July 21, 1978 R&M No. 851561
Marston Real Estate
2060 West Dimond Boulevard
Anchorage, Alaska 99502
Attention: Bob Debaker ~
Re: Adequacy Test on Existing Sanitary Sewer System; E 1/2, Lot 6,
Block 3, Vans Subdivision, Anchorage, Alaska.
Dear Mr, Debaker:
At your request of July 17, 1978, we conducted a test of the septic
system on the above described property.
During this test the liquid level in the septic tank was monitored as
water was added to the system. The measurements are summarized in the
following table:
Liquid Level Below Top Total Gallons
Time of Standpip~ Added
9:13 10.0 0
9:20 9.8 25
9:36 9.8 75
9:50 9.75 125
10:00 9.7 175
10:14 9.8 175
10:30 9.8 175
The meter used during the test was a Rockwell 5/8" standard water meter
which had previously been calibrated by R&M Consultants, Inc.
If the 2 bedroom residence on the property is to house 4 people, the
average load on the system can be expected to be 300 gallons per day or
.21 gallons per minute. During the test, the system accepted 175 gallons
in 77 minutes. This indicates an average effluent acceptance rate of
approximately 2.3 gallons per minute at the time of the test.
Because the house on the lot is occupied, we assu~e that the leach field
was at its normal degree of saturation. We can therefore conclude that
the system is disposing of effluent at an adequate rate for a 2 bedroom
residence.
July 21, 1978
Marston Real Estate
Page -2-
We appreciate this opportunity to be of service to you. Please contact
us if you have any questions concerning this test or if we can be of
additional service.
Very truly yours,
Lynne Kosikowski Gary Smith
Staff Geologist Project Manager
JMB/kah
GREATER ANCHORA,,~, AREA BOROUG'~-~,
HEALTH DEPA~:T~IENT
327 EAGLE STREET
ANCHORAGE, ALASKA 99501
CASE
Performed For ~, ~-7~_aC-f?--- ~, '~UA/~ Date Performed
negal,Deserlp'tlon: Lot~lock.~,_$ubalvlsion ¥./~A/ ....
This ~e~m Reports a: Soxls Log ~, ~ · .Percolation Tesz
Depth
Feet Soil Characteristics
Location Sketch
........J J,, 1, J
Readlng Date Gmoss Time Net Time Depth To H20 Net Drop
.~rcola%ion ~a~e 1,,/ , , ~41nnt'~
Proposed Instal~Seepage Pit ~" Drain field ,~ '
Depth' Of inlet , ])ep~h To B~it Or '!l~4ench ....
COMMENTS: ~V[~d, iurn to, slow perc0]atioq __i 2~5 sqU~ fe~t ,of ~eepage
Test Pemformed B~: Alaska Geological Consultants
ALASKA GI---OLOGICAL CONSULTANTS
May 20, 1970
Mr. George R. Jones
8140 Briarwood
Anchorage, Alaska
Re: Percolation characteristics of soils, E½ Lot 6, Block 3,
Van Subdivision
Dear Mr. Jones:
The attached report presents the results of an investigation of the '.
percolation characteristics of soils on your building site.
On the basis of this investigation we conclude that 225 square feet
of seepage area per bedroom will be required.
Very truly yours,
ALASKA GEOLOGICAL CONSULTANTS ': '
BGP:js B~ce G, PUrcell
/
cc: GAAB Health Department
Attach.
JUly 17¢ 197~
Subject: East % of ~m~ 6 }~lock 3 Va~s subdivision
the
following r~aaons ~
are~. The ~it ~ b~ one-hun~re~(100) feet
araa, t~ ~ two(2) f~r~ that perform ~he test
If there ~e any question~, plea~ contact this
~l~cerely~
~3anit ar ~an
Date
ALASKA
'~'ARTMENT OF HEALTH AND SOCIAL~ SEI~"~ES
DIVISION OF PUBLIC HEALTH
Lab. No.
BACTE RI 0 LOGICAL~-WATE R ANALYSIS
Office
PLEASE MAIL RESULTS TO:
NAME ; .~ ' :" ' ...... - "
ADDRESS
Sample eo~ected by ~c ( ~_..a
Phone No. ~
ZIP CODE
Date Collected
Time _
Sampling Address
Specific place of collection
REASON FOR SAMPLE SUBM/SSION:
[] nlness suspected
[] Hialth Regulated F~blishment
[-~-Other ~- ~-~'
WATER SAMPLE SOURCE
[] Well Type of casing
~ Improved (Enclosed, Covered) Spring
--] Surface (Reservoir, stream, lake)
[] Holding Tank
[] Other
Analysis shows this'WATER SAMPLE to be:
[~]~atisfac~o~ .
[] Unsatisfactory
[] Questionable [] submit other sample
[] Sample too long in transit to indicate reliable results.
Sample should nol be over 48 hours old at time of
examination.
[] B6{ile broken or leaked in transit.
[] Other
SANITARIAN'S REMARKS
Sanitarian's Signature:
~EAD INSTRUCT ONS
BEFORE
_COLLECTING SAMPL
06-1220 lb) BAC~TERIOLOG ICAL WATER A qALY5 IS RECORD
Date Collected -: ___ Source
Date Received Time Received ~,m. Lab, NO.~
Presumptive ~
24 Hours .
_Confirmatory ., , ,
EMB
Multiple Tube Report: J
verification: LTD
Final Membraq~ ?~ter Results
~roth 24 hours:
Broth 48 hours:
lOml Tubes posinve/Tota lOml Portions
MUNICIPALITY OF ANCHORAGE
DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTECTION
825 L Street - Anchorage, A~aska 99501
ENVIRONMENTAL ENGINEERING DIVISION
Telephone 264-4720
REQUEST FOR APPROVAL OF INDIVIDUAL WATER AND SEWER FACILITI'ES
DIRECTIONS: Complete all parts on page 1. Incomplete requests will not be processed. Please allow ten (10) days for processing.
1. PROPE T OWNER PHONE ~
3. LENDING INSTITUTION -- PHONE
· . REALTOR/AGENT
/IAI LING ADDRESS
5. LEGAL DESCRIPTION
STREET LOCATION
S. TYPE OF RESIDENCE NUMBER OF BEDROOMS
~[~SI N [] One [] Four
GLE FAMILY [~'~'~wo [] Five
[] MULTIPLE FAMILY [] Three [] Six
[] Other
[~ INDIVI DUAL* * ATTACH WELL LOG. A well log is required for all wells drilled
[] COMMUNITY since June 1975. For wells drilled prior to that date, give well
[] PUBLIC UTI LITY depth (attach log if available,)
8. SEWAGE DISP~)S~AL SYSTEM
(~ INDIVI DUAL/ON-SITE**
PUBLIC UTILITY
**If individual/on-site, give installation date.
If system is over two (2) years old an adequacy test is required
by this Department,
NOTE: THE INSPECTION FEE MUST ACCOMPANY EACH REQUEST BEFORE PROCESSING CAN BE INITIATED.
72-010(3/78)
THIS SIDE FOR OFFICIAL USE ONL.
DATE RECEIVED
INSPECTION APPOINTMENTS
TIME TIME TIME
DATE DATE DATE
INSPECTOR INSPECTOR INSPECTOR
DIRECTIONS:
I. TYPE OF RESIDENCE NUMBER OF BEDROOMS
[] SINGLE FAMII~Y [] ONE [] THREE [] FIVE [] OTHER
[] MULTIPLE FAMILY [] TWO [] FOUR [] SIX
PERMIT NUMBER
2. WATER SUPPLY
[] INDIVIDUAL DEPTH OF WELL
[] COMMUNITY
DATE DRILLED
[] PUBLIC UTILITY
Connection Verified LOG RECEIVED
3. SEWAGE DISPOSAL SYSTEM PERMIT NUMBER
DINDIVIDUAL/ON -SITE DATE INSTALLED
[]PUBLIC UTILITY
Connection Verified INSTALLER
[~Septic Tank or [] Holding Tank
Size: If Tank is h(~memade SOILS RATING
give dimensions:
TYPE OF TANK MANUFACTURER
TOTAL ABSORPTION AREA MATERIAL
4. DISTANCESwELL TO: Septic/Holding Tank Absorption Area Sewer Line Nearest Lot Line
Absorption Area to nearest Lot Line
5. COMMENTS
[] DISAPPROVED
LEGAL DESCRIPTION
72-010 (Rev, 3/78)