HomeMy WebLinkAboutVALLI VUE ESTATES #1 BLK 1 LT 12Onsite File Valli Vue Estates # 1 Lot 12 #015-311-13 Municipality of Anchorage Community Development Department Page 1 of 3 On-Site Water and Wastewater Program 4700 Elmore St. • P.O. Box 196650 Anchorage,AK 99519-6650 •http://www.muni.org/onsite•(907)343-7904 ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP191181 PID Number: 015-311-13 ❑ New ✓❑ Upgrade Name: SYLVIA SWATOSCH ABSORPTION FIELD Address ❑ Deep Trench ✓❑Shallow Trench ❑ Bed 0 Mound 6706 DOUBLE TREE COURT ❑Other Phone Number of Bedrooms Soil Rating Total depth from original grade 4 1.2 GPD/SF 9.0 Ft. LEGAL DESCRIPTION Depth to pipe invert from original grade Gravel depth beneath pipe Subdivision Block Lot 5.0 Ft 4•0Ft. VALLI VUE ESTATES#1 1 12 Fill added above original grade Gravel length Township Range Section 0.0 Ft. 60 Ft. Gravel width Beds:Number of Lines Distance between lines SEPARATION DISTANCES 5.OFt. N/A N/A Ft. To Septic Absorption I Holding Sewer Total absorption area Number of trenches Dist.between trenches From Tank Field Lift Station 1 Tank Line 6 00 Ftz 1 N/A Ft. Well N/A N/A 25'+ TANK 0 Septic ❑S.T.E.P. 0 Holding 0 Other Manufacturer Capacity Surface Water 100+ 100+ INFILTRATOR 1537Ga1. Material Number of compartments Lot Line 10+ 10+ I I PLASTIC 2 NA Foundation 10+ 10+ LIFT STATION Manufacturer Capacity I Curtain Drain 50+ ! 50+ Gal. Remarks Pump on level at Pump off level at High water alarm at in. in. in. Pump make and model Electrical Inspections performed by PIPE MATERIAL House to tank Tank to Installer 3034 drainiield 3034 A+ HOME SERVICES Drainfield 3034 CO/MT 3034 Inspector Pannone Engineering Services BENCH MARK (Assumed elevation) 708ft Inspections, Location and description dates: 1 6/20/19 2' 6/20/19 • p 3a 6/21/19 4Th 6/25/19 BOTTOM TRIM AT HOUSE POINT A COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL Engineer's Stamp Conditional Approval: Date ; O ...161 0.. *PIM .- - 0 t Steven .•F5a 'riotae rr �0 . CE 814 .;&„;',"' .-- Appro . — _____ _ Date -3-1 ci yokv?f,,f. . ..074...w., AiorEssiokk .i....- v„,...„....._%._...-ca. Inspection Report_1-1-12.doc • i -....„ DESIGN PARAMETERS ' ' A B — 1-- -, PRIMARY SEPTIC SYSTEM • N O. BEDROOM: 4(600 gpd) � T1 27.4 47.1 TANK SIZE: IM-1530 1a T2 36.5 54.6 t ,PERC RATE: �1 MPI DCO 36.3 52.7 N SOIL RATING: 1.2 GPD/SF / C1 11.2 25.2 ----` ---- - , AREA RQD: 500 SF i M1 12.8' 24.2 -- - — ~ SYS. TYPE: WIDE TRENCH 4.0' ED/ / RF: 0.50 /J C2 68.9 800 ADJ AREA: 250 SF ( M2 i 68.6 . 80.2 MIN LENGTH: 50 LF i (' _ 1 1 ~ N USED: 60LFx5'Wx4.0' E.D., 9' TO TOTAL AREA: 300 SFM '� II I \I \ , i _____. -• DOUBLE TREE COURT / —__i j/ .I / 1 Vc:; ) 48R HOUSE DRIVE.1AY I / •f I\ ' \ (E) �OT 12 / �A 1 `\1 \/,__. f 1 / REMOVED 10009 SEPTIC TANK(E) /� / PER MOA CODE�1 ,--___\_ T, DECOMMISSIONED EXISTING 1.•t / / �. I \ \\\ 1 •• M�' CRIB PER CODE I / INSTALLED IM-1530/DCO TREK_ .`� .� �k j/ '• i N' DCO AFTER • 13 /� \\ 111\ r ) , I � • , . � 1 \ \ \ ‘9R•1 ` • R AR NI / / 1 TA !R I F r ` ,` BASED ON CAT III \ 60LFx5.0'Wx4.0'EDx9.0'TO </ `` INSTALLED CO AND MT AT EACH END\ \it_ 1` ` TH / TH_\ �! ` l: (R&M1972) ,,.' — —(R&M 1972)_ _ 27 1 ', 2 \' - / \ TH_17 \ / / \ 25 J 0 O Wm a a a �1 , DRAIN ROCK 6" g oo J J o o ABOVE PIPE INV Zzq U U V o 0 4-0 DRAIN PIPE m u V 2 - EL:706.Q ELEV:706.0 FILTER FABRIC 19 2 IM-1530 SEPTIC f 702.4/ TANK(N) 702.7 \ 4.0'CRAI ROCK 701.0 DR'. PROFILE 701.0 SCALE:NTS 691.0 PERrORVED 1972 NOTES: +,����\, Dote RECORD DRAWING PANNONE ENG SVC, LLC OF Ai,. �l 6/28/2019 P.O. BOX 100217 ANCHORAGE, AK 99510 r �� "" q''.4-.:,A, �tJ ��p. Scole PHONE (907) 272-8218 FAX (907) 272-8211 ig. y ( _ DRAWN BY: *: 49 *9 P.LD N ' ACP VALLI VUE ESTATES #1, BLOCK 1, LOT 1 - -13 SYLVIA SWn ATOSCH Steven R. Pannoe PERMIT NO. 6706 DOUBLE TREE CT +0� . CE 8149 1 OSP191181 ANCHORAGE, AK 99507 ( �A•' •'• '..' Sheet PLAN t<<\\\����`4 2 of 3 • • SOILS LOG - PERCOLATION TEST SLOPE SITE PLAN X TH SLOPE TH X WATER READING DATE CLOCK NET TIME LEVEL NET DROP TIME READING 1 6/20/2019 8:30 --. 3.37 2 8:40 10 MIN 5.93 2.56 3 8:40 ___ 3.37 4 8:50 10 MIN 5.51 2.14 5 8:50 __- 3.37 6 9:00 10 MIN 5.45 2.08 5 9:00 --- 3.37 6 9:10 10 MIN 5.43 2.06 SOIL TEST RESULTS/ANALYSIS • PERCOLATION RATE<1 {min/inch (Hydrologic Soils Group:HSG A) • PERC HOLE DIAMETER 6" • TEST RUN @ 9 FT. COMMENTS:Test hole excavated by A+ HOME SERVICES PERFORMED BY: Dan Moran. I CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDLINES IN EFFECT ON THE DATE OF THIS TEST. NOTES: PANNONE ENG SVC, LLC �— "`��� Dote RECORD DRAWING OF.AC q�1�� 6/26/2019 P.O. BOX 100217 ANCHORAGE, AK 99510 OF _sq /26 co e DRAWN BY: PHONE (907) 272-8218 FAX (907) 272-8211 1 ,;76‘..•49 TH %\ *+f, I NTS ACPP.ID. NO VALLI VUE ESTATES #1, BLOCK 1, LOT 1 -311-13 SYLVIA SWA T OSCH Steven R. Pannone PERMIT NO. 6706 DOUBLE TREE CT +�Fcs. CE 8149 � // DSP191181 SOILS LOG ANCHORAGE, AK 99507 ,L111�' osst`� Sheet 0F 3 MUNICIPALITY OF ANCHORAGE - On -Site Water & Wastewater Program PO Box 196650 4700 Elmore Road Anchorage, Alaska 99519.6650 Phone: (907) 343-7904 Fax: (907) 343-7997 ht,p://vA,Av.rnuns.org/onsil,e Permit Number: OSP191181 Work Type: Septic Upgrade Tax Code Number: 01531113000 Site Legal Address: VALLI VUE ESTATES #1 BLK 1 LT 12 G:2539 Site Mailing Address: 6706 DOUBLE TREE CT, Anchorage Owner: SWATOSCH ROBERT W & SYLVIA K Design Engineer: PANNONE ENGINEERING SERVICES This permit is for the construction of: RI Disposal Field Ov Septic Tank ❑ Holding Tank 0 Privy Effective Date: Expiration Date 5/29,12019 5/2812020 Lot Size in Sq Ft: 20000 Total Bedrooms: a- � El Private Well El Water Storage All construction shall be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15,65 and the State of Alaska Wastewater Disposal Regulations (I SAAC72) and Drinking Water Regulations (1 8AAC80) 3, The wastewater code requires inspections during the installation. The engineer shall notify the Development Services Department per AMC 15,65. Provide notification by calling (907) 343-7904 (24/7). 4, From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather shall be either: a. Opened and Closed on the same day, or b. Covered, sealed, and heated to Prevent freezing Special Provisions: 1 An insulated, 20" diameter (minimum) rnanway riser is required on the first compartment of the septic tank, in accordance with 15.65,205FA 2) A percolation test and, 'or a sieve analysis shall be provided for the accepting soil prior to construction of the drainfield to confirm application rate and whether a sand filter is required. If results require a design change, construction shall stop pending Onsite review and approval of a change order. Please submit results with the change order (if applicable) or the inspection report, CC) (01/11) kewise 4v q-bedt-oom Received By: Date: Issued By: Date: MUNICIPALITY OF ANCHORAGE Community Development Department p Phone: 907-343-7904 Development Services Division Fax: 907-343-7997 On -Site Water & Wastewater Program ON-SITE SEWER/WELL PERMIT APPLICATION Parcel I.D. 015-311-13 Property owner(s) Sylvia Swatosch Mailing address 6706 Double Tree Ct, Anchorage, AK 99507 Site address 6706 Double Tree Court Day phone Legal description (Sub'd., Block & Lot) Valli Vue Estates #1, Block 1, Lot 12 Legal description (Township, Range & Section) Lot Size 20,000 Sq. Ft. Number of Bedrooms 3 APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING: (® all that apply) Absorption Field ❑X Initial ❑ Single Family (SF) ❑X Septic Tank ❑X Upgrade ❑X (w/wo ADU) Holding Tank ❑ Renewal ❑ Duplex (D) ❑ Privy ❑ Multiple Dwellings ❑ (SF and/or D) Private Well ❑ Water Storage ❑ THIS APPLICATION INCLUDES A VARIANCE I WAIVER REQUEST'FOR: i Distance: I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal Codes. Ignature of property owner or authorized agent) Permit/Rush Fees: /R� Waiver Fees: Date of Payment: Date of Payment: Receipt Number: C(UW6 Receipt Number: Permit No. Q15PI9 its/ Waiver No. Permit App__- i Pannone Engineering ServiCeS LLC Steven R. Pannone, Principal Registered Professional Engineer E-mail: steve@panengak.com June 11, 2019 Subject: Valli Vue Estates #1, Block 1, Lot 12 Septic System Upgrade Permit Request Design Narrative This is a design narrative for a permit to install an upgrade septic system to be issued for this property. The proposed septic system will serve an existing four bedroom (4) bedroom house. This lot and the surrounding lots are served by public water. There are no wells within 200' of the proposed system. 1. Soils. Per 15.65.210 Exception, eight test hole logs were located completely surrounding this system on the surrounding lots by PES. Numerous engineers and agencies have performed test holes in the area and similar soils were found in every hole. Groundwater monitoring hasbeen n_afa_m_e.d_axa o groundwater has been encountered as deep as 18'. There was groundwater monitored at a depth of 15.75' to 16.5' in test holes to the south of the subject lot. The water was encountered in a layer of ML (gravelly silt) that was not logged in any of the other test holes. With a total depth of 9' the proposed system will maintain 6.0' separation to the higher testhole while the test hole with the 15.75' ground water reading is within 5.75 distance to surface, the hole is actually 12' lower in elevation and it is highly unlikely that that water table is found at the same depth at the top of the slope. Bedrock in the area is known to be deep in the area. The soils are typically 1 mpi or faster with sufficient fines existing to make unnecessary the use of a sand filter. See soils logs and sieve analysis included. Based on the results of the surrounding percolation tests and known soil types in the area; an application rate of 1.2 gallons/day/square feet was used for a conventional wastewater system in the area of the test hole. 2. Soil Absorption System Design. a. See Sheet 1 of the design package. 3. Surface Water: There is no surface water within 100 feet of the proposed septic tank and drain field. The proposed drain field upgrade will maintain at least 100 feet from all surface water and drainage ditches. 4. Topography: The existing topography generally slopes from the east to the west in the area surrounding the septic system at approximately 4%-5%, with a slope of approximately 20% to the west of the system. There are no steep slopes within 50' of the proposed system. S. Drawing Markings: The Drawings are marked "For MoA Review Only'. When written notification that the review is complete and that there are no further comments is received from MoA On -Site Department, the note will be removed and "Issued for Construction" drawings will be issued. The proposed installation will not affect the future development of this or the surrounding lot i.ilaiiing: P.O. Box 1807, Palmer, AK' 99645 Telephone: (907) 745-8200 FAX: (907) 745-8201 • I 1 TH-PE413SON984 ' TH-ANO ERSON:1989 0 l TH-LEE REID;1987 TH=THOMAS SMITH 1985 • '\- DRIVEWAY DOUBLE TREE COURT - 'I 4BR HOUSE - I \ \� (E) LOT 12 - COLLAPSED 10008 SEPTIC TANK / o DECOMMISSION PER CODE AND REPLACE DECOMMISSION EXISTING z W/ 1250g SEPTIC TANK (P) \ CRIB PER CODE INSTALL DCO / 3 DRAIN FIFI n (P) 60LF x 5'W x 4.0'ED x 9.0'TD INSTALL CLEAN OUT AND MONITOR TUBE AT EACH END ''. \ \ / RESERVE DRAIN FIELD (FUTURE)' TH ' 1OLF x 5'W x 4.0'ED x 9.0'TD INSTALL CLEAN OUT AND _ TH— (RacM` 19`72) .t MONITOR TUBE AT EACH END'27 (R&M 1972) \ /' BASED ON CAT III y- 26 25 TH-1 TH /(TED MOORE 1993)7 .._ TED MOORE 201 1 1 '.TH-2 - r MOORS 1993) *4' CONTOUR INTERVALS DESIGN PARAMETERS DESIGN PARAMETERS PRIMARY SEPTIC SYSTEM RESERVE SEPTIC SYSTEM ABBREVIATIONS N0. BEDROOM: 4(600 gpd) NO. BEDROOM: 4(600 gpd) TANK SIZE: 1500g ADVANTEX TH TEST HOLE TANK SIZE: 1250g W/ AX20 POD (P) PROPOSED PERC RATE: F�&1 MPI PERC RATE: ;--1 MPI (E) EXISTING SOIL RATING: 1.2 GPD/SF SOIL RATING: 6 GPD/SF CO CLEAN OUT NO. AREA ROD: 500 SF AREA RQD: 100 SF MT MONITOR TUBE NO. SYS. TYPE: WIDE TRENCH 4.0' ED SYS. TYPE: WIDE TRENCH 4.0' ED TYP TYPICAL RF: 0.50 RF: 0.50 MIN LENGTH: 50 LF MIN LENGTH: 10 LF W WATER LINE/ USE: USE: WELL RADIUS 60LFx5'Wx4.0' E.D., 9' TD 1 OLFx5'Wx4.0' E.D., 9' TD TOTAL AREA: 600 SF TOTAL AREA: 100 SF SS NEW SEPTIC NOTES: PANNONE ENG SVC LLC �� ®N. Date CHANGE ORDER OF q� 0'� P.O. BOX 100217 ANCHORAGE, AK 99510 ,m '�. • • ' ' ' • 6/11/2019 ' 'qs e DRAWN BY: PHONE (907) 272-8218 FAX (907) 272-8211 ��cj�P �+P Sct 80 1e ® : 49 DRM ... . _ .. .... :.. P.I.D. NO VALLI VUE ESTATES #1, BLOCK 1, LOT 12 -311-13 SYLVIA SWATOSCH S'te'ven 'R. 'Ponnone PERMIT NO. 6706 DOUBLE TREE CT r� ����, CE x149���� OSP191181 PLAN ANCHORAGE, AK 99507 r,1�iF�/�?pFFSS10NP\o Sheet 1�\\�ava4 1 OF 2 SPECIAL PROVISIONS TO SPECIFICATIONS I. SCOPE AND SPECIFICATIONS: 1.1. ALL CONSTRUCTION SHALL BE INSTALLED AS SPECIFIED IN THE MOST CURRENT EDITION OF THE MOA COMPONENT PARTS AND MATERIALS USED IN CONSTRUCTION OF ON—SITE WASTEWATER DISPOSAL SYSTEMS AND AND IN ACCORDANCE WITH AMC 15.65 AND 15.55. 1.2. CONTRACTED WORK WILL BE IN COMPLIANCE WITH MUNICIPALITY OF ANCHORAGE STANDARD SPECIFICATIONS (MASS) DIVISION 10 & DIVISION 20 AS APPROPRIATE. 1.3. SCOPE OF WORK: INSTALL NEW 12508 SEPTIC TANK, AND SOIL ABSORPTION SYSTEM. 1.4. GROUNDWATER WAS NOT ENCOUNTERED TO A DEPTH OF 16.5 FEET BELOW EXISTING GRADE AS EVIDENCED BY THE SURROUNDING SOIL TEST HOLES. IF AN APPARENT WATER TABLE IS OBSERVED IN ANY OF THE EXCAVATIONS LESS THAN 16.5 FEET BELOW EXISTING GRADE NOTIFY THE ENGINEER IMMEDIATELY. -SEE NARRATIVE 1.5. STRUCTURES DEPICTED ON THE SITE PLAN ARE BASED UPON ONE OF THE FOLLOWING: CONCEPTUAL PLOT PLAN DEVELOPED BY OWNER; A PLOT PLAN DEVELOPED BY RLS; OR A SURVEY AS—BUILT, 2. CONSTRUCTION SPECIFICATIONS: 2.1. ALL EXCAVATION DEPTHS ARE ADVISORY. THEY ARE TO BE VERIFIED AND MAY BE MODIFIED BY THE ENGINEER IF ACTUAL FIELD CONDITIONS VARY FROM THOSE USED TO PREPARE THE DESIGN 2.2. EXCAVATE THE DRAIN FIELD. BOTTOM OF EXCAVATION SHALL BE LEVEL AND SCARIFIED. RECORD ELEVATIONS AT BEGINNING, MIDDLE AND END OF TRENCH BOTTOM. CONSTRUCTION EQUIPMENT SHALL NOT OPERATE ON THE FLOOR OF THE EXCAVATION. ANY MATERIAL COMPACTED BY THE OPERATION OF THE CONSTRUCTION EQUIPMENT SHALL BE REMOVED AND REPLACED WITH UNCOMPACTED MATERIAL. 2.3. PLACE THE SEWER ROCK TO THE SPECIFIED DEPTHS. DO NOT CONTAMINATE SEWER ROCK WITH NATIVE MATERIAL OR SPOILS FROM EXCAVATION. LEVEL ROCK SURFACE TO ±1" PRIOR TO INSTALLING THE PERFORATED PIPE. 2.4. ALL PIPE SHALL BE PVC CONFORMING TO ASTM D3034 OR ENGINEER APPROVED EQUAL. MINIMUM SOIL COVER SHALL BE 3 FEET OVER THE PIPE AND 4 FEET OVER THE SEPTIC TANK. ONE INCH OF INSULATION MAY BE SUBSTITUTED FOR 1 FOOT OF SOIL COVER. 2.5. ALL INSULATION SHALL BE 2" THICK DOW HI -40 INSULBOARD OR ENGINEER APPROVED EQUAL. CENTER INSULBOARD WIDTH OVER SEPTIC TANK OR LINES. 2.6. GEOTEXTILE SHALL BE MIRAFI 1405 OR ENGINEER APPROVED EQUAL. LAP ALL JOINTS 2 FEET 2.7. COVER THE DISTRIBUTION PIPE WITH A MINIMUM OF 2" OF SEWER ROCK AND COVER WITH GEOTEXTILE BEFORE PLACING INSULATION AND BACKFILL. 2.8. MATERIAL USED AS FILL SHALL BE CLEAN AND FREE OF ORGANICS, TRASH AND CONSTRUCTION DEBRIS. 2.9. SLOPE ALL FILL MATERIAL TO DRAIN AT 2% MINIMUM SLOPE AND 3:1 MAXIMUM SLOPE AND IN SUCH A MANNER THAT PONDING AT OR NEAR THE DRAIN FIELD DOES NOT OCCUR. THE FILL SHALL BE LEFT AT 6•' HIGHER THAN SHOWN TO ALLOW FOR SETTLEMENT. SEED SURFACE AFTER COMPLETING INSTALLATION AS PER MOA CODE. 2.10. RECORD THE FINISH GROUND ELEVATION OVER THE BEGINNING, MIDDLE AND END OF SYSTEM. 2.11. MAINTAIN 5' SEPARATION BETWEEN PERCOLATION HOLE AND THE DRAIN FIELD TRENCH. 2.12. EXPOSE, PUMP AND FILL LOG DISPOSAL CRIB OR CONCRETE TANK WITH SOIL TO ABANDON IAW WITH MOA CODE IF NEEDED. 3. CONTRACTOR RESPONSIBILITIES: 3.1. THE CONTRACTOR SHALL FAMILIARIZE THEMSELVES WITH THE SITE CONDITIONS AND LOCATIONS OF ALL LOT LINES, EASEMENTS, WELLS (E & P), SEPTIC SYSTEMS (E & P) AND SHALL MEET MINIMUM SEPARATION DISTANCES OR AS NOTED. 3.2. THE CONTRACTOR (BOTH WELL AND SEPTIC SYSTEM CONTRACTORS) SHALL HAVE ANY WELL LOCATION AND SEPTIC LOCATION STAKED AND ANY LOT LINE AND WELL RADIUS SHOWN ON THE PLAN WITHIN 30 FEET OF THE PROPOSED SYSTEM STAKED BY A REGISTERED LAND SURVEYOR BEFORE STARTING THE WORK. 3.3. THE CONTRACTOR IS RESPONSIBLE FOR ALL R.O.W. AND OTHER REQUIRED PERMITS, OTHER THAN THE ATTACHED. 3.4. THE CONTRACTOR SHALL CALL FOR LOCATING OF ALL BURIED UTILITIES. 3.5. THE CONTRACTOR SHALL PROVIDE 24 HOUR NOTICE TO THE ENGINEER PRIOR TO START OF WORK. ALL SURVEYING AND LOCATES SHALL BE IN PLACE PRIOR TO NOTIFYING THE ENGINEER. 3.6. THE CONTRACTOR SHALL NOTIFY THE ENGINEER OF ANY DISCREPANCY BETWEEN THE APPROVED DRAWINGS AND SITE CONDITIONS/LIMITATIONS POTENTIALLY CAUSING THE NEED TO MODIFY THE DESIGN. 3.7. AT THE COMPLETION OF THE WORK, THE CONTRACTOR SHALL SUBMIT RED—LINE AS—BUILT DRAWINGS TO THE ENGINEER. THE RED—LINES SHALL INCLUDE PIPE LENGTHS, ORIGINAL GROUND ELEVATIONS, PIPE ELEVATIONS, AND TANK ELEVATIONS. 3.8. THE CONTRACTOR SHALL PROVIDE PHOTOGRAPHS OF THE SYSTEM INSTALLATION TO INCLUDE BOTTOM OF EXCAVATION, TOP OF PIPE WITH CLEAN—OUTS AND MONITOR TUBES INSTALLED, INSTALLED TANK AND FINAL GRADING. 4. THE CONTRACTOR SHALL SIGN THE FOLLOWING: I CERTIFY THAT ALL WORK WILL BE PERFORMED IN ACCORDANCE WITH THE APPROVED PERMIT, AND ANY AND ALL CHANGE ORDERS, AND THAT THE AS—BUILT REDLINES ARE TRUE AND ACCURATE REPRESENTATION OF THE PROJECT AS CONSTRUCTED. CONTRACTOR: BY: NOTES: PANNONE ENG SVC, LLC P.O. BOX 100217 ANCHORAGE, AK 99510 PHONE (907) 272-8218 FAX (907) 272-8211�P � OF A�q�>t� S 'FyrP/ .... .. ..... .. _ . . • / J Steven R. Pannone CE 8149 �l F�Fo�F.� i`�\ 0fE$5101�a Date 019 CHANGE ORDER ScaleNTS DRAWN BY: VALLI VUE ESTATES #1, BLOCK 1, LOT 12 -.. SYLVIA SWATOSCH 6706 DOUBLE TREE CT ANCHORAGE, AK 99507 DRM P.I.D. NO 015-311-13 PERMIT NO. 0SP191181 PLAN sheet 2 OF 2 82 ED A J .._ Lot 11 ti N .77 173.09 s flock 4 `a 36,0 .i i 15 ' iZ 71 1 AsPhait An r �7 Lot 27 �v U - LJ 7 1 '�= i_�I�_ �S'xi�1 ! i i Ur ( oS o - E PC rdi ! Prerim, iMaslka,ind, the r -,,(cS_ .C. ,wi c ..i r m the p t.. .,r it -tes ism UK a1t.. v we w w.,..1.... Kj ible ease.. onk ar :jat p iJpwW :aA. ao 2s WaNd ,,,. Lir EASECv�E?.TS O RECOREI OTHER THAN S ti fN� — �. � �'�� _.. APRIL _........... PLAT ARE NOTSIHOVVN HEREON BE EyMmomwSwmps IPA _S TAFER19SF f_ n FD ET n P9 19 2 ,. FOS! rJ?'j g._ iJ. ,5 GR:'"'J'ER ANCHORAGE AREA BOROI/~"~"~ Db~'ARTMENT OF ENVIRONMENTAL OUALIl~- 3500 TUDOR ROAD ANCHORAGE, ALASKA 99507 279-8686 ,/ INSPECTION REPORT ON-SITE SEWAGE DISPOSAL SYSTEM SEPTIC TANK: MAILING ADDRESS ~¢:~'~ '~'~ ,,~"~ PHONE. LEGAL DESCRIPTrON ~ /~w ~/, ~~' NUMBER OF ~ DISTANCE FROM WELl ~--~°..,-'"~Z/~'/Z~:.4/~/-z'~-.-'~ MATERIAL --~%~'---,~'~- COMPARTMENTS ,,.~- ~'~,.~'--,~:~,Z, ~ ~/~,,~...~, LIQUID LIQUID CAPACITY /"~:) g'~2~_) GALLONS. IN,SIDE LENGTH. ~ INSIDE WIDTH ~ DEPTH SEEPAGE SYSTEM: SEEPAGE PIT: NUMBER OF PITS. / OUTSIDE DIAMETER LINING MATERIAL~ NEAREST LOT LINE ~ OR WIDTH /--~ LENGTH /'~"' , DEPTH <J~"~ / DISTANCE FROM WELL ~,~,,~./~,.,~/~,,,/,~x//-~,~/ BUILDING FOUNDATION "(-/,~"~ ,/ TOTAL EFFECTIVE ABSORPTION AREA (WALL AREA) '~/.'~ SQ. FI. TILE DRAIN FIELD: DISTANCE FROM WELl ~'~"~, FOUNDATION NUMBER OF L,..J~b'''''''/ .DISTANCE BETWEEN LINES ABS R~D~P[ION AREA SQ. FT. LENGTH OF EACH LINE , NEAREST LOT E TOTAL LENGTH , OF LINES IN. TOTAL EFFECTIVE DEPTH: TOP OF TILE TO FINISH GRADE DEPTH OF FILTER MATERIAL BENEATH TILE IN. ABOVE TILE WELL: ~ TYPE ~.~,/'~.,.~-',4//~,~" DEPTH ~ NEAREST ~ SEPTIC LOT LINE , SEWER LINE ., TANK DISTANCE FROM / WATER ., BUILDING FOUNDATION _SAMPLE 4..---- . NEAREST ~ SEEPAGE ~ ~ OTHER ~ , SYSTEM_ , CESSPOOL , SOURCES__ DISTANCES: DATE 7 '~ ./'/~ "7 ~ , DIAGRAM OF SYSTEM G.A.A.B. GRE:A~WR ANCHORAGE AREA BOROUGH DEPARTMENT OF ENVIRONMENTAL QUALITY 3500 TUDOR ROAD ~ POUCH 6-650 ANCHORAGE. ALASKA 99502 TELEPHONe 279-8686 SEWAGE DISPOSAL SYSTEM -- APPLICATION AND PERMIT PERMIT NO. 2185 LEGAL DESCRmTION Z--/ INSTALLATION OF: SEPTIC TANK FINANCED THROUGH TO Bg INSTALLED BY . / DRAIN FIELD WATER MAIN TO SEPTIC TANK DRAIN FIELD · SEEPAGE PIT · ALSO CONSIDER AREA WELLS, , SEEPAGE PIT //c/~) / DRAIN FIELD- ~i ~ CAST IRON INTO AND OUT Of SEPTIC TANK AND INTO CRIB CROSSING GAP OF EXCAVATION 5 FEET INTO UNDISTURBED ~oig; 4 INC~_H DIAMETER CAST IRON SIPHON PIPES ON SEPTIC TANK AND SEEPAGE PIT FITTED WITH AIRT{GHT REMOVABLE CAPS. GRAVEL BACKFILL CONFORM TO BOROUGH REGULATIONS REGARDING INSTALLATION. HEALTH ~U~ ORITY LICENSED ~GNER I CERTIFY THAT ] AM FAMILIAR WITH THE REQU[REMENTS OF GREATER ~ANCHORAGE AREA BOROUGH ORDINANCE NO. 28-68 AND THAT THE ABOVE DESCRIBED SYSTEm IS IN ACCORDANCE W[TH SAID CODE. / / T.H.-I 6 -19-72 SILTY SAND W/SOME GRAVEL (GM) 0.0~ GRAVELLY SAND W/SOME COBBLES TRACE SILT ( S P) GRAVELLY SAND (SW) No water table Note: Hole excavation with tractor mounted 10.5' I1.0' backhoe. Engineering ~ Geological Consultants Robert Swatosch Property LOG OF TEST BORING Anchorage Alaska ~ATE 6-19-72 ISCALE I"=~ ~ BY GAW R&M Civil Engineers ENGINEERING & GEOLOGICAL CONSULTANTS 229 EAST 51st. AVE. - P.O. BOXed087 -~ANCHORAGE, ALASKA 99503 TELEPHONE 907-279-0483 TELEX 090-35419 Geologists Land Surveyors JAMES W. ROONEY, P. E. MALCOLM A. MENZIES, P.E., L.S. JAMES H. WELLMAN, P.E. June 19, 1972 1VI No. 2~528 RALPH R. MIGLIACCIO Engineering Geologist l~Ir. Robert Swatosch 7800 De Bart Road Anchorage, Alaska RE: Test Hole and Soil Log Report for Sanitary System Lot 12, Block l, Va{Icy Vi~, Estates Dear lVIr. Swatosch: I~ECEIVED We are submitting herewith the test boring results and our comments re- gardlng soil conditions encountered at the subject site. This investigation was performed in accordance with your request of June 19, 1972, and those procedures outlined in a letter dated September 13, 1971 by 1VIr. Roll Strick- land of the Greater Anchorage Area Borough. Department of Environmental Quality. A single test hole was put down within the Lot 12, area for the purpose of defining general subsurface soil conditions for the proposed sanitary system. Excavation was accomplished with a tractor-mounted back,hoe and the test }{ole was ex~kended to a total depth of 11 £eet below ground surface. One sample was recovered from the bottom of the test hole and retained for grain .size analysis. The sample will be held in storage, up to approximately one month, for possible testing before it is discarded. The final log prepared for the test hole has been included in Drawing A-01. Ground water was not encountered in the test hole. We appreciate being given this opportunity to be of service ko you. Should you have any questions with regard to the above, please do not hesitate to contact us. Very truly yours, R & 1VI ENGINEERING & GEOLOGICAL CONSULTANTS JWR: wb cc: Greater Anchorage Area Borough EPtinkiS MUNICIPALITY OF ANCHORAGE . ,tri Development Services Department 1^7/ Phone: 907-343-7904 On-Site Water& Wastewater Section Fax: 907-343-7997 Certificate of On-Site Systems Approval Parcel I.D. 015-311-13 Expiration Date: 7-z - Z 0 1. GENERAL INFORMATION Complete legal description Valli Vue Estates #1 B1 L12 Location (site address) 6706 Double Tree Current property owner(s) Robert & Sylvia Swatosch Day phone Mailing address Real estate agent Day phone 2. TYPE OF DWELLING: Single Family (w/wo ADU) ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF BEDROOMS: 4 4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Private Well ❑ Private Septic CI Water Storage ❑ Holding Tank ❑ Community Well Q Community ❑ Public Water System ❑ Public Sewer ❑ Waiver request for: Distance: Received by: Date: COSA to be released to the engineer,unless otherwise requested by the engineer. COSA Fee $ $gQ / Waiver Fee $ Date of Payment io j 119 Date of Payment Receipt Number 66 WO Receipt Number COSA# VS C ! s Waiver# 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On-Site Systems Approval Guidelines for this application. shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is (are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. In conducting an adequacy test, I attempt to provide a thorough, conscientious engineering analysis of the system in accordance with MoA COSA guidelines and regulations.The reported results describe the performance of the system under the conditions encountered at the time of the test,and separation distances measured to readily identifiable features.The operational life of all wells and septic systems depend on the local soil condition,ground water levels that may fluctuate during the year,and the water usage of the family being served by the system. These conditions are outside the control of the evaluator of this system. All systems eventually fail and satisfactory test results do not guarantee future performance of the system,nor do they guarantee that there are no hidden defects or encroachments.Therefore we cannot provide any warranty for future performance, nor can we estimate remaining life of the system. The content of this report is for the sole benefit of the owner listed above. Reliance on this report by another person is at their own risk. Pannone Engineering Services LLC highly recommends buyers hire their own engineer to evaluate this report. Name of Firm Pannone Engineering Services Phone (907) 745-8200 Address P.O. Box 1807 Palmer, AK 99645 Engineer's Printed Name Steven R. Pannone P.E. Date 6/26/19 6. DSD SIGNATURE •••gym• ••* X System #1 Approved for bedrooms Y PP •• levan - -anriore 442) System #2 Approved for bedrooms CE 8149/ Disapproved q _ PP t ti Conditional approval for bedrooms, with the following stipulations: Lotl((((((((((1 ``` J���pp�LlTYD,c ?rii' � 14/47. -SiTt do RGQTSR 1Cri 1) VICES By: ( w ( � Original Certificate Date: 7_3 -1 The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On-Site Systems Approval(COSA)based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 7. ATTACHMENTS: COSA Checklist X Nitrate Advisory Septic System Advisory Arsenic Advisory Well Flow Advisory Other COSA Checklist blue sheet COSA Checklist Legal Description: Valli Vue Estates#1 B1 L12 Parcel ID: 015-311-130 If more than 1 septic system on lot: COSA Checklist# of Structure served by this system A. WELL DATA ❑Well log is filed with Onsite(or attached) Well production at time of test gpm Date drilled Water storage tank volume gallons Total depth ft Well disinfected for coliform test? ❑Yes 0 No Cased to ft ❑ Coliform bacteria is Negative ❑Sanitary seal is functioning correctly Nitrate mg/L ❑ Nitrate less than MRL(ND) ❑Wires are properly protected Arsenic ug/L 0 Arsenic less than MRL(ND) Casing height(above ground) in. Collected by Date of flow test for COSA Date of Sample Static water level at beginning of test ft. Comments N/A B. TANK DATA C. LIFT STATION Age of tank(s) 6J20"9 years ❑ Required maintenance completed Tank type/material "` Age of lift station years Measured operating fluid level in septic tank Lift station material ❑Standpipes/foundation cleanout per record drawing Comments: 2" Rigid Insulation over tank Date of pumping D. ABSORPTION FIELD DATA Shallow Trench Which system tested(date installed) 6120/19 Adequacy test date n/a ID ALL standpipes present per record drawing Results ID Pass For 4 bedrooms Total measured depth from grade 9.0 ft(max) Fluid depth prior to test in Measured depth to pipe invert from grade 5.0 ft(min) Water added gal ❑ N/A—pressurized field New depth in It Monitor tubes go to bottom of effective. If not,state Elapsed time min depth into effective ❑ Code-required soil cover over field Final fluid depth in ❑ System presoaked Absorption rate gpd (Required if vacant for greater than 30 days prior to Any rejuvenation treatment(past 12 months) date of test) If yes, enter date Gallons introduced gallons Comments/Deficiencies: COSA Checklist yellow sheet E. SEPARATION DISTANCES From Private Well on Lot to: (Please enter distances if less than required or if community well) Septic Tank/Lift Station on Lot > 100' Community Sewer Manhole/Cleanout> 100' 0 Yes if No ft 0 Yes if No ft Neighboring Tank > 100' 0 Yes if No ft Private Sewer/Septic Line >25' 0 Yes if No ft Absorption Field on Lot> 100' 0 Yes if No ft Holding Tank > 100' 0 Yes if No ft Neighboring Absorption Fields > 100' Animal Containment> 50' 0 Yes if No ft 0 Yes if No ft Manure/Animal Excreta Storage> 100' Community Sewer Main > 75' 0 Yes if No ft in Yes if No ft From Septic/Holding Tank on Lot to: (Please enter distances if less than required) Building Foundations > 10' 0 Yes if No ft Surface Water> 100' 0 Yes if No ft Property Line > 5' 0 Yes if No ft Wells on Adjacent Lots: Absorption Field > 5' 0 Yes if No ft Private Wells > 100' 0 Yes if No ft Water Main > 10' 0 Yes if No ft Community Wells> 200' 0 Yes if No ft Water Service Line > 10' 0 Yes if No ft If septic tank is under driveway comment below From Absorption Field on Lot to: (Please enter distances if less than required) Building Foundation > 10' 0 Yes if No ft If absorption field is under driveway comment below Property Line > 10' 0 Yes if No ft Wells on Adjacent Lots: Water Main > 10' 0 Yes if No ft Private Wells > 100' 0 Yes if No ft Water Service Line > 10' 0 Yes if No ft Community Wells>200' El Yes if No ft Surface Water> 100' 0 Yes if No ft F. ENGINEER'S COMMENTS G. ENGINEER'S CERTIFICATION ��OF L, 1kk s%P•' 'f-48 I certify that I have determined through field inspections and review c0.• �, - ':9 y of Municipal records that the above systems are in conformance with 0'k• '�� t .:* �3 MOA COSA guidelines in effect on this date. f 46�Z�r / . . ••.• • to t COSA Checklist yellow sheet 1 / t 1 Lot 11 4<! 4: N83°52142"W 173.09 / -0,./ •q2N./ ,f4 \ \ Chain link fence �tYp)\ 1-r--------------------1 Q \ deck = f-- HIM `�'3 90\\'''.:r \ h 36.0 ,.,,,‘,.c,,,,:...\. oi2.7 2 1/2 Story \\:: ." • CO: 2.1 Frame House up ,p 8 \ � \ 17.7 \\`�CO� \ N .•� co 0 41 m wsom r \ 5.7 __' 1:. `•, \ 0 o \ \ o Asphalt ON \ 24.0 `v Lot 13 G ` "p \\ manhole------'° U4 OF ° Al 411 �O \ 0 ei � ° ° . ° . •q� \ `� 0'` 49tH . \ septic vent(typ) 00 / \.,i \ //�, f• ri' ° °i / GSA;I \ Lot 12 ��•J� • :;= ,�� `�,_ d ?, ° _Iizabeth L. Walatkc Lot 27 \ l i, d''.,.,` 8036 - LS • 1y B � • O r • ° • \ o :i 1 F ° • °p _Q $ lit) Essi 01,1 A- - `\ F \ RECERTIFIED 06/24/2019 CJ C. ' \ r•` AS-BUILT NO CORNERS SET THIS DATE \ \ I hereby certify that I have performed a Mortgagee's insp \ of the following described property: LOT 12, BLOCK VALLI VUE ESTATES UNIT No. 1 Anchorage Recording Precinct, Alaska, and that the - — improvements situated thereon are within the property Iii and do not overlap or encroach on the property lying /Lot 26 adjacent thereto, that no improvements on the property I adjacent thereto encroach on the premises in question that there are no roadways,transmission lines or other visible eesements on said property except es indicated ALE ;�i�� r beret rt ' t — 3Q opliod git Atlriwrwr•Mr Alsh*tilrre