HomeMy WebLinkAboutVANS BLK 3 LT 5B July 21, 1978 R&M No. 851561 Marston Real Estate 2060 West Dimond Boulevard Anchorage, Alaska 99502 Attention: Bob Debaker ~ Re: Adequacy Test on Existing Sanitary Sewer System; E 1/2, Lot 6, Block 3, Vans Subdivision, Anchorage, Alaska. Dear Mr, Debaker: At your request of July 17, 1978, we conducted a test of the septic system on the above described property. During this test the liquid level in the septic tank was monitored as water was added to the system. The measurements are summarized in the following table: Liquid Level Below Top Total Gallons Time of Standpip~ Added 9:13 10.0 0 9:20 9.8 25 9:36 9.8 75 9:50 9.75 125 10:00 9.7 175 10:14 9.8 175 10:30 9.8 175 The meter used during the test was a Rockwell 5/8" standard water meter which had previously been calibrated by R&M Consultants, Inc. If the 2 bedroom residence on the property is to house 4 people, the average load on the system can be expected to be 300 gallons per day or .21 gallons per minute. During the test, the system accepted 175 gallons in 77 minutes. This indicates an average effluent acceptance rate of approximately 2.3 gallons per minute at the time of the test. Because the house on the lot is occupied, we assu~e that the leach field was at its normal degree of saturation. We can therefore conclude that the system is disposing of effluent at an adequate rate for a 2 bedroom residence. July 21, 1978 Marston Real Estate Page -2- We appreciate this opportunity to be of service to you. Please contact us if you have any questions concerning this test or if we can be of additional service. Very truly yours, Lynne Kosikowski Gary Smith Staff Geologist Project Manager JMB/kah GREATER ANCHORA,,~, AREA BOROUG'~-~, HEALTH DEPA~:T~IENT 327 EAGLE STREET ANCHORAGE, ALASKA 99501 CASE Performed For ~, ~-7~_aC-f?--- ~, '~UA/~ Date Performed negal,Deserlp'tlon: Lot~lock.~,_$ubalvlsion ¥./~A/ .... This ~e~m Reports a: Soxls Log ~, ~ · .Percolation Tesz Depth Feet Soil Characteristics Location Sketch ........J J,, 1, J Readlng Date Gmoss Time Net Time Depth To H20 Net Drop .~rcola%ion ~a~e 1,,/ , , ~41nnt'~ Proposed Instal~Seepage Pit ~" Drain field ,~ ' Depth' Of inlet , ])ep~h To B~it Or '!l~4ench .... COMMENTS: ~V[~d, iurn to, slow perc0]atioq __i 2~5 sqU~ fe~t ,of ~eepage Test Pemformed B~: Alaska Geological Consultants ALASKA GI---OLOGICAL CONSULTANTS May 20, 1970 Mr. George R. Jones 8140 Briarwood Anchorage, Alaska Re: Percolation characteristics of soils, E½ Lot 6, Block 3, Van Subdivision Dear Mr. Jones: The attached report presents the results of an investigation of the '. percolation characteristics of soils on your building site. On the basis of this investigation we conclude that 225 square feet of seepage area per bedroom will be required. Very truly yours, ALASKA GEOLOGICAL CONSULTANTS ': ' BGP:js B~ce G, PUrcell / cc: GAAB Health Department Attach. JUly 17¢ 197~ Subject: East % of ~m~ 6 }~lock 3 Va~s subdivision the following r~aaons ~ are~. The ~it ~ b~ one-hun~re~(100) feet araa, t~ ~ two(2) f~r~ that perform ~he test If there ~e any question~, plea~ contact this ~l~cerely~ ~3anit ar ~an Date ALASKA '~'ARTMENT OF HEALTH AND SOCIAL~ SEI~"~ES DIVISION OF PUBLIC HEALTH Lab. No. BACTE RI 0 LOGICAL~-WATE R ANALYSIS Office PLEASE MAIL RESULTS TO: NAME ; .~ ' :" ' ...... - " ADDRESS Sample eo~ected by ~c ( ~_..a Phone No. ~ ZIP CODE Date Collected Time _ Sampling Address Specific place of collection REASON FOR SAMPLE SUBM/SSION: [] nlness suspected [] Hialth Regulated F~blishment [-~-Other ~- ~-~' WATER SAMPLE SOURCE [] Well Type of casing ~ Improved (Enclosed, Covered) Spring --] Surface (Reservoir, stream, lake) [] Holding Tank [] Other Analysis shows this'WATER SAMPLE to be: [~]~atisfac~o~ . [] Unsatisfactory [] Questionable [] submit other sample [] Sample too long in transit to indicate reliable results. Sample should nol be over 48 hours old at time of examination. [] B6{ile broken or leaked in transit. [] Other SANITARIAN'S REMARKS Sanitarian's Signature: ~EAD INSTRUCT ONS BEFORE _COLLECTING SAMPL 06-1220 lb) BAC~TERIOLOG ICAL WATER A qALY5 IS RECORD Date Collected -: ___ Source Date Received Time Received ~,m. Lab, NO.~ Presumptive ~ 24 Hours . _Confirmatory ., , , EMB Multiple Tube Report: J verification: LTD Final Membraq~ ?~ter Results ~roth 24 hours: Broth 48 hours: lOml Tubes posinve/Tota lOml Portions MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTECTION 825 L Street - Anchorage, A~aska 99501 ENVIRONMENTAL ENGINEERING DIVISION Telephone 264-4720 REQUEST FOR APPROVAL OF INDIVIDUAL WATER AND SEWER FACILITI'ES DIRECTIONS: Complete all parts on page 1. Incomplete requests will not be processed. Please allow ten (10) days for processing. 1. PROPE T OWNER PHONE ~ 3. LENDING INSTITUTION -- PHONE · . REALTOR/AGENT /IAI LING ADDRESS 5. LEGAL DESCRIPTION STREET LOCATION S. TYPE OF RESIDENCE NUMBER OF BEDROOMS ~[~SI N [] One [] Four GLE FAMILY [~'~'~wo [] Five [] MULTIPLE FAMILY [] Three [] Six [] Other [~ INDIVI DUAL* * ATTACH WELL LOG. A well log is required for all wells drilled [] COMMUNITY since June 1975. For wells drilled prior to that date, give well [] PUBLIC UTI LITY depth (attach log if available,) 8. SEWAGE DISP~)S~AL SYSTEM (~ INDIVI DUAL/ON-SITE** PUBLIC UTILITY **If individual/on-site, give installation date. If system is over two (2) years old an adequacy test is required by this Department, NOTE: THE INSPECTION FEE MUST ACCOMPANY EACH REQUEST BEFORE PROCESSING CAN BE INITIATED. 72-010(3/78) THIS SIDE FOR OFFICIAL USE ONL. DATE RECEIVED INSPECTION APPOINTMENTS TIME TIME TIME DATE DATE DATE INSPECTOR INSPECTOR INSPECTOR DIRECTIONS: I. TYPE OF RESIDENCE NUMBER OF BEDROOMS [] SINGLE FAMII~Y [] ONE [] THREE [] FIVE [] OTHER [] MULTIPLE FAMILY [] TWO [] FOUR [] SIX PERMIT NUMBER 2. WATER SUPPLY [] INDIVIDUAL DEPTH OF WELL [] COMMUNITY DATE DRILLED [] PUBLIC UTILITY Connection Verified LOG RECEIVED 3. SEWAGE DISPOSAL SYSTEM PERMIT NUMBER DINDIVIDUAL/ON -SITE DATE INSTALLED []PUBLIC UTILITY Connection Verified INSTALLER [~Septic Tank or [] Holding Tank Size: If Tank is h(~memade SOILS RATING give dimensions: TYPE OF TANK MANUFACTURER TOTAL ABSORPTION AREA MATERIAL 4. DISTANCESwELL TO: Septic/Holding Tank Absorption Area Sewer Line Nearest Lot Line Absorption Area to nearest Lot Line 5. COMMENTS [] DISAPPROVED LEGAL DESCRIPTION 72-010 (Rev, 3/78)