ON-SITE WASTEWATER INSPECTION REPORT
Permit Number: OSP211016
PID Number: 018-241-14
Dwelling: Q Single Family (SF)
❑ with ADU ❑ Duplex (D) ❑ Two Single Family Project: ❑ New ®❑ Upgrade
Name
George & Amy Brun
ABSORPTION FIELD
❑ Deep Trench ❑Q Wide Trench E] Bed E] Mound
Site Address
2435 Clements Drive
❑ Other
Phone
Number of Bedrooms
Soil Rating
Total depth from original grade
3
1.2 GPD/SF
8 Ft.
LEGAL DESCRIPTION
Depth to pipe invert from original grade
4 Ft.4
Gravel depth beneath pipe
Ft.
Subdivision
Block Lot
]Gravel
Turnagain Park #2
1 5
Fill added above original grade
NA Ft,
Gravel length
38 Ft.
Township Range Section
width
5 Ft.
Beds: Number of Lines
NA
Distance between lines
NA Ft.
SEPARATION DISTANCES
To
SepticI
Absorption
Lift Station
i Holding
I Sewer
Total absorption area
Number of trenches
Dist. between trenches
From
Tank
Field
Tank
Line
380 y- cs� Ftz
1
NA Ft.
Well
100'+
100'+
NA
NA
25'+
TANK ❑® Septic ❑ S.T.E.P. ❑ Holding ❑ Other
Manufacturer
Greer
Capacity
1250 Gal.
Surface Water
100'+
1001+
NA
NA
Material
Number of compartments
Lot Line
5'+
5.1'
NA
NA
NA.
HDPE
2
Foundation
10'+
10'+
NA
NA
LIFT STATION
Manufacturer
Capacity
Remarks
Gal.
Alarm location
Electrical installed by
PIPE MATERIAL House to tank 3034 Tank t03034
Installer
drainfield
Pomraning Excavation
Drainfield 3034 CO/MT3034
Inspector Pannone Engineering
BENCH MARK (Assumed elevation) 174 fl
Inspection im 5/3/2021
5/4/2021
Location and description
3,d
2nd
41"
Deck trim at point A
ON-SITE WATER AND WASTEWATER SECTION APPROVAL
Engineer's Stamp
Conditional Approval:
Date
,�� OF AC,jk�
Seven F2. I'unnone �s
Septic System
Approved <rw (x+ Date
19 . CE 814
�b
Note: this approval does not include well permit requirements.
o,Fsst
�u�c voivu 1.)
p� = D I I O KWIC �(n DID (n �-1Z
v CO Or -1n Io�I1o1Dp�
C0 ti O2 yam Zcn� A-C)Z• fTl
t r
� y m rx r Do n�Op D
�p�0� x m < I I m_O Dp Z-jp TTlO�-D-i DSO
F nz-�zZ��~D �� m� �mD �Zm!'�O�z
Dx 2 m
�A�oo�oo0 co I mp W� W�� J.. ,N�m�
-=z M O �v cn I
c z (n Z m 00 min N cn U C3 mC7 DT1
cn
oncn
o rm-m 00,Ti� mm's mm�Op'S
0 m�� zcn o z �mM
- 0 DOZ D _ n
E m --I
Co Q (T1
P
N� O O
m
M W
/\�� W r' /� cn 3 ami
� D
m T\ m
m 1 m oo E
3
zLn
N 3 V
m I I Z o O
D O N _ J /£ III/
I m 0 � 3 oV �I
o - 1\
oxer / �I
00 C) - to
M z 3 A U 2
f� \r
M �7 M n Z / 0 A IIC7 I :
Iff J I fTl
I r\
/ _ = cn 4,
I� � cin J � � I
v R.
\
FTIC/)
almcnalmcn
zzZ
m u
D O (J)
ar�iiio� r I/ �, F m f C_
m z m �: / j� z /
M v� IW W — / (W o / o cn �
gow. I I. l � o� �z-I w- m
Z''D N / •--' (nom ➢ w O 2 cn W N
m cn� 0000 mx m t=
m No \ J m NQ I ocno
m c '
Ell= a: / / /. m / / mmr- D _ O�D`I
pm-ZE�� ( — C
x I
my��� 4- \ / m ' cn y Z—
�aN` � 20
o
cpm _ — — _ — — — — ` _ 1 o m o _
c- W z
02
cu
Omg—
Z
NOTES: PANNONE ENG SVC LLC ER AK C.I. 1088) "`,,, REVISIONS 'DATE
RECORD DRAWING PHONE (9007)Y745082 OALIFAX, (907)9745-8201 ^ E OF AC�sf� SCALE 10/2021
1" = 40'
TURNAGAIN PARK #2 B1 L5 `h'•.' P.I.D. NO
DRAWN MJL GEORGE & AMY BRUN " 018-241-1a
•. St- - Pan ana
2435 CLEMENTS DRIVE ce-e,a9n �= PERMIT No.
� = OSP211016
FSITE PLAN ANCHORAGE, AK 99516 ' SHEE, of 2
N N N � � � N �
W W •P .p W w W N
y
Ln
in
o
-.
v
�
w
V
W
W
Cn
Cn
Cn
.P•
�P
-P
N
W
P
Cn
O
V
�
Cn
[�
N
V
CO
W
0
Q au
� N
0�
r O
D�
G1
Z m
x rn� I
o
Q I c
I
I
1
I
— a
}
[1
m o fo
y f -
Nm
I
I
L n
9
b
R }
�R
I
- I o
Ay
O a S
NG 8
NOTES: PANNONE ENG SVC LLC (C.1. 1088) ........REVISIONS DATE
RECORD DRAWING P.O. 60X 1807 PALMER, Al( 9645 P�E`QF. A,,, 05/20/2021
PHONE 907) 745-8200 FAX (907) 745-8201 SCALE
NTS
TURNAGAIN PARK #2 B1 L5 _ P.I.D. 241-14
DRAWN MJL GEORGE & AMY BRUN "
y�'•. Steven R. Pannone
2435 CLEMENTS DRIVE ce _y PERMIT
SITE PLAN ANCHORAGE, AK 99516`
a`cssia SHEE2 OF 2
�" • Z .T] > y m V . Uta (.+ N O N O io m V T N A 4 N - 0 N A W N O O
O
y Onm 2 Z p -1
C+ m ,> 'M
�lmyrnyDO-INyyD-���DytAr-a -, �m 1 MM�m5N�mn OZD ZOD TKM'Zmmm y �Nrm O Ono n Wo> V M
MOOO >Xmr�.1myD mMmm>lmpm2m>T°m a Oven ZO-'�O-FwO">v-x Orin Or �, OWN{p omzNzr m
o w>z r�O; rn2, nGnnn Os yO >r' n DOy ovx ZvmOm y.�_cm -mm� <D- C yC'n-'C'Dn yij D
A boa OD..,O-zmn O�o 0,2,10 Amozo p_mZ Oji �rnnmA yovzismvay mo=�•GDimx -pi v�ymo m-n��po
8 ,Atmn no_2i00 vt_2,z-2-,20� vZ-mZ O m >r DC o�m�r-'zmomAD O Cx nnvlzZ !S
A8F0 OZ z2o An a y �zN-� m�,,,2'A=r Cpm ma Z2 m m0A2 _G Z z:UD tnc ODy my y
z mvvz nz A. n mon �� vi 'nom "'D''Di_m�o,n05 P`�Opinymay"D N oN ZZ.+FM:E �~ n
2 O'_'i oz. Oy yy y yF 9 �N 2 O D A Cy rn O r.77 ZOO C m (n
R myto -O92p .mi V1A0AA .0 '�0.�"m.ZI Z m �ZOZ Vr OOy rOZmrVV FyO yOnZ m <ry�j �f+l A�OD>y 'n
zm� oN'�'2zm NONVI V='.-.zm N hiAoNz�+1>/1-:fl ,-S'n mmmm0 �02m AC0 -n-it r mND T..-.M6.0 [� m
yy m�1 y�yxOMZ D
O>r -n2Zm S>22 "' OOmmy= m m0y 2. OZm=1 ,/IC mO�mWm 1nA2=ZZrV > Vm~2NZ> 2 IWZon
n�� vrTmOzr��� ma oniNNg m ��zo `zojrsz�Ammmn mzOCnZmm,x o OOtrr�-boD a D
pOy Fm'<o,2.,o 0=.Z9]> O KJ>Cm AmD N OmZ Oyr=.O -p>Nm N-1pp-1O�OOD t•Z/.1 KZ� mP�mn�r r
yOm y�-DiZrZ+"+1OF N wor'>; V1 yKy n�0 mm ��O�ZM--d CAA mO=Ag:* om OS m�1n Z�m Am(mn
mm nmZNA\y m0 �zZ ZAZ O-Zr OZAmgF �n2o�� DmNOOjOo 12+1, yzZ �2 nz '>
Z
mOa� �=Nx"r`�mmpA 'n y00 mR'm Ovy *.Tlzpm2 ND7COmZ -.��r 2>i00 AmcZ'�vM w- Cm`�a O<
M�� ZO gmy ZZ O xzm ivy DAO Oyyrz>•OV xO TI�-n-1 znrm200NK �VOAO N{���mfr*1 V:
18 y xn m{9 2 Foz mx �X O
.DZ p0 pOVOD O y m O m �.O Tmm �rn-1.02200
y D N Z- F- m O m X m G
2 0� C S n n Z 25--22 r .66 W m 0° r_ n m y r m m D y O >
y 5 V ZZ m nZ OZO VGn _
y NU rzMmm 0 {y' .morn m",m a, z �_'-S OzN "m Om COn{12�1 >my>yN mZV, z
Oz- >x 0y'p 00 Z) >I-,n G zA 'Mn20 mmm- oi, rmiyOzrn vmzF noFnnm
Z{n 60 m➢0 •Dy.^ O Z-, nm O y mZ-.� m„,OOa A-pOp mDT,D S OyODZ --p-p vi
rn O ' Q2001r1D pm; N .� x �m p."0. , O O=m Z-'IOOm zm mm"D XWZn
D� O nmT-n m N 2m m- c
OZ"y m:501>m O> {f (")0 2-cm D Z +1W pN0 Z'Z- 0W>
rn0 r' D Z (n Or'm -1r Tf VINmO T. m y t� rnyy Ut�-
x>� z2 mVIPr' OOm O mOz �2. O>m>0 y"a P'.ZI mOya NOzzn=00 mOm�OZNZ>oo
mr2 Om m2't0 :[ O mFy Nx mZ2 Im�t00 OOG 0000 COO'<2D IAM OC OD n02 �2
mK vn-Di ]10 6r> Npmm y O'> m mOZ pmm O� "m DOfG.12 mZME-m mmm-ro'^vn�Z
OD> C =NC „��tiZO A rDaO rntn 'xp W >> mm OmMAZ m9g4>JMo„2 OZn rtmm�-O-yyo M
O nor mi N�Z jZ2F M 000 mm ROE TOO(Z7 m0 .101• m`—' 8OA5z'm-o= mzm y�A Kamm
y -1mF N_ OaOZnm_ m E- �n x00 > W� A� m OZOI �-O ,gym.-mm'n3 zo
m yOS 212/1 LS-1y2 n(-tmm C C'nN Dz ��Or mR:1 O Z IN*i rni. H'D nOmO> N'r<r S7"D 1y
NOS ND Z.Urn m,et '�N <'nD ZO SZm £CKD ns ez a> --EM: >,Z ME0O-�-I A Nn
0� �r Boz yymm o '2oF Oy Inmz �lAxt_n x'o m civ �n=-0 z,zmO o=o �O x mC
ZN� ms n1�mmCz]A .Z07ZS SZ FOO .mv y3 zr >O 0m2.Ct %, >+tm>OjW a Dm
W O O O m > D N r S C> O r
AZm _2 Omyzmy .%1 mO,G., r> y Z nm>O >0 xm .11 m()oynm C:,. Z-C n y-2i
oom Zy 2b0 MO - �zD i0 0m , 0Tfnp 00 O c� Eaym C:,. Z-4 m m
1Sm 40 Oma_. y f/1 022 m D,z.10 mroo my O zm OM1 o{z �1m-y <E ,03 N y0
R->+m �n ,rm,.-11C9'0-_+11yD99 y o mm{ `-1' O Zmyx �w_mvzi m'^ m me ,zna-n•=ovOo `�czin, z Ao
y0�1 oC «K V 2 -N-MA �y O N n .iyl yN 0 Z' ynOOmc AN�t N.. mo o Oz
MM yo -> O Om A Azr 20 z m goo xm O 2E =x30<ozo Io rnm O N0
D O -y E Z _ Z _ I m C Z _f D m rn ME X>
DO Zm z9 M F S 2*0 Mw > i -N-, rmi 26 0, r o? ozz:i'mmo m co nm Oy
mZ T.p .FOO 02 > OLn
yn O f r> Z 0� "C y2mz-D, '-'O '� yV <m jm
C, ANO S "0 D = S�Sm -X-11 Z ,,, M M m_Ir ZD m r>" am
ZZ r0
y O m'z g m O r La ZyDm r1� A m Ornr mo D
m 0
O
D
mm V rn N a W N - O p� J O1 N a W N -•
m
M
Z) y
Q n Imo
M OO O y
N 2
vm o
I
O n)D
I < O
O r (�
I
O
Crn
� M O m z D
p n In
O
C)
Z m C m z M
Imit An m Zj D m O in
ZOO H ~ IZ0
-mrt .,{- rD = 150
r
m �+ D
2M
° ~ m r
z n r x Z A
n z
= O � a D
M { m
DD y a . .
Z
mnD O' mmm^-p-
�iy�tn�-ny
= O o
==G =cc=0 Qy
m m " Q
�O Wl7p z
M X oOmmut SIA
D n zf<,Iz�C)f*I>
m�
< I� 'm A .Z7 C .�.>. D
-9Z_I
c O m > x;u,
Z z <OZ In -
n 0 c: C7 Z
D Zr
r
NOTES: PANNONE ENG SVC LLC (C.1. 1088) """`1 REVISIONS DATE
P.O. BOX 102954 ANCHORAGE, A 99510 '�E OF AC', 05/13/2021
RECORD DRAWING _- � q ,
PHONE 907) 272-8218 FAX (907) 272-8211
=c- �P ' `rfy'h, SCALE
s:' '•, NTS
TURNAGAIN PARK #2. 81 L5 .. P.I.D. N241-14
DRAWN MJL GEORGE& AMY BRUN
• ste en It noon. -fir PERMIT N0.
2435 CLEMENS DRIVE %c ce-etas_ OSP211016
SOIL LOG a •.-.-
ANCHORAGE, AK 99516 ``III,E�,��� SHEET
3 OF 3
��a1
N Tfl-
o
�
N
£j
z
0
�
a
m
0
s
z
m
0
s
z
m
0
s
z
m
z
�
y
s
rn
Sty
m
o
=
e
nr�
N
I 4
I
N
I
9 y
LOT 5
v
w
00
a
00
02
LOT A
N 89'9'00" E 100.00'
SEPTIC
VENTS
(tm)
b moo.
LOT 5
BLK 1
�' 30.5'
GRAVEL
D/W
(�)ELL
N89°59'00"E 100.00'
O
N CLEMENTS DRIVE
0
N
i
ANCI30RA.G1 RECORDING DISTRICT, ALASKA
AS -BUILT OF:
'I'ITR AGAIN PARK SUBDIVISION Not
LOT 5 BLOCK 1 PLAT P -160A
SURVEY CERTIFICATE: 1, John L. Schuller, Have conducted a
physical survey of this propem as shown on this drawing and that the
improvements situated hereon are within the property lines and no
enchroachments exist other than noted. Under no circumstance should
any information on this drawing be used for construction of fences,
structures. -improvements, or for establishing boundary lines.
EXCLUSION NOTES: It is the owners responsibility to determine
the existence of any easements, covenants, or restrictions which
do not appear on the recorded subdivision plat.
WORK, ORDER NUMBER: I DATE: SCAlE r—uaw
MA° 6, 202 i 1 "=30'-schuilergaknet
21 - 0 3 5MIAMI BY: CHE BY GRfll mjmB : BDQK/ Ate•
JLS SV13033 210149
2.2'x2. D'
FP CANT
U
w
06
O
�1-
00
ro
2'x6' S:
CANT O
14.5' O
r
O
O
O
Z
© = FND 5118" RE13AR
49TH
%JOHN L. SCHULLER.•'� O
LS-10408AO
{
°fessionot L�
�
B
SU
�� N� LARD
W
Z
1831 Talkeetna Street
Anchorage, Alaska 99508
(907) 227-1455 office
(907) 274-4992 fax
MUNICIPALITY OF ANCHORAGE
On -Site Water & Wastewater Program
PnBox 1SW85U � 47UOElmore Road
Anchorage, Alaska S9519-OG5O Ph 904 Fax: (307)343-7397
Permit Number: OSP211016
Work Type: Septic Upgrade
Tax Code Number: 01824114000
Site Legal Address: TURNAGA|N PARK #2 BLK 1 LT 5 G:3033
Site Mailing Address: 2435CLEK4ENTSDR, Anchorage
Owner: BRUNGEORGE G&AMY K
Design Engineer: PANNONEENGINEERING SERVICES
This permit isfor the construction of:
R1 Disposal Field 0 Septic Tank El Holding Tank 171 Privy
Effective Date:
Expiration Date
Lot Size in Sq Ft:
Total Bedrooms:
2/10/2021
2/10/2022
[] Private Well 171 Water Storage
All construction shall beinaccordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska
VVaab*wehyr Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC8O)
3. The wastewater code requires inspections during the installation. The engineer shall notify the Development
Services Department per AMC 15.G5.Provide notification bycalling (8O7)343-7BO4(24/7).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather
shall beeither:
e. Opened and Closed onthe same day, or
b Covered, sealed, andheated hoprevent freezing
Special Provisions: A test hole is required prior to construction of the field to confirm the soil profile
and percolation rate for any portion ofthe field that iooutside the 3Uftradius ofopercolation test.
Received
Z C)
i
Municipality of Anchorage
P.O. Box 196650 0 4700 Elmore Road
Anchorage, Alaska 99519-6650 a (907) 343-7904 0 Fax (907) 343-7997
http://www.muni.org/Onsite
Development Services Department
On -Site Water and Wastewater Section
Waiver#: OSV211007 COSA#: Permit#:OSP211016
PID#: 018-241-14
Legal Description: Turnagain Park #2 Block 1 Lot 5
Engineer: Pannone Engineering Services
Applicant: George & Amy Brun
Your request for a waiver of the required 10 feet horizontal separation from the absorption field
to the property line has been approved. The approved separation distance is 3.0 feet. See
engineer's waiver request for justifications. The proposed absorption field must meet the
minimum 16 ft separation to the absorption field on the lot to the north.
This waiver approval applies to the proposed absorption field only. Any future upgrade to the
on-site wastewater disposal system will require all separation distances be met or another
approval from this department.
■vaaaaavaaaaavaaaaaaaaaasaaavaaavavaaaavvaaaaa■alavaavavavaa0aaaasaavaavavvava1
Waiver is Granted: X Waiver is not Granted:
Date: 291d o Q I _ Approved by: xt,�_gt 0,a�i M
Name of Reviewer
■vvvvvaavvvvaaavvavvavaaavaaaaaavvaaay.evaavava■aaeaaaaaasaavvvavaavvavavvaaavaI
MUNICIPALITY O
Community Development Department
Development Services Division
On -Site Water & Wastewater Program
f
Phone: 907-343-7904
Fax: 907-343-7997
ON-SITE SEWERIWELL PERMIT APPLICATION
Parcel I.D. 018-241-14
Property owner(s) George & Amy Brun Day phone
Mailinq address 2435 Clements Drive Anchorage, AK 99516
Site address same
Legal description (Sub'd., Block & Lot) Turnagain Park #2 B1 L5
Legal description (Township, Range & Section)
Lot Size 13,831 Sq. Ft. Number of Bedrooms 3
APPLICATION IS FOR:
APPLICATION IS AN:
TYPE OF DWELLING:
(® all that apply)
Absorption Field
❑X
Initial ❑
Single Family (SF) ❑X
(w/wo ADU)
Septic Tank
❑X
Upgrade ❑X
(D) F-1
Holding Tank
❑
Renewal ElDuplex
Multiple Dwellings ❑
Privy
❑
(SF and/or D)
Private Well
❑
Water Storage
❑
THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR:
Drain Field to lot line
Distance: 3p 0
I certify that the above information is correct. I further certify that this is in accordance with
applicable Municipal Codes.
(Signature of property owner or authorized agent)
Permit/Rush Fees: Waiver Fees: !� a a 5 ,
Date of Payment: ) -Z�i' Z I Date of Payment: �Tl 1 Q O21
Receipt Number: O 4 07 9 C2 Receipt Number: 030-1 G
Permit No. 25P2 1 1016 Waiver No, O SV Q i i ocn
Permit App_:- :• :-.,:c
Pannone Engineering ServiceS Lac
Steven R. Pannone, Principal
Registered Professional Engineer
E-mail: steveC@panent?ak.com
Municipality of Anchorage
Development Services Department
On -Site Water & Wastewater Program
4700 Elmore Road
P. Q. Box 196650
Anchorage, Alaska 99519
Subject: Turnagain Park #2 B1 L5
Septic System Upgrade Permit Request
Design Narrative
Mnicipality of And-oroge
On-site water and Wastewater
REVIEWED FOR CODE CONPUANCE
OSP21IOld f becca Carydf, 07140'29
21 January 2021
This is a design narrative far a permit to install a septic system upgrade on the subject property. The proposed
upgrade will serve an existing three-bedroom (3) house. This lot and surrounding lots are served by private wells.
Currently there are no wells within 100 feet of the proposed upgrade.
1. Soils:
A test hole was performed on this lot by Stephen D. Shrader, PE on 9/29/1980, and by Garness Engineering Group
(GEG) in 2010. There is no soils fog available for the GEG test hole however, the groundwater monitoring tube is stili
on the property and in operating condition. The monitor tube was inspected by Pannone Engineering anti found be
dry. Available surrounding test hole data shows similar soil profiles and percolation rates to those used to design this
septic system upgrade. Pannone Engineering will perform a test hole during construction of the upgrade to confirm
the soil profile and percolation rate. Based on the results of the Shrader test hole, historical data, and the selection
of the proposed drain field; an appiication rate of 1.2 galfonslday/square feet was used for a conventional
wastewater system in the area of the test hole.
2. Soil Absorption System Design.
a. See Sheet 1 of the design package.
3. Surface Water:
There is no surface water within 100 feet of the proposed septic tank and drain field.
4. Topography: See attached site plan for area topography.
5. Waivers:
Due to area constraints on the lot the proposed drain field upgrade encroaches on the north property line. The
distance required by AMC 15.65 is 10,0'. we are requesting a waiver to 2.5' from the proposed drain field to the
north property line on the subject lot. Granting this waiver will not pose a threat to public health on this or
surrounding lots.
Mailing: P.O.Box 1807, Palmer, AK 99645
Telephone: (907) 745-8200 FAX: (907) 745-8201
Page 2 of 2
6. Drawing Markings: The Drawings are marked "For MoA Review Only". When written notification that the review
is complete and no further comments are received from MoA On -Site Department, the note will be removed and
"For Construction" drawings will be issued.
The proposed installation will not affect the future development of this or the surrounding lots.
If you have any questions or concerns, please contact me at 745-8200.
Sincerely,
Steven R. Pannone, P.E.
Owner/Civil Engineer
Mailing: P.O.Box 1807, Palmer, AK 99645
Telephone: (907) 745.8200 FAX: (907) 745-8201
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP211016, Rebecca Carroll, 02/10/21
MUNICIPALITY OF ANCHORAGE
DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTECTION
ENVIRONMENTAL ENGINEERING DIVISION
825 L Street - Anchorage, Alaska 99501 Telephone 2644720
ON-SITE SEWAGE DISPOSAL SYSTEM AND/OR WELL INSPFCTInal RFPnRT
NAME / oo'
0
/--PHONE
f /�
EW
❑ UPGRADE
MAILING ADDRESS ` / V
LEGAL DESCRIPTION
LOCATION
0-60NO.
Well Absorption area
OY DISTANCE TO:
PX-
OF BEDROOMS
3
cc�/ Dwelling PERMIT NO. ,b2 160YO
wzz
~
Manufacturer
Material
No. of compartments 2
N
Liq. capacity in gallons
00
IF HOMEMADE:
Inside length
Width
Li ui
q ddepth
6 Y
J(7z
DISTANCE TO:
Well
Dwelling
PERMIT NO.
2 zFQ-
Manufacturer
Material
Liquid capacity in gallons
D
X
u z
Q ¢
F-
C331-57--_
W
0
Well
DISTANCE TO: �(��
No. of lines Length of each Ii
/ i9
Top of the to finish grade
Length Width
Foundation Nearest lot lin-Ae
/UUr.�r{/ z
Total Total length of lin s Trench width
�3 �9 inches
Material beneath rile /
-Depth
PERMIT NQ.!
Distance between lines �/ //j
�L' �7
Total effective absorption area '
7-5
PERMIT NO.
i F-
wa
Type of crib
Crib diameterCrib
depth
Total effective absorption area
rn
DISTANCE TO:
Well
Building foundation
Nearest lot line
J
Clase�j� UF1E
Depth 7
f
Driller
Distance to lot line
PERMIT NO.
DISTANCE TO:
Building foundation
Sewer line
Septic tank
Absorption areasI
OTHER
PIPE MATER/IACs
IOGiwS C .
E
SOIL TEST RATING
92
^/
INSTALLER
REMARKS
,a
hr
t
z
rR
no
o
,e
OVE
E�� "
n-nts rRa„ anal ,
DATE LEGAL
a /2
9-°'91-_19°-9 117 19=" 1=19- _ I T Ne CiP
vccr-ri.. r_... . i r, , ,,, "-grimur-4MEgTAL 'ROTE .._
825 '`/ STREET: ANCHORAGE, Ak:.
264-4720
t,.g9=9._9� 1=1!AE> eDr4-- 11-9� E=NJE FT 1=•� rwool im w l f� �ur�
PERMIT NO. 811=1048 ? Outn
- J ISO
APPLICANT GLORIA B. THOMPSON 617 N. IRVIN ST ;_77
' fil
LOCATION OLD & NEW SEWARD HIWYS �u AI
LEGAL LO B1 TURNAGAIN PARK #c LOT SIZE 12800 SQUARE FEET'
TYPE OF SOIL ABSORPTION SYSTEM IS: TRENCH
MAXIMUM NUMBER OF BEDROOMS = _ =OIL RATING <SQ FT/BR)= 125
THE RE?UIR.ED SIZE OF THE _:OIL_ ABSORPTION SYSTEM IS:
E-a9-F"-9-fA—= A El 9_E�94C3-FFI _1. 13FQFA °E=9_ ESE=F`-'ThA== N_,
THE LENGTH DIMENSION IS THE LENGTH (IN FEET) OF THE TRENCH OR DRAINFIELD.
THE DEPTH OF A TRENCH OR PIT IS THE DISTANCE BETWEEN THE SURFACE OF THE
GROUND AND THE BOTTOM OF THE EXCAtrATION ON FEET).
THERE IS NO SET WIDTH FOR TRENCHES.
THE GRAVEL DEPTH IS THE MINIMUM DEPTH OF GRAVEL BETWEEN THE OUTFALL- F'IF'E
AND THE BOTTOM OF THE EXCAVATION (IN FEET).
F=° E =1 �a LJ "F FZ E 9" a r ' T 3 rt T FA p-.9 AZ _`: 1 T 9= = AL1A-e CA CA 13 FA 9-"_ Cl r4 I=
PERMIT- AP'P'LICANT HAS THE RESF'ONSIBILITY TO INFORM THIS DEPARTMENT DURING THE
IN`.TALLATION INSPECTIONS OF ANY WELLS ADJACENT TO THIS PROPERTY AND THE
NUMBER OF RESIDENCES THAT THE WELL WILL SERVE.
T ._. T 9s-9171 c: _, T 14 in F=* E CD T 1 13 rA in 1'=1 FR Eo 9 � " EO G-41_1 >I F� EF_ L:�
BACKFILLING OF ANY SYSTEM WITHOUT FlNAL INSPECTION AND APPROVAL BY THIS
DEPARTMENT WILL BE SUBJECT TO PROSECUTION.
MINIMUM DISTANCE BETWEEN A WELL AND ANY ON-SITE 'SEWAGE DISPOSAL SYSTEM IS
100 FEET FOR A PRIVATE WELL OR 150 TO 200 FEET FROM A PUBLIC WELL DEPENDING
UPON THE TYPE OF PUBLIC WELL.
MINIMUM DISTANCE FROM A PRIVATE WELL TO A PRIVATE SEWER LINE 15 25 FEET AND
TO A COMMUNITY SEWER LINE IS 75 FEET"
WELL LOC,- ARE REQUIRED AND MUST BE RETURNED TO THE DEPARTMENT WITHIN 30 DAY'S
OF THE WELL COMPLETION.
OTHER REQUIREMENTS MAY APPLY. SPECIFICATIONS AND CONSTRUCTION DIAGRAMS ARE
AVAILABLE TO INSURE PROPER INSTALLATION.
r= FEE 9=_ lrl I T Es 11 9-'° I FZ EE E> En C3 EO 81 Ea 9= 90 =J _ fl- S-0 wofflL
I CERTIFY THAT
1: I AM FAMILIAR WITH THE REQUIREMENTS FOR ON-SITE SEWERS AND WELLS AS SET
FORTH BY THE MUNICIPALITY OF ANCHORAGE.
I WILL INSTALL_ THE SYSTEM IN ACCORDANCE WITH THE CGDE_.
_: I UNDERSTAND THAT THE ON-SITE 'SEWER SYSTEM MAY REQUIRE ENLARGEMENT IF THE
RESIDENCE IS REMODELED TO INCLUDE MORE THAN 3 BEDROOMS.
SI
IS:
[N SOILS LOG
MUNICIPALITY OF ANCHORAGE
DEPARTMENT OF HEALTH AND ENVIRONMENTAL PROTECTION PERCOLATION
TEST
Pouch 6-650, Anchorage, Alaska 99502 276-2221
SOILS LOG —PERCOLATION TEST ASI NO. 01980
PERFORMED FOR: Mrs. Gloria Thompson DATE PERFORMED: 9/25/80
LEGAL DESCRIPTION: Lot 5, Block 1, Turnagain Park Subdivision No. 2
SLOPE SITE PLAN
u♦yo.iiiu 0.5
t Organic Silt Brown 1.5 d
2 Gray Silt
2.5 —
3 o
0.0 "
�/
o °o Silty Sandy
5 ° ��° Gravel
p/dam (Dense)
6 w/Boulders
.01,07,10O
7 0'O0'°
. OD
8 �v
9 r�'J
, a o--
Od�j Clements Drive
18
X10, q/Q -
I 1 '� WAS GROUND WATER ND 5_ I! ,
'° ENCOUNTERED? L.
�� O I
// P {
12 E 7
Y�—
°A 0• IF YES, AT WHAT N/A011
_
Q'0 DEPTH?
13 p J --
0 0
14o•.0 14.
T.D.
01- �2 ��
` t�
°. �.
S4pl:en D. Shrader
No. 4143-E
19 �� c9°°°0°...° °..•° °•��,�
Reading Date
Gross
Time
Net Depth to
Time Water
Net
Drop
00.0
3:40
'
0.43' -
5:10 10
0.18'
t
4:10
6.0 FT AND 7.3 FT
5:mi.rVinch Pere.rat
COMMENTS Test Material was
4:20
10
0.28'
0.78
4:30
less silt.
I
4:30
0.50'
4:40
10
0.25'
Test
Ho
Ie
4:50
i
M
t'1
co
n
m
M
i
I
I
0a.0
LJ
, a o--
Od�j Clements Drive
18
X10, q/Q -
I 1 '� WAS GROUND WATER ND 5_ I! ,
'° ENCOUNTERED? L.
�� O I
// P {
12 E 7
Y�—
°A 0• IF YES, AT WHAT N/A011
_
Q'0 DEPTH?
13 p J --
0 0
14o•.0 14.
T.D.
01- �2 ��
` t�
°. �.
S4pl:en D. Shrader
No. 4143-E
19 �� c9°°°0°...° °..•° °•��,�
Reading Date
Gross
Time
Net Depth to
Time Water
Net
Drop
0.30 9/25
3:40
0.43' -
5:10 10
0.18'
0.30
4:10
6.0 FT AND 7.3 FT
5:mi.rVinch Pere.rat
COMMENTS Test Material was
4:20
10
0.28'
0.78
4:30
less silt.
4:30
0.50'
4:40
10
0.25'
4:50
20
®�®ROfib �
U
U.
0.43' -
5:10 10
0.18'
TEST RUN BETWEEN
6.0 FT AND 7.3 FT
5:mi.rVinch Pere.rat
COMMENTS Test Material was
well compacted
with some layers more
sandy and
less silt.
PERFORMEDBY: Harry Bates CERTIFIEDBY: Stephen D. Shrader P,.FyATE: 9/26,1980
Alaska bolls Investigations
624 W. Intl Airport Rd. Suite 103
72-008 (7176) Anchorage, AK 99502
MUNICIPALITY OF ANCHORAGE
Development Services Department Phone: 907-343-7904
On -Site Water & Wastewater Section Fax: 907-343-7997
Certificate of On -Site Systems Approval
Parcel I.D. 018-241-14
1. GENERAL INFORMATION
Expiration Date:
Complete legal description TUrnagain Park #2 131 L5
Location (site address) 2435 Clements Drive
Current property owner(s)
Mailing address
Real estate agent
2. TYPE OF DWELLING:
0 Single Family (w/wo ADU)
❑ Duplex
❑ Multiple Dwellings (Single Family and/or Duplex)
3. NUMBER OF BEDROOMS: 3
Day phone
Day phone
4. TYPE OF WATER SUPPLY:
TYPE OF WASTEWATER DISPOSAL:
Private Well
0
Private Septic
0
Water Storage
❑
Holding Tank
❑
Community Well
❑
Community
❑
Public Water System
❑
Public Sewer
❑
Waiver request for: Distan
Received by: Date:
COSA to be released to the engineer, unless otherwise requested by the engineer.
COSA Fee $ Waiver Fee $
Date of Payment S �c� �2' Date of Payment
Receipt Number Receipt Number
COSA # 0 5 C Q 91.2 q Waiver #
5. STATEMENT OF INSPECTION BY ENGINEER
As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures
outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or
wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated
herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and
inspection, the on-site water supply and/or wastewater disposal system is (are) in compliance with all applicable Municipal and State
codes, ordinances, and regulations in effect at the time of installation.
In conducting an adequacy test, I attempt to provide a thorough, conscientious engineering analysis of the system in accordance with MoA
COSA guidelines and regulations. The reported results describe the performance of the system under the conditions encountered at the time
of the test, and separation distances measured to readily identifiable features. The operational life of all wells and septic systems depend on
the local soil condition, ground water levels that may fluctuate during the year, and the water usage of the family being served by the system.
These conditions are outside the control of the evaluator of this system. All systems eventually fail and satisfactory test results do not
guarantee future performance of the system, nor do they guarantee that there are no hidden defects or encroachments. Therefore we cannot
provide any warranty for future performance, nor can we estimate remaining life of the system. The content of this report is for the sole
benefit of the owner listed above. Reliance on this report by another person is at their own risk. Pannone Engineering Services LLC highly
recommends buyers hire their own engineer to evaluate this report.
Name of Firm Pannone Engineering Services
Address P.O. Box 1807 Palmer, AK 99645
Engineer's Printed Name Steven R. Pannone P.E.
DSD SIGNATURE
System #1 Approved for bedrooms
System #2 Approved for bedrooms
Disapproved
Phone (907) 745-8200
Date
OF ALgSIt��
:A H
...... .... o.. .....
Steven •R�•Pannorie
I � CE 87 49 - ,
'n0FES9.G,®J��
Conditional approval for bedrooms, with the following stipulations:
Ut- Ah,
w-
nN-SITE
WATER 0
Original Certificate Date:
The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the
representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is
not responsible for errors or omissions in the professional engineer's work.
7. ATTACHMENTS:
COSA Checklist X Nitrate Advisory
Septic System Advisory Arsenic Advisory
Well Flow Advisory Other
COSA Checklist blue sheet
COSH Checklist
Legal Description: Turnagain Park #2 B1 L5 Parcel ID: 018-241-14
If more than 1 septic system on lot: COSA Checklist # 1 of 1 Structure served by this system 1
A. WELL DATA
❑ Well log is filed with Onsite (or attached)
Date drilled `1980
Total depth 110+ ft
Cased to 110+ ft
Sanitary seal is functioning correctly
0 Wires are properly protected
Casing height (above ground) in.
Date of flow test for COSA 78012020
Well production at time of test 3.7+* gpm
Water storage tank volume n/a gallons
Well disinfected for coliform test? ❑ Yes ❑✓ No
H Coliform bacteria is Negative
Nitrate mg/L Fffl� Nitrate less than MRL (ND)
Arsenic 1.58 ug/L ❑ Arsenic less than MRL (ND)
Collected by Pannone Engineering
Date of Sample 4/7/21
Static water level at beginning of test 92.2* ft.
Comments *Data collected from Garness Engineering Group, Ltd inspection letter
B. TANK DATA
Age of tank(s) <1 years
Tank type/material 5e ff�9
Measured operating fluid level in septic tank MA
0_1 Standpipes/foundation cleanout per record drawing
Date of pumping New System
D. ABSORPTION FIELD DATA Wide Trench
C. LIFT STATION
❑ Required maintenance completed
Age of lift station years
Lift station material
Comments:
Which system tested (date installed) 5/5/2021 Adequacy test date New
Q ALL standpipes present per record drawing Results ❑Pass For bedrooms
Total measured depth from grade 8 ft (max) Fluid depth prior to test in
Measured depth to pipe invert from grade 4 ft (min) Water added gal
❑ N/A — pressurized field
New depth in
Q Monitor tubes go to bottom of effective. If not, state Elapsed time min
depth into effective
Q Code -required soil cover over field Final fluid depth in
❑ System presoaked Absorption rate gpd
(Required if vacant for greater than 30 days prior to Any rejuvenation treatment (past 12 months) no
date of test) If yes, enter date
Gallons introduced gallons
Comments/Deficiencies: System is brand new and does not need an adequacy test
COSA Checklist yellow sheet
E. SEPARATION DISTANCES
From Private Well on Lot to: (Please enter distances if less than required or if community well)
Septic Tank/Lift Station on Lot > 100'
❑✓
Yes
Community Sewer Manhole/Cleanout > 100'
❑✓ Yes
if No
ft
❑ Yes
if No
Neighboring Tank > 100' Q Yes
if No
ft
Private Sewer/Septic Line > 25' ❑ Yes
if No
Absorption Field on Lot > 100' ❑ Yes
if No
ft
Holding Tank > 100' Q Yes
if No
Neighboring Absorption Fields > 100'
Yes if No.
Water Main > 10'
Animal Containment > 50' ❑✓ Yes
if No
❑✓ Yes
if No
ft
✓❑ Yes if No.
Water Service Line > 10'
❑✓
Yes
if No
Manure/Animal Excreta Storage > 100'
If septic tank is under driveway comment below
Community Sewer Main > 75' ❑✓ Yes
if No
ft
[Z] Yes
if No
From Septic/Holding Tank on Lot to: (Please enter distances if less than required)
Building Foundations > 10'
❑✓
Yes
if No
ft
Surface Water > 100'
Q Yes if No.
Property Line > 5'
0
Yes
if No
ft
Wells on Adjacent Lots:
ft
Absorption Field > 5'
P/1
Yes
if No
ft
Private Wells > 100'
Yes if No.
Water Main > 10'
0
Yes
if No
ft
Community Wells > 200'
✓❑ Yes if No.
Water Service Line > 10'
❑✓
Yes
if No
ft
If septic tank is under driveway comment below
From Absorption Field on Lot to: (Please enter distances if less than required)
Building Foundation > 10' 21 Yes if No ft If absorption field is under driveway comment below
Property Line > 10'
❑ Yes
if No 5.1
ft
Wells on Adjacent Lots:
Water Main > 10'
✓D Yes
if No
ft
Private Wells > 100' ❑✓ Yes if No
Water Service Line > 10'
❑✓ Yes
if No
ft
Community Wells > 200' El Yes if No
Surface Water > 100'
0 Yes
if No
ft
F. ENGINEER'S COMMENTS
G. ENGINEER'S CERTIFICATION
I certify that I have determined through field inspections and review
Of Municipal records that the above systems are in conformance with
MOA COSA guidelines in effect on this date.
COSA Checklist yellow sheet
16
4�H'�
�
S even R"Po*n' one
CE 8149
ft
ft
ft
ft
ft
ft
ft
ft
ft
ft
Municipality of Anchorage
• Development Services Department
Building Safety Division
On -Site Water and Wastewater Program
4700 Bragaw Street
P.O. Box 196650
Anchorage, AK 99519-6650
www.muni.org/onsite
(907) 343-7904
CERTIFICATE OF ON-SITE SYSTEMS APPROVAL
FOR A SINGLE FAMILY DWELLING
Parceil.D._01R-241-14 COSA# (2RD0"I5
Expiration Date: r LLQ O — D S
1. GENERAL INFORMATION '
Complete legal description ._ 7VRNAGAIN
PARK f 2 LOT 5 BLOCK 1
Location (site address) 2435
CLEMENTS
DRrVE. ANCHORAGE exp 9951
— Current Property owners) PAIJI.
J. i.1(:HT
Day phone
Mailing address 3915
W 79T" COURT
ANCHORAGE. AK 99502-4205
Lending agency
Day phone
Mailing address
Real Estate Agent TERRI
RARRUS
Day phone _562-3638
Mailing Address _664313RAYTONDRIVE
ANCHORAGE, err 2507
Unless otherwise requested, COSA will be held by DSD for pickup.
2. NUMBER OF BEDROOMS:
3
3. TYPE OF WATER SUPPLY:
TYPE OF WASTEWATER DISPOSAL:
Individual Well
®
Individual On-site
Individual Water Storage
❑
Individual Holding Tank
Community Class Well
❑
Community On-site
Public Water System
❑
Public Sewer
The Municipality of Anchorage Development Services Department (DSD) issues Certificates of On -Site Systems
Approval (COSA) based only upon the representations given in paragraph 4 by an Independent professional
civil engineer registered in the State of Alaska. Certificates of On -Site Systems Approval are required for the
transfer of title (except between spouses) for properties served by a single-family on-site wastewater disposal
and/or water supply system. DSD also issues COSAs upon request to homeowners. Certificates of On -Site
Systems Approval are valid for 90 days from the date of issue for properties served by a private or Class C well
and may be reissued with new water sample results. (Certificates may be reissued for a period of up to one
year with valid water samples.) Certificates are valid for one year for properties served by Class A or B wells or
a public water system. The Municipality of Anchorage is not responsible for errors or omissions in the
professional engineer's work.
4. STATEMENT OF INSPECTION BY ENGINEER
As certified by my seal affixed hereto and as of the validation date shown below, I verify that my
Investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for
this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe,
functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify
that based on the information obtained from the Municipality of Anchorage files and from my investigation
and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all
applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation.
Name of Firm ArcTeffa Engineering & Surveying. Inc. Phone 868-3792
Address 20441 PTARMIGAN BLVD EAGLE RIVER, AK 99577
Engineer's Printed Name KENNETH M DUFFUS Date 02/29/2008
Engineer's Comments: This investigation was completed in compliance with ADEC and MOA regulations.
The assessment of the condition of the well and septic applies only to the conditions as of the day tested.
The flow and absorption rates may change due to subsurface conditions that may not be observed from
the surface, changes inland use, local soil characteristics, groundwater levels that may fluctuate during the
year and the water usage of the family being served by the system. The operational life of all well and
septic systems are subject to these various and dynamic characteristics and are outside the control of the
evaluator of the well and septic system. Therefore,
ArcTerra can not give any estimate of how long a
!Q'CE'�� pF A\tq 11�
system will function satisfactory for current or future .�..•«•••.
occupants or can ArcTerra guarantee that no unseen M y,,.• •'Vol
encroachments, deficiencies or discrepancies exist. r* iAnTu %. 4Ii
5. DSD SIGNATURE
Approved for bedrooms.
Disapproved.
Conditional approval for bedrooms, with the following
vivvn c
WATERAND •;
Attachments:
COSA Checklist X Arsenic Advisory
Septic System Advisory Maintenance Agreements
Well Flow Advisory Supplemental Engineer's Report
Nitrate Advisory Other
By: Original Certificate Date: b — O 8
(a« ,, as
Municipality of Anchorage
• Development Services Department
Building Safety Division
Onsite Water & Wastewater Program • • ..
4700 Bragaw Street
P.O. Box 196650
Anchorage, AK 99519-6650
www.muni.org/onsite
(907) 343-7904
CERTIFICATE OF ON-SITE SYSTEMS APPROVAL CHECKLIST
Legal Description: TURNAGAIN PARK a 2. I OT 5 Bli O K 1 Parcel ID: 018-241-14
A. WELL DATA
Well type PRIVATE If A. B, or C provide PWSID # _
Date completed 19so+J- Sanitary seal (Y/N) y
Total depth UNKNOWN ft. Cased to •40+ ft.
FROM WELL LOG
Date of test
Static water level
Well production - - 9 -p.m -
WATER SAMPLE RESULTS:
1 •- . . r . . rrt
Wires properly protected (Y/N) y
Casing height (above ground) 36 in
AT INSPECTION
91 ft.
7.6 g.p.m.
Coliform _Q—colonies/100ml. Nitrate ND mg/L Other bacteria _0 colonies/100 mL
Arsenic: mg/I Date of sample: 02/22/2oo9 Collected by: ArcTerra
B. SEPTIC/HOLDING TANK DATA
Tank Type/Material Septic/Steel Date installed o4/3o/1961 Tank size 1000 gal.
Number of Compartments y Cleanouts (YIN) y Foundation cleanout (YIN) y Depression over tank (Y/N) r[ _
High water alarm (Y/N) N --Pate of pumping 02/22/2008 Pumper McDonald,;
C. ABSORPTION FIELD DATA
Date installed 4/3o/1981 Soil rating (g.p.d./f? or fe/bdrm)125 System type Deep Trench
Length _3b-_ ft Width _a ft.' Gravel below pipe &ft. Total depth 13 ft. (measured 2/23/08)
Eff. absorption.area 3gfe Monitoring tube y
Date of adequacy test 2123/08
Depression over field X
Results (Pass/Fail) rass For L. bedrooms
Fluid depth in absorption field before test 4M in. Water added.= gal. New depth 69.6Jn.
. Elapsed Time: 1411 min. Final fluid depth !UA in. Absorption rate >=450+g. d.
P•
Any rejuvenation treatment (past 12 mo.) (Y/N & type) N If yes, give date .....
D. LIFT STATION
Date installed
Manhole/Access (Y/N)
Size in gallons_
'Pump on' level at—in. 'Pump off" level at—in. High water alarm level at—in.
Datum Cycles tested Meets alarm & circuit requirements?
E. SEPARATION DISTANCES
SEPARATION DISTANCES FROM WELL ON LOT TO:
Septic tank/lift station on tot 100'+ - On adjacent lots 100'+
Absorption field on lot 100'+
Public sewer main y5'+
Sewer /septic service line 25'+
On adjacent lots 100'+
Public sewer manhole/cleanout
Holding tank 100'+
Animal containment areas sn'+ Manure/animal excrete storage areas 100'+
SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO:
Building foundation 5'+ Property line 5+ Absorption field 5'+
Water main 10'+ Water service line 10'+ Surface water 100'+
Wells on adjacent lots 100'+
SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO:
Property line 10'+ Building foundation 10'+ Water main 10'+
Water Service line 101+ Surface water t00'+ Driveway, parking/vehicle storage 10'+
Curtain drain 50'+ (None Known) Wells on adjacent lots 100'+
F. COMMENTS
*A Row WELL DOCUMENTATION LETTER Vacant residence wastewater syclem was surcharged
G. ENGINEER'S CERTIFICATION
I certify that I have determined through field inspections and
review of Municipal records that the above systems are in
conformance with MOA COSA guidelines in effect on this
date.
Engineers Printed Name KENNETH M. DUFFUS
Date 0212912008
COSA Fee $430 0 Waiver Fee $ _
Date of Payment JIDo Date of Payment
Receipt Number )J0� Receipt Number.
(Rev. 11105)
..
SGS Ref.#
1080703001
Client lame
ArcTerra Engineering and Surveying
Project Name/#
Tumagain #2 Q1, L5
Client Sample ID
Tumagain #2 1)1, L5
Alam:
Drinking Water
PIVSID
0
Sample Remarks
All Dates/rimes are Alaska Standard Time
Printed Datelrime
03/05/2008 16:29
Collected Date/Time
02/22/2008 10:45
Received Datelrime
02/222008 11:20
Technical Director
Stephen C. Ede
Parameter
Results
PQL Units
Allowable
Method Container ID Limits
Prep Analysis
Date Date
Init
Metals by ICP/MS
Arsenic
ND
5.00 ug(L
EP200.8
C
(<10)
03/03/08 03/04/08
M11
Waters Department
Total Nitmte/Nitritc-N
ND
0.100 m8/L
SM204500NO3-P
D
(<10)
0227/08
LCP
Microbiology Laboratory
Colony Count
0
coV100ml,
SM20 92223
A
(<200)
0222/08
DLC
Total Coliform
0
col/100ml,
SM209222B
A
(<I)
0222/08
DLC
Fecal Coliform
0
coVI00mL
SM2092220
A
(<I)
0222/08
DLC
Cl
LOT 5
W
O
04
N 89'39'00" E 11
SEPTIC
• VENTS
•
1p'd
DECK/
CARPORT
3.4'x8'
CANT
LOT 5
BLK 1
N89'59'C
LOT 4
CO 1.0
2.2'x2.0'
o
F
FP CANT
00
010 S"0, --A G,
M
5���
0.10 1�
2'x6'
CAN
3
o.
4.5
O
OFGZeo
P
O
RAVEL
O
Z
D/W
fV
N
WEL®L
100.00'
CLEMENTS DRIVE
0
N
ANCHORAGE RECORDING DISTRICT
ASBUILT OF:
TURNAGAIN PARK SUBDIVISION NO 2
LOT 5, BLOCK 1 PLAT P -160A
SURVEY CERTEFICATE:1. John L. Schuller, Have conducted a
physical survey of this property as shown on this drawing and that the
improvements situated hereon are within the property lines and no
enchroulunnts exist other than noted Under no circurnstance should
any information on this drawing be used for construction of fences,
structures, improvements, or for establishing boundary lines.
EXCLUSION NOTES: It is the owners responsibility to determine
the existence of any easements, covenants, or restrictions which
do not appear on the recorded subdivision plat
1OXR rnota MUYBFA: Mx: xtic rrw
FEB 22. 2008 1'.30' ene.,peyu,.r
VO—VI I ++•ac ocamnc ZWKI I —
I aS 3033 001/16
'OF `4h
;7k� .... .A gtt'
..
OHN L SCHULLER:
LS -10408 +`i
FEE -27-2000 10:39A FRa9: 70:8;83793
P.1
AAROW PUMP & WER SERVICE, LLC q �G1dOo �C�G�
P.O. Box 110496
Anchorage, AK 99511
Office: (907) 346-0355 • Fax (907) 333-8976
Eagle River: (907) 622-9335 N° 07954
CUSTOMER JOB SITE
�- 4;
Y - 0 e o- i - _1 L- J
ICE DATE_- u
WELL DEPTH$WL
/
CKORMATEO PUWDEPTH .0
SA 5 RSQV
QUANTITY
DESCRIPTION
PRICE
AMOUNT
o WI to rex 0 ct
a -IL 11eq i a e 01 a I� W LLJ
01 to Op r Anz-1iH S
FEB 'l 7 20 a r �►r B
LABOR
HOURS
RATE
AMOUNT
TOTAL MATERIAL
TOTAL LABOR
WORK ORDERED BY
DATE COMP,
TOTAL
LABOR
/ _y
PAY THIS AMOUNT /
OO
Thank You
SIGNATURE r --
(I Hereby Acknowledge the Satisfactory Completion of the Above Doscribed Work and agree that It above work is not paid for In 90 days I agree to snow Aarow
Pump 8 Well Servke, L.L.C. the Mhl to remove unpaid for equipment and charge for labor already pedamied & labor to remove unpaid for equipment.)
TERMS: ACCOUNTS PAYABLE AT 10TH OF MONTH FOLLOWING PURCHASE.
SERVICE CHARGE AT RATE OF 1.5% PER MONTH WILL BE CHARGED ON OVERDUE ACCOUNTS.
Municipality of Anchorage
• Development Services Department
Building Safety Division
On -Site Water and Wastewater Program °
4700 South Bragaw St. 5 ° f '
P.O. Box 196650 Anchorage, AK 99519-6650
www.ci.anchorage.ak.us
(907)343-7904
ON-SITE SEWER/WELL SUBMITTAL COMMENT SHEET
To: Jeff Gamess
Legal description: Mann Block 2 Lot 2
❑Permit ®C.O.S.A. ElInspection Report
The attached paperwork has been reviewed and is being returned for the following reasons:
1. An absorption field may not be located within 10 feet of a building foundation.
2. Aseptic tank may not be located under a driveway or parking area.
Name of reviewer: Poet
Date: March 4, 2008
Please supply the necessary information and re -submit your request.
LEAVE THIS FORM ATTACHED TO THE PAPERWORK