capacity of 150 PSI. As recommended, the grout procedure was
discontinued at 15 feet in order not to encase-the pitless
adaptor.
If you concur in the above stated procedure and agree that the
work as completed will meet the requirements set forth in your
letter of April 13th, please sign in the space provided. We
Page 2
James O. Start
Lot 3, Block 4,
April 19, 1979
Turnagain Subdivision
have attached an additional copy of this
Thank you for your cooperation.
Sincerely,
MOEN~G-GI~E~S, INC.
Howard J. Gr~J~,/
HJG/tg
letter for your
files.
I CONCUR IN THE ABOVE STATED GROUTING OPERATION.
James O. Starr
Environmental Engineer
Date