Municipality of Anchorage
On -Site Water and Wastewater Section • (907) 343-7904 Page 1 of 3
ON -SITE WASTEWATER INSPECTION REPORT
Permit Number: OSP231124 PID Number: 015-231-21
Dwelling: W Single Family (SF) ❑ with ADU ❑ Duplex (D) ❑ Two Single Family Project: ❑ New ❑■ Upgrade
Name
Mike Holland
ABSORPTION FIELD
Deep Trench Wide Trench ❑ Bed ❑ Mound
❑❑
Site Address
12151 Rockridge Dr
❑ Other
Phone
(907) 748-4813
Number of Bedrooms
Five(5)
Soil Rating
Total depth from original grade
1.0 GPD/SF
4.0 / 4.0 Ft.
LEGAL DESCRIPTION
Depth to pipe invert from original grade
3.5 / 3.5 Ft.
Gravel depth beneath pipe
0.5 / 0.5 Ft,
Subdivision Block Lot
Tengberg Tr-131
Fill added above original grade
0.7 / 0.5 Ft,
Gravel length
75 / 75 Ft.
Township Range Section
Gravel width
5.0 / 5.0 Ft.
Beds: Number of Lines
n/a
Distance between lines
n/a Ft.
SEPARATION DISTANCES
To
Septic
Absorption
Lift Station
Holding
Sewer
Total absorption area
Number of trenches
Dist. between trenches
From
Tank
Field
Tank
Line
750 Ftz
TWo(2)
>6
Ft.
Well
94'*
>100'
N/A
N/A
>25
TANK 9 Septic ❑ S.T.E.P. ❑ Holding ❑ Other
Manufacturer
Greer
Capacity
1,500 Gal.
Surface Water
>100'
>100'
N/A
N/A
Material
Plastic
Number of compartments
2
Lot Line
>5'
>10'
N/A
N/A
NA
Foundation
> 10'
> 10'
N/A
N/A
TATION
Manufacturer
Capacity
Remarks Trenches listed SW / NE
Gal.
*See waiver request
Alarm location
Electri alled by
Installer
PIPE MATERIAL House to tank D3034 drainfield Tank to
D3034
Arctic Terra
Drainfield D3034 CO/MT D3034
Inspector B Schiller
BENCH MARK (Assumed elevation) 100 ft
Inspect ectioes: 1s` 6/29/23 6/30/23
Location and description
2�d
3rd 7/12/23 4"
Bottom of shed siding
ON -SITE WATER AND WASTEWATER SECTION APPROVAL
Engineer's Stamp
Conditional Approval: Date
Aw
Of
% P• BenjamIySchiller
Septic System
Approved Date �'
/r , / ,�
Fc CE 12592
's A
� lac • . 9/5/23 . • •�Co ,W
Note: this does
AW
11E�pROFESSI4��
approval not include well permit requirements.
k ,e
TENGBERG TRACT B1
PERMIT # OSP231124
PI D # 0 15-231-21
TRACT Al
15'ROADWAY EASEMENT
10'UTILITY EASEMENT
TRACT B2A
TRACT 131
tu
Lu
of
of
0
u-
3t
(2)x75'LONG x 5'WIDE, 0.5'
GARAGE EFFECTIVE DEPTH WITH 2'SAND
FILTER ABSORPTION TRENCHES
MIN 6'SEPARATION
�A
C04
MT4
CO2 MT2
X
TH#
C06
0
1500-GAL SEPTIC
A
C05
uj
TANK
PRIVATE WELL
W/
H
Lu
100'RADIUS
FCO
CO3
MT3
z
D
5-BDRM HOME
z MT
2CO1
2CO2 FS
4
B
15'ROAD-
TRACT B2B
EASEMENT/
BENCHMARK
-- - - -------
T
A B
WN R3W SE-C la,?AR-
WELL > 200'FROM PROPERTY LINE
ENGINEERING ,
Benja i Schiller
C C
E 2592
W15/23 •'\\2 A
PLAN AS -BUILT
0 50 100
ins m �m FEET
1"=50'
FCO
1.5
25.1
2CO1
33.2
45.1
M-H
37.0
48.2
SV
41.9
52.8
2CO2
45.4
56.0
FS
81.6
92.4
COI
78.4
90.2
MT1
77.7
89.3
CO2
79.1
105.0
MTT-
80.3
106.1
CO3
89.9
103.8
MT3
86.7
100.6
C04
95.5
121.1
MT4
97.5
123.0
C05
69.6
90.8
C06
1 82.0
103.5
50'RADIUS
TURNAROUND.
SEE PLAT 71-247
LEGEND
CO - CLEANOUT
2CO - DOUBLE CLEANOUT
FCO - FOUNDATION CLEAN(
FS - FLOW SPLITTER VALVE
MH - MANHOLE
MT - MONITORING TUBE
SV - SEPTIC VENT
TH - TEST HOLE
TENGBERG TRACT B".'
PERMIT # OSP231124
PID # 015-231-21
to C,4 C14
0 0 �- 0
02 93.9 FINISH GRADE U — 93.2 ORIGINAL GRADE 20
n i n
89.7
89.7 DRAINFIELD ROCK 89.7
89.2 MOA APPROVED SAND 89.2
75' 87.2
GROUNDWATER AT 83.2 5/19/2023
-r 81.2 TRENCH 1 (SOUTHWEST TRENCH)
oCY) cv) 0 �— 0 .q NT
l--
93.7 FINISH GRADE 0 — 93.2 ORIGINAL GRADE 20
n
11
89.7
89.7 DRAINFIELD ROCK 89.7
89.2 MOA APPROVED SAND 89.2
75' 87.2
'---GROUNDWATER AT 83.2 5/19/2023
N C14
81.2 TRENCH 2 (NORTHEAST TRENCH)
ll
PROFILE AS -BUILT 0
Or. 1rH
.. ... .
(NO SCALE) %.. .....
U
.. ........•
.........
Benja Schiller .
CE 12592
Munici alit of Anchorage -'°�"c"t Sp�
epar menr
P.O. Box 196650 • 4700 Elmore Road
Anchorage, Alaska 99519-6650 • (907) 343-7904 0 Fax (907) 343-7997
http://www.muni.org/Onsite
Development Services Division
On -Site Water and Wastewater Program
* * * * VARIANCE/WAIVER REVIEW * * * *
Waiver#: OSV241007 COSA#: Permit#: OSP231124
P I D#: 015-231-21
Legal Description: TENGBERG TR B1
Engineer: Forge engineering -
Your request for a waiver of the required 100 feet horizontal separation from the septic tank to
the private well has been approved. The approved separation distance is 94.0 feet.
This waiver approval applies to the existing septic tank only. Any future upgrade to the on -site
wastewater disposal system will require all separation distances be met or another approval from
this department.
................................ 0 0 N H E E 0 0 0 0 a x ... ■ ............................. ■ 1
Waiver is Granted: X Waiver is not Granted:
Date: �° ed A rov b
Approved Y
Name of Reviewer
**** VARIAN C E/WAIVE R REVIEW ****
PO BOX 240773
ANCHORAGE, AK 99524
522-7773
677-7766 (FAX)
November 25, 2024
MOA Development Services, On -Site Water & Wastewater Program
4700 Elmore Rd
Anchorage, AK 99507
Subject: Tengberg Tract Bl - 1.2151 Rockridge Drive
Waiver request — well to septic tank
Dear On -Site Services Engineer:
At the time of installation for this system the contractor was concerned about the separation
distance to the well and used GPS location tools to confirm that the tank was outside the 100' well
radius. However, once the stamped survey was completed, we found out that the GPS was not as
accurate as expected and that the edge of the tank is approximately 94' from the center of the well.
The septic tank is on the other side of the home from the well. Grade slopes down from the house
toward the septic system to the northeast. There is no possibility of effluent running out of the tank
and contaminating the well head. Any overflow of effluent would flow away from the well toward
the septic trenches. The design of the trenches, with 2' of filter sand, adds additional treatment
before the effluent flows downward into the actual receiving soils. Also, although there is no well
log available, the previous test hole information shows sands and silts below 10-16', which will
also provide significant additional treatment before any possibility of reaching the well
underground. All of this additional treatment would offset the 6' less separation.
In our judgment, there is no threat of contamination of the well head due to the slightly closer
location of the septic tank. For this reason, we request a waiver be issued for the 94' separation to
the well.
Sincerely,
Benjamin Schiller, PE
AS --BUILT SURVEY I" = 40'
NO CORNERS SET THIS DATE
I HEREBY CERTIFY THAT I HAVE PERFORMED A SURVEY
OF THE FOLLOWING DESCRIBED PROPERTY
TRACT B -1 TENGBERG SUB. (PLAT 71 - 247)
ANCHORAGE RECORDING DISTRICT, ALASKA, AND THAT THE
VISIBLE IMPROVEMENTS SITUA TED THEREON ARE WITHIN
THE PROPERTY LINES AND NO VISIBLEENCROACHMENTS
THE INFORMA TION HEREON /5 FOR THE USE OF L ENDING INS TITUTIONS SPECIFICA L L Y TO S140 WA NY
EXIST0THERTHANNOTED.
CONFLICTS BETWEEN EXISTING STRUCTURESAND PLA TTED LOTLINESAND/OR EASEMENTS,' AND 15
DA TED A TANCHORA GE,ALASKA THIS21 ST DAYOF
NOT TO BE USED FOR POSIT/ON/NG ADDITIONAL STRUCTURES, IMPROVEMENTS, OR FENCELINES
JUL Y , 2023
EASEMENTS OFRECORD, OTHER THAN THOSEAPPEARING ON THE RECORD PLAT, ARENOT SHOWN
HEREON ( UNLESS INDICATED)
NOTE' FENCELINES THAT MA YAPPEAR ON THIS DRAWINGARE NOT TO BE USED TO DETERMNE
HOIT LAND SURVEYING
PROPERTYLINES OR POSITIONADD/TIONAL IMPROVEMENTS
ANYPAV/NG HEREON MA YBEAPPROX/MA TEDUE TO EXCESSIVE WANDXOR ICE
9509GROVERDRIVE
SHOWN SNO
ANCHORIIGFAK 99507
15726 230-28 232-57 223-8615
W
al I
0 000�O�DO
OF A
15'
�
Epp
a�P
pf 0 49 TFi 000
SHE
0.A
O0p
385
f SHANE A. HOLT .' �O
LS-6914
44�apr0/es
Lso�
---�
--
SIon
�_�"
j
EDGE OFORAVEL ROAD
14
N
M
M
o
V
Q Z
z
W
I
V
J
J
O
V
, iQ
PROPER TYIINE
LOT3 S► OPES
CKApFF
CNIA
TRACT A 1
N8958'08"W305.01
J �i SINGLE FAMIL Y
HOUSE
r
15' ROAD EASEMENT
MH
••• •••
•
N 89 58' 45" W 305.00
II'oo SEE PLAT71-247AROUND ��S V
TENGBERG
A VE
MUNICIPALITY OF ANCHORAGE
On -Site Water & Wastewater Program
PO Box 196650 4700 Elmore Road
Anchorage, Alaska 99519-6650 Phone: (907) 343-7904 Fax: (907) 343-7997
hftp://www.muni.org/onsite
On -Site Wastewater Disposal System Permit
Permit Number: OSP231124
Work Type: Septic Upgrade
Tax Code Number: 01523121000
Site Legal Address: TENGBERG TR B1 G:2739
Site Mailing Address: 12151 ROCKRIDGE DR, Anchorage
Owner: HOLLAND H RUSSELL & DIANE
Design Engineer: FORGE ENGINEERING
This permit is for the construction of:
Effective Date:
Expiration Date:
Lot Size in Sq Ft:
Total Bedrooms:
,Dillcnt S,
Department
6/8/2023
6/7/2024
100726
Q Disposal Field Q Septic Tank ❑ Holding Tank ❑ Privy ❑ Private Well ❑ Water Storage
All construction shall be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska
Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80)
3. The wastewater code requires inspections during the installation. The engineer shall notify the Development
Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather
shall be either:
a. Opened and Closed on the same day, or
b. Covered, sealed, and heated to prevent freezing
�
Fie L s u ej -tc, 2SIa P,
Issued By:�
Date:
Date:
5
MUNICIPALITY OF ANCHORAGE
0 -
Community
Community Development Department Phone: 907-343-7904
Development Services Division Fax: 907-343-7997
On -Site Water & Wastewater Program
ON-SITE SEWER/WELL PERMIT APPLICATION
Parcel I.D. 015-231-21
Property owner(s) Mike Holland
Mailing address PO Box 102085, Anchorage, AK 99510
Site address 12151 Rockridge Drive
Day phone 907-748-4813
Legal description (Sub'd., Block & Lot) Tengberg Tract 131
Legal description (Township, Range & Section)
Lot Size 100,726 Sq. Ft. Number of Bedrooms 5
APPLICATION IS FOR:
APPLICATION IS AN:
TYPE OF DWELLING:
(® all that apply)
Absorption Field
❑X
Initial ❑
Single Family (SF) ❑X
Septic Tank
❑X
Upgrade ❑X
(w/wo ADU)
Holding Tank
❑
Renewal ElDuplex
(D) E]
Privy
❑
Multiple Dwellings ❑
(SF and/or D)
Private Well
❑
Water Storage
❑
THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR:
Distance:
I certify that the above information is correct. I further certify that this is in accordance with
applicable Municipal Codes.
(Signature of property owner or authorized agent)
Permit/Rush Fees:--P596-Waiver Fees:
Date of Payment: r 20 Date of Payment:
Receipt Number: d t If 0111 Receipt Number:
Permit No. cap 2- 3 117-0 Waiver No.
Permit App_::- : ,—.,:c;
May 30, 2023
MOA Development Services, On-Site Water & Wastewater Program
4700 Elmore Rd
Anchorage, AK 99507
Subject: Tengberg Tract B1 - 12151 Rockridge Drive
Septic system design
Dear On-Site Services Engineer:
The septic system on the above lot has failed, so we are submitting this permit application for the
construction of a new one. The attached site plan identifies the location of the home as well as the
existing well, septic location. The owner currently has a 4-bedroom system, but has asked for a 5-
bedroom replacement.
The ground surface on the lot slopes toward the road moderately around the home, but where the
test holes were dug the ground flattens out to 1-5% slopes. There are no slopes greater than 25%
within 50 feet downslope of either the primary or alternate site. Contours are shown on the site
plan showing the grade and direction of flow. Stormwater drainage will not impact this septic
system. The new trenches will be constructed parallel to the slope as much as possible.
Wells on this and adjacent lots are shown. The new system will be a minimum of 100’ from all
wells and surface water, and more than 5’ away from the septic tank. Please refer to the attached
test hole logs, plan and profile pages for the septic design. If this design is followed, there will be
no adverse impacts to adjacent properties.
Sincerely,
Benjamin Schiller, PE
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP231124, Deb Wockenfuss, 06/08/23
Benjamin Schiller
CE 12592REGISTEREDPROFESSION A L E N GINEER
1"=50'
(2)x75' LONG x 5' WIDE, 0.5'
EFFECTIVE DEPTH WITH 2' SAND
FILTER ABSORPTION TRENCHES
MIN 6' SEPARATION
50' RADIUS
TURNAROUND.
SEE PLAT 71-247
CO - CLEANOUT
2CO - DOUBLE CLEANOUT
FCO - FOUNDATION CLEANOUT
FS - FLOW SPLITTER VALVE
MH - MANHOLE
MT - MONITORING TUBE
SV - SEPTIC VENT
TH - TEST HOLE
LEGEND
2CO TH#1
TENGBERG TRACT B1
FEET
0 50 100
FCO
5-BDRM HOME
950
5/29/23
10' UTILITY EASEMENT
15' ROADWAY EASEMENT
SEPTIC PLAN
GARAGE
SHED
SHED
15' ROAD
EASEMENT
945
940
935
935
TH#2
FS
CO1
MT1
CO3
MT3
CO4
CO2
MT2
MT4
1500-GAL SEPTIC
TANK
DECOMMISSION
EXISTING
SEEPAGE PIT
DECOMMISSION AND
REMOVE EXISTING
SEPTIC TANK
PRIVATE WELL
WE
L
L
>
1
0
0
'
F
R
O
M
P
R
O
P
E
R
T
Y
L
I
N
E
UN
D
E
V
E
L
O
P
E
D
-
N
O
W
E
L
L
WELL > 200' FROM PROPERTY LINE
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP231124, Deb Wockenfuss, 06/08/23
TENGBERG TRACT B1
TYPICAL TRENCH SECTION
(NO SCALE)
NOTES:
1. GRADE AREA OVER TRENCH TO DRAIN AWAY
2. PROVIDE 3' OF COVER OVER TRENCHES AND 4' OVER SEPTIC TANK, OR 2'
WITH 2" OF INSULATION
3. CHECK GROUNDWATER AT TIME OF CONSTRUCTION. IF LEVEL IS HIGHER
THAN PREVIOUSLY OBSERVED, CALL ENGINEER IMMEDIATELY
Benjamin Schiller
CE 12592REGISTEREDPROFESSION A L E N GINEER
5'
ADD ADDITIONAL FILL TO ENSURE 3' COVER AFTER SETTLEMENT
3'
DESIGN FACTORS:SYSTEM REQUIREMENTS:
750 GPD PEAK FLOW
PERK RATE: <1 MIN/IN
APPLICATION RATE: 1.0 GPD/SF
5' WIDE TRENCH SYSTEM
1500-GAL SEPTIC TANK
BOTTOM OF TRENCH: 4' BELOW GRADE
FLOW LINE ELEVATION: 3.5' BELOW GRADE
750 GPD / 1.0 GPD/SF / 5' WIDE * 1 RED FACTOR [0.5 DEEP] = 150 LF TRENCH REQUIRED (150 LF SPECIFIED)
4" PERFORATED PVC
(HOLES DOWN)
5/29/23
6"
6"
GEOTEXTILE FABRIC
DRAINFIELD ROCK
MOA-APPROVED SAND FILTER
2'
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP231124, Deb Wockenfuss, 06/08/23
LEGAL DESCRIPTION:
PERFORMED FOR:
DATE: PARCEL ID#:
SOILS LOG AND PERCOLATION TEST
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
DEPTH
(feet)
TEST HOLE 1
DATE READING START TIME NET TIME
(minutes)
DEPTH to
WATER NET DROP
PERCOLATION RATE: (MIN/INCH)
(inches)(inches)
DATE OF MONITORING
WAS WATER ENCOUNTERED?
DEPTH TO WATER AFTER MONITORING
IF YES @ WHAT DEPTH?
0.4
5/19 1
2
3
4
5
6GM (SILTY GRAVEL)
Professional Engineers Stamp:
YES
Tengberg Tract B1
5/19/2023 015-231-21
Mike Holland
9:35 5"
1' OB
1:33
Benjamin Schiller
CE 12592REGISTEREDPROFESSION A L E N GINEER
5/30/23
PERC TEST LOCATION
TECHNICIAN: B. Schiller
11"
10'
9.5'
5/30/23
COMMENTS:
SITE PLAN
6"
USCS SOIL CLASSIFICATION WAS VISUALLY DETERMINED
5" 1:43 11" 6"
5" 2:11 11" 6"
5" 2:30 11" 6"
5" 2:26 11" 6"
5" 2:24 11" 6"
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP231124, Deb Wockenfuss, 06/08/23
LEGAL DESCRIPTION:
PERFORMED FOR:
DATE: PARCEL ID#:
SOILS LOG AND PERCOLATION TEST
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
DEPTH
(feet)
TEST HOLE 2
DATE READING START TIME NET TIME
(minutes)
DEPTH to
WATER NET DROP
PERCOLATION RATE: (MIN/INCH)
(inches)(inches)
DATE OF MONITORING
WAS WATER ENCOUNTERED?
DEPTH TO WATER AFTER MONITORING
IF YES @ WHAT DEPTH?
0.26
5/19 1
2
3
4
5
6GM (SILTY GRAVEL)
Professional Engineers Stamp:
YES
Tengberg Tract B1
5/19/2023 015-231-21
Mike Holland
10:30 5"
1' OB
1:10
Benjamin Schiller
CE 12592REGISTEREDPROFESSION A L E N GINEER
5/30/23
TECHNICIAN: B. Schiller
11"
10' *
None
5/30/23
COMMENTS:
SITE PLAN
6"
USCS SOIL CLASSIFICATION WAS VISUALLY DETERMINED
5" 1:15 11" 6"
5" 1:08 11" 6"
5" 1:17 11" 6"
5" 1:25 11" 6"
5" 1:32 11" 6"
SW (SAND)
SM (BROWN SILTY
SAND W/ GRAVEL)
*SIGNIFICANT WATER RAN OUT OF THE SAND LAYER DURING DIGGING. ASSUMED TO BE RUNOFF FROM BREAKUP
PERC TEST LOCATION
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP231124, Deb Wockenfuss, 06/08/23
NOTE FENCEL/NES THAT MAYAPPEAR ON THIS DRAW/NGARE NOT TO BE USED TO DETERMNE HOLT IAND SUAWYING
PROPERTYLINES OR POS/T/ONADD/TIONAL IMPROVEMENTS 9509 GROVER DRIVE
ANYPAV/NG SHOWN HEREON MA YBEAPPROX/MATEDUE TO EXCESSIVE SNOWAND/OR ICE
OF A
49 TH
s.�,
A
N SHANE A. HOLT �d
Q P LS -6914 5o`DO
ssiona� �o
EDGE OF GRA VEL ROAD
14
15726 230-28
ANCHORAGEAK 99507
225-8615
385
N
,4S --BUILT SURVEY I" =40'
NO CORNERS SET THIS DATE
M
I HEREBY CERTIFY THAT I HAVE PERFORMED A SURVEY
OF THE FOLLOWING DESCRIBED PROPERTY
TRACT B -1 TENGBERG SUB. (PLAT 71 - 247)
ANCHORAGE RECORDING DISTRICT, ALASKA, AND THAT THE
VISIBLE IMPROVEMENTS SITUA TED THEREON ARE WITHIN
THE PROPERTY LINES AND NO VISIBL E ENCROACHMENTS
THE INFORMATION HEREON /5 FOR THE USE OFLENDING INS T/TUTIONSSPEC/F/CALLYTOSHOWANY
EXIST0THERTHA NNOTED .
CONFLICTS BETWEEN EX/ST/NG STRUCTURESAND PLA TTED LOTL/NES AND/OR EASEMENTS,' AND IS
DATEDATANCHORAGE,ALASKA THIS 9TH DAYOF
NOT TO BE USED FORPOSIT/ON/NGADDITIONAL STRUCTURES, IMPROVEMENTS, ORFENCELINES
FEBRUARY , 2023
EASEMENTS OFRECORD, OTHER THAN THOSEAPPEARING ON THE RECORD PLAT, ARENOT SHOWN
W
HEREON ( UNLESS INDICATED)
NOTE FENCEL/NES THAT MAYAPPEAR ON THIS DRAW/NGARE NOT TO BE USED TO DETERMNE HOLT IAND SUAWYING
PROPERTYLINES OR POS/T/ONADD/TIONAL IMPROVEMENTS 9509 GROVER DRIVE
ANYPAV/NG SHOWN HEREON MA YBEAPPROX/MATEDUE TO EXCESSIVE SNOWAND/OR ICE
OF A
49 TH
s.�,
A
N SHANE A. HOLT �d
Q P LS -6914 5o`DO
ssiona� �o
EDGE OF GRA VEL ROAD
14
15726 230-28
ANCHORAGEAK 99507
225-8615
385
N
M
S
o
V
Q Z
s
W
I
V
J
J
O
V
!:Q
PROPER TYLINE
LOT3 S► OPES
CKApFF
CNIA
PSP
TRACT A 1
N 89 58' O8" W 305.01
J Q�G SINGLE FAMIL Y
HOUSE
�14i9.
r
15' ROAD EASEI}4ENT
N 89 58' 45" W 305.00
II'oo SEE PLAT 71-247AROUND
��S V
TENGBERG
A VE.
D
R&M
CivilEngineers
ENGINEERING & GEOLOGICAL CONSULIANTS
229 EAST 51st. AVE. - P.O. BOX 6087 - ANCHORAGE, ALASKA 99503 TELEPHONE 907-279-0483 TELEX 090-35419
Geolo#/sts Land Surveyors
JAMES W. ROONEY, P. E.
MALCOLM A. MENZlES, P.E., L.S,
JAM[iS H. WELLMAN, P.E.
May 10, 1974
R & M No. 462023
RALPH R. MIGLIACClO
Mr. H. R, Holland
Box 385B SRA
Anchorage, Alaska
Re: Test Hole and Soil Log Report for Sanitary System, Track B-l,
Tengbeg Subdivision
Dear Mr. Holland:
We are submitting herewith the test boring results and our comments
regarding soil conditions encountered at the subject site. This
investigation was performed in accordance with your request of May 6,
1974, and those procedures outlined in a letter dated September 13,
197i by Mr. Roll Strickland of the Greater Anchorage Area Borough
Department of Environmental Quality.
A single test hole was put down within the Tract B-1 area for the
purpose of defining genera], subsurface soil conditions for the proposed
.sanitary system. Excavation was accomplished with a tractor-mounted
backhoe and the testhole was extended to a total depth of 16.0 feet
below ground surface. The final log.prepared for the test hole has
been included in Drawing A-01.
Ground water was not encountered in the test hole.
We appreciate being given this opportunity to be of service to you.
Should you have any questions with regard to the above, please do not
hesitate to contact us.
Very truly yours,
R & M ENGINEERING & GEOLOGICAL CONSULTANTS,
James W. Rooney V
INC.
JWR:ph
ANCHORAGE FAIRBANKS JUNEAU
NOTE:
T.H. 1
5-9-74
ORGANICS
Sandy Silt
Sand, Some Gravel (SP)
Gravelly Sand, Trace Silt (SP)
0.0{
1.0'
4.5t
Silty Sands (SM)
Sand Trace Silt (SP)
10.0'
12.5'
No Water Table
Test hole excavated with tractor mounted backhoe.
Engineering ~ Geological Consultants Inc.
ANCHORAGE FAIRBANKS ALASKA ~UN~AU
16.0' T.D.
H. R. HOLLAND PROPER'I~f
LOG OF TEST HOLE
Anchorage Alaska
--DATE 5--9--74 ISCALE 1"=2' I OWN E,.Y JRS I CHKO mY WED I P~ou. NO. 462023.lO.We.NO. A-01
i
/
/
April I0, 1974
Mr. Rolf Strickland, Chief Sanitarian
Dept. of Enviornmental Quality
Greater Anchorage Area Borough
3330 "C" St.
Anchorage, Alaska 99501
APl'{ ¢ :' 1974
SUBJECT: Tract B-I, Tenberg Subdivision
Dear Mr. Stricl<land:
Due to the topography o¢ this lot as described to us by Mrs. H.
Russel Holland, we have no objections 1'o tile placement of the septic tank
approximately 75 feet from the well. This represents a waiver from the
provisions of 18 AAC 72.020 (c) (2).
Yours truly,
Kyle J. Cherry, P.E.
Regional Enviornmental Engineer
cc: H. Russel Holland