ON-SITE WASTEWATER INSPECTION REPORT
Permit Number: OSP141381 PID Number: 015-322-30
Dwelling:* Single Family (SF) ❑ Duplex (D) ❑ Multiple (SF and/or D) Project: ❑ New N Upgrade
Name:
DAVID PRINCE
ABSORPTION FIELD
N Deep Trench ❑ Shallow Trench ❑ Bed ❑ Mound
Address
6257 WEST TREE DR ANCHORAGE AK 99507
❑ Other
Phone
Number of Bedrooms
Soil Rating
Total depth from original grade
3
0.8 GPD/SF
11.0 Ft.
LEGAL DESCRIPTION
Depth to pipe invert from original gradeGmvel
2.9 Ft.
depth beneath pipe
8.1 Ft.
Subdivision Block Lot
VALLI VUE ESTATES #2 2 27
Fill added above original grade
1-1.5 Ft.
Gravel length
40 Ft.
Township Range Section
Gravel width
3 Ft.
Beds: Number of Lines
Distance between lines
-- Ft.
SEPARATION DISTANCES
To
Septic
Absorption
Holding
Sewer
Total absorption area
Number of trenches
Dist. between trenches
From
Tank
Field
Lift Station
Tank
Line
648 '-Ftp
1
NA Ft.
well
>200'
>200'
>200'
NA
>25'
TANK ❑ Septic ■ S.T.E.P. []Holding ❑ Other
Manufacturer
ANCHORAGE TANK
Capacity
11250 Gal.
Surface Water
94'
>100'
94'*
NA
Material
Number of compartments
Lot Line
>5
>10'
>5'NA
STEEL
2
NA
Foundation
>5'
>10'
>5'
NA
LIFT STATION
Manufacturer
Capacity
Curtain Drain
>50'
>50'
>50'
NA
ANCHORAGE TANK
1250 Gal.
Remarks 1986 DRAINFIELD CONNNECTED VIA
Pump on level at
25 in
Pump off level at
44 in
High water alarm at
22.5 in.
DIVERTER VALVE IN LIFT STATION.
"WAIVER ON FILE.
Pump make and model
ORENCO
Electrical Inspections performed by
MOA
PIPE MATERIAL House to tank 3034 Tank to SCH40
dminfield
Installer
DEAN CONSTRUCTION
DrainfieldSCH40 CO/MT F810
Inspector LARS SPURKLAND, ANSON MOXNESS
BENCH MARK (Assumed elevation) 100 ft
Inspd ction
1� 9/19/14 9/19/14
Location and description
tion 2M
a" 9/20114 0
BOTTOM SIDING NW HOUSE CORNER
COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL
Engine r' tamp
OF
Conditional Approval: Date
�...
SPURKLAND:Z�%
11500
Approved Date —30 /
Z' ZVZ Il
Inspection Report_9-1-12.doc/
W,
u.
18
Septics
(- Area
VAL L I VUE ES TA TES #2 S/D
A�0, 1 �1
E
26
INSTALLED 1250 GALLON STEP TANK
INSTALLED DIVERTER VALVE
TRENCH LENGTH 40 FEET
TRENCH WIDTH 2 FEET
MAX EXCAVATION DEPTH 11 FEET
ROCK DEPTH 8.1 FEET
LOT
1
1
21
1
�
1 1 1
yN
1 \�
C.O. C 29' B.5'
STATION D 32' 17.5'
M. I. E 33' 61'
M. I. F 47.5' 73.5'
12
NOTE: SOUTH AND WEST LOT LINES STAKED
DY A REGISTERED LAND SURVEYOR. 4' CONTOUR LINES
NOT£.• SLOPES EXCEEDING 25X WERE NOT OBSERVED
WITHIN 50 FEET DOWN GRADIENT OF THE PROPOSED
ABSORPTION FIELD LOCATION.
NOT£.• THIS 15 NOT A SURVEYED PUT. WELL ! SEPTIC
LOCATIONS TAKEN FROM ON -S17£ WATER AND WASTE WATER
DEPARTMENT DOCUMENTATION. ALL LOCATIONS SHOWN ARE
APPROXIMATE.
25 0 25 50 75 100 125 150
SCALE I' = 50 FL
tN(iINLtK/NG I I VALL( SEPTIC SYSTEM ASBU/LT
20303 V W 15TH.
AVENUE DATE, SEPT 22 2014
MCHMCHAK.K. TH.TH. I ME ESTATES 12 BM 4 LT 27 I
99501 DAVIN &PATTY PRINCE
(907) 279-3916 6257 WEST TREE DR ANCHORAGE AK 99507 SHEET, 2/3 GRID: SV2538
PERMIT If DSPI41381 PID # 015-322-30 VV£2B4L27.SC50-ASB.DWG
TH
SG atv
$as'
E# ME nEYW7A'
1W REI-mr
EUAdI M ElEY
ERI'
Trench Elevation (TyP)
Septic Rock
BENCH MARK BOr M SONG NW CORNER
ASSUMED ELEVAAOH 100 MT
DIVERTER
T STATION
ISPIIRKUND ENGINEERINGI I VALLI WE ESTATES 12 Bm 4 LT 27 (I SEPTIC SYSTEM ASOVILT
203 V 15TH. AVENUE DA VIN PRINCE DATE, SEPT 22 2014
ANCH. AK. 99501
(907) 279-3916 6257 VEST TREE DR ANCHURAGE AK 99507 SHEET, 3/3 01D, SV2538
PERMIT # OSP 141381 PID #015-322-30 VV£5B4L27.D3-ASBBVG
On -Site Wastewater Disposal System Permit
MUNICIPALITY OF ANCHORAGE
Development Services Department
On -Site Water & Wastewater Program
4700 Elmore Road, PO Box 196650
Anchorage, AK 99519-6650
Telephone: (907) 343-7904
Permit Number: OSP141381
Tax Code Number: 01532230000
Work Type: Septic Upgrade
Permit Effective Dates: September 17, 2014 to September 17, 2015
Design Engineer:
Subdivision:
Site Legal Address
Owner/Address:
SPURKLAND ENGINEEI
VALLI VUE ESTATES #2
VALLI VUE ESTATES #2 BLK 4 LT 27 G:2538
PRINCE DAVID A
6257 WEST TREE DR ANCHORAGE AK 995070000
Site Mailing Address: 6257 WEST TREE DR, Anchorage
This permit is for the construction of:
Y Disposal Field Y Septic Tank N Holding Tank
9/1tgItL-1 qpm
Lot Size in Sq Ft: 22113
Total Bedrooms: 3
N Privy N Private Well N Water Storage
All construction must be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater
Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80).
3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services
Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either:
A. Open and Close on the same day.
B. Covered, sealed, and heated to prevent freezing.
Received
Issued By
SRI
By: Date:
Dater
MUNICIPALITY OF
Community Development Department
Development Services Division
On -Site Water & Wastewater Program
ANCHORAGE
Phone: 907-343-7904
Fax: 907-343-7997
ON-SITE SEWER/WELL PERMIT APPLICATION
Parcel I.D. 015-322-30
Property owner(s) DAVIN PRINCE
Mailing address 6257 WEST TREE DR ANCHORAGE AK 995070
Site address SAME
Day phone
Legal description (Sub'd., Block & Lot) VALLI VUE ESTATES #2 BLK 4 LT 27
Legal description (Township, Range & Section)
Lot Size Sq. Ft. Number of Bedrooms 3
APPLICATION IS FOR:
APPLICATION IS AN:
TYPE OF DWELLING:
IN all that apply)
Absorption Field
E]
Initial ❑
Single Family (SF)
0
(w/wo ADU)
Septic Tank
El
Upgrade n
Duplex (D)
F]Holding
Tank
ElRenewal
❑
❑�
^ Ilings
Per / r D)
E]Privy
AMo 23,10. t .
Private Well
❑
S F. N
Water Storage
❑
THIS APPLICATION
INCLUDES A VARIANCE / WAIVER-REQUESTfflR—=
Distance:
I certify that the above information is correct. I further certify that this is in accordance with
aodicable Municipal Codes.
M
of property owner or authorized agent)
Permit/Rush Fees: 50 ' Waiver Fees: _
Date of Payment: -! IS I I y d,*, Date of Payment:
Receipt Number: 061VI b G Receipt Number:
Permit No. Ci`yh I L(I 3ri Waiver No.
Permit App_9-1-12.doe
Spurkland Engineering
Environmental Consulting and Design
SEPTIC SYSTEM DESIGN
VALLI VUE ESTATES #2 B4 L27
Municipality of Anchorage September 4, 2014
Development Services Department
On Site Water and Wastewater Program
4700 Elmore Road
Anchorage, Alaska 99519
Subject: Septic System Installation Permit
6257 West Tree Drive
Ladies and Gentlemen:
I am writing to request a septic system installation permit for the above referenced property. The
existing septic system did not meet COSA operational requirements. The proposed system will
serve a 3 -bedroom single-family residence. Soil logs, design calculations, a site plan, design
drawings and construction specifications are enclosed for your review.
Design Cales: Groundwater was not observed (Test hole depth 19.5 feet below ground surface
9/4/14).
Soil Rating. From Test hole 8/29/14
8.3 min/in = 0.8 gal per sq.ft/day
No. of Bedrooms 3
Required Area per Bedroom: 150/ 0.8=187.5sq.ft.
Total area required: 187.5 x 3 = 563 sq.ft.
System: We are proposing a 1250 gallon STEP tank followed by a trench absorption field. The
absorption field will be 40 feet long and 2 feet wide and contain 8.0 feet (640 sq.ft. effective) of
sewer rock.
Soils: A test hole was excavated to a depth of 19.5 feet on August 28a`, 2014. See the attached
soil logs. Groundwater was not observed on September 4, 2014. Ground water monitoring will
continue through construction of the septic system.
Surface Water: A stream/ drainage runs along the eastern property line approximately 95 feet
from the existing septic tank.
203 West 150' Avenue Suite 203, Anchorage, AK 99501, Phone: (907) 279-3916
Fax: (866) 354-1597, Lspurkland@gci.net
iikra-& Spurkland Engineering
Environmental Consulting and Design
Topography: The ground level slopes down towards the northeast at approximately a 5% grade
Waivers: An existing surface water waiver has been granted for the septic tank. The
existing waiver justifications apply to the new tank (see attached letters). Per conversation with
Jay Crewdsen (9/5/14) the existing waiver is worded such that is should apply to the new tank.
The installation of this septic system will not prevent wells and septic systems from being
installed on the adjacent lots. The proposed septic system will not change the general slope of
the area. Ponding and/or concentration of surface runoff will not result from this installation.
If you have any questions or concerns, please contact me at 279-3916.
Sincerely,AJ L
Lars r kland, P.E.
Civil Engineer
203 West 15a' Avenue Suite 203, Anchorage, AK 99501, Phone: (907) 279-3916
Fax: (866) 354-1597, Lspurkland@gci.net
I
20
30 1 1 1 1S 1
ATE _
29 S 20
LI i1 — 11 44
28 1 21�or�\ \
45
LOT 27 1 `,
'
26 1 — 46
T'
23 \ \ \
24, 1 V
44•
lY
NOTE: VAlLI VUf ESTATES SCrBDlVISION LS SERVED 8Y A
PUBLIC WATER SUPPLY
NOTE. THS IS NOT A SURVEYED PLAT. WELL 4 SEPTIC
LOCATIONS TAKEN FROM ON—SIT£ WATER AND WASTE WAT£P
DEPARTMENT LH1CUMfNTAT10N. ALL LOCATIONS SHOWN ARE
APPROXIMATE.
50 0 50 100 150 200 250 300
SCALE., 1' = 100 Fl.
SPURKLAND ENGINEERING 1 1 PACU ME ESTATES 12 ff TES 4 LT 271 I SEPTIC SYSTEM DESIGN
203 W 15TH. AVENUE
ANCH, AK, 99501 DAVIN & PATTY PRINCE DAAUG 25 2014
(907) 279-3916 6257 VEST TREE BR ANCHURAG£ AK 99507 SHEET.- 1/3 GRID: SV2538
PERMIT # USP141XXX PID # 015-322-30 VVE2B4L27.SCIoODVG
28
Septic
(- Area
VAL L I VUE ES TA TES #2 S/D
26
INSTALL 3-H£DROOM SEPNC SYSTEM
INSTALL 1150 GALLON STEP TANK
INSTALL DIVERTER VALVE
TRENCH LENGTH 40 FEET
TRENCH WIDTH 2 FEET
MAX EXCAVATION DEPTH 11 FEET
ROCK DEPTH 8.0 FEET
EASE 1
LOT
NOT£.• SOUTH AND WEST LOT LINES TO Bf STAKED
BY
A REGISTERED LAND SURVEYOR. 4' CONTOUR LINES
NOTE: SLOPES EXCEEDING 25% WERE NOT OBSERVED
WHIN 50 FEET DOWN GRADIENT OF THE PROPOSED
ABSORPTION FIELD LOCATION.
NOTE: THIS 1S NOT A SURVEYED PLAT. WELL & SEPTIC
LOCATIONS TAKEN FROM ON-SITE WATER AND WASTE WATER
DEPARTMENT DOCUMENTATION. ALL LOCATIONS SHOWN ARE
APPROXIMATE.
25 0 25 50 75 100 125 150
SCALE., I' = 50 FT,
S3 V 15 H, AVENUE
xmv I I VALU VUE ESTATES 12 Bm 4 LT 27 I I SEPTIC SYSTEM DESIGN
203 W 15TH. AVENUE
ANCH AK, 99501 DAVIN & PATTY PRINCE DATE.., SEPT 4 2014
(907) 279-3916 6257 WEST TREE DR ANCHORAGE AK 99507 SHEET 213 GRIBt EV2538
PERMIT At DSP141XXX PID 0 015-322-30 VV£2B4L27.SC50.DWG
LA
\
22
z
1
NOT£.• SOUTH AND WEST LOT LINES TO Bf STAKED
BY
A REGISTERED LAND SURVEYOR. 4' CONTOUR LINES
NOTE: SLOPES EXCEEDING 25% WERE NOT OBSERVED
WHIN 50 FEET DOWN GRADIENT OF THE PROPOSED
ABSORPTION FIELD LOCATION.
NOTE: THIS 1S NOT A SURVEYED PLAT. WELL & SEPTIC
LOCATIONS TAKEN FROM ON-SITE WATER AND WASTE WATER
DEPARTMENT DOCUMENTATION. ALL LOCATIONS SHOWN ARE
APPROXIMATE.
25 0 25 50 75 100 125 150
SCALE., I' = 50 FT,
S3 V 15 H, AVENUE
xmv I I VALU VUE ESTATES 12 Bm 4 LT 27 I I SEPTIC SYSTEM DESIGN
203 W 15TH. AVENUE
ANCH AK, 99501 DAVIN & PATTY PRINCE DATE.., SEPT 4 2014
(907) 279-3916 6257 WEST TREE DR ANCHORAGE AK 99507 SHEET 213 GRIBt EV2538
PERMIT At DSP141XXX PID 0 015-322-30 VV£2B4L27.SC50.DWG
Deep Trench:
2' Wide
40' Long
11' Max, Depth
8' Sewer Rock
3' Cover
3/16' hole 36' on Center
SCH40 1 1/4' Piping
N17 SCALE
Trench Elevation (TyP)
�- Monitors
Silt Barrier --
8 Ft of Septic Rock
I�EWAY
INS01.A1E UNDER DR
3 BDRM
SFR
I�INSTALL DIVERTER
IN LIFT STATIDN
1250 GAL
Q STEP TANK
1250 GALLDN STEP TANK
ISPURKLAND ENGINEERINGI I VALLI VUE ESTATES 12 BLK 4 LT 27 I I SEPTIC SYSTEM DESIGN
203 W 15TH. AVENUE
ANCH. AK. 99501 DAVIN PRINCE BA TE, SEPT 4 2014
(907) 279-3916 6257 WEST TREE DR ANCHORAGE AK 99507 SHEET 3/3 GRIDS SW2538
PERMIT # USP 141XXX PID #015-322-30 VVE5B4L27,D3.DWG
Spurkland Engineering
203 W.15th Ave. Ste. 202A
Anchorage, AK99501
TEST HOLE I L_
DEPTH
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
10
SOIL LOG AND PERCOLATION TEST
cnii DESCRIPTION DATE. 8/28/14
WAS GROUNDWATER OBSERVED. No
IF YES, AT WHAT DEPTH.•
AFTER MONITORING PERIOD. Div
DA TE OBSERVED: 9/4/14
PERCOLATION TEST.•
some sand
VOTES.- PRE-SOAKED
FILL
DATE I GROSS TIME
NET TIME I
DISTANCE
DROP
11.313
B 29 14 9.30 AM
0 min.
13.750
10:00 AM
30 min.
9.563
1.750
12.000
10:30 AM
30 min.
12.000
1.750
11:00 AM
30 min.
18250
1.750
PERCOLATION RATE.• 8.3 minutes/ inch
P£RC HOLE DIAMETER. 6 inches
TEST RUN BETWEEN 3 FT AND 4 FT
SITE PLAN.
N
SEE ATTACHED SITE PLAN
PERFORMED BY.• Anson Moxness. 1, Lars Spurkland P.E. CERTIFY THAT THIS TEST WAS PERFORMED IN
ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE.
SPURKLAND ENGINEERING VALU WE ESTATES /2 BLK 4 LT 27 1 ISOIL LOG PERCOLATION TEST
203 W 15TH. AVENUE
ANCH. AK. 99501 DAVIN PRINCE DATE, SEPT 4 2014
!9077 279-3916 11 6257 WEST TR££ DR ANCHORAGE AK 99507 GRID #.• SV2538
PERMIT # P171 # 015-322-30
MUNICIPALITY OF ANCHORAGE
- DE, ITMENT OF HEALTH AND HUMAN SERV..cS
Environmental Health Division
825 "L" Street, Anchorage, Alaska 99502, Telephone 264-4720
ON-SITE SEWAGE DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT
Name u�kle
Ttiemus N)
DISTANCES
TO
FROM
SEPTIC
TANK
ABSORPTION
FIELD
WELL
Address
st re- rjn'r.e R.,L%• 995"/d
J, 2S- We'T
Phonefs) Permit No. No. of Bedrooms
21ii 86 c a, bed upg"A
WELL
zoo
LOT LINE
af8
zoo f
LEGAL DESCRIPTION
Lot
Block
Subtlimsion
Township, Range. Section
see ! K T 1 2 IV A 3 ✓J'
AS-BUILT DIAGRAM
driveway, water bodies,
(Show location of well,
etc.)
septic system. property
Innes, foundation,
TANKS
❑ SEPTIC ❑ HOLDING
Manufacturer
�Xt C•}h
Capacity in gallons
I
Ne
'it
'iwt
7-4
EX
7�
E
5>Z�n
rSi
9
Material
No of Compartments
TYPE OF SYSTEM
TRENCH ❑ BED ❑ W. DRAIN ❑ OTHER
Depth to pipe bottom from
Original gradeFT
Total depth from original grade
3 FT
t
z.
.F
X
Fill added above original grade
FT
Gravel depth beneath pipe
6 FT
Gravellength
FT
Gravel width
a.S ^ .3-S FT
Total absorption area
91' SQ FT
Distance between Innes
FT
Number of hoes
Sol rating
2L13 SQ FT
Pipe material
CI F'8/a Da'L31JIL
Installer
Date Installed
WELLS
❑ PRIVATE ❑ OTHER (Identiiv)
Classification (A, B.C)
Total Depth
FT
Cased to
FT
Installer
Dale Installed.
REMARKS:
L7te ugde. (- f—x is C/ r',r so I- Ar'( it f-4 I/„
61o" l7rr.-✓ in'n`!` 2
Scale: NTS
Inspections Performed by
R ECS
ENGINEER SEAL
Dale:
I �rY,l certify that this
inspection was perlorrned according to all
Municipal and State guidelio in effect an this date:
Health Department Approval: zist'y
Date:
72-013 (3/85)
I17 A LIy�T STATIO% IS INSTALLED IN AN AREA CDVE�En RY MOA BUIL�JNG CODES,
THFM (1) �N ELECTR�CAL PF�MIT AND INSPECTIUN �UST BE �BTAINED; (2> AS-CU�LTS
WILL NOTDE APFRj.VED WITHOUT AN ELFCT��ICAL IN�PECTION PEPORT; AND (3> THE
ELECTRICAL WORK MUST BE DONE 9y A LICENSED ELECTRICIAN^
SI0NED ' DATE:
---�-C��-^�--^�~=~�~~~------------------ ---------------
APPLICANT: THnMAS J. MOCKLER
ISSU[�D DY /1 ` DATE: //.-c�/^
^—.--77-----------/-------------------- ------------
v
4�
'p-leT \J
2-4
u
�
������������
'
1ETiT HEALTu AI D E.I'd VICUN11[NT8L �OTECTIna
825 L STREET, ANCHORASE, AV 99501
��--:-j; �����T*
��
DATL. ISSUED:
10�31/O6
APPLICANT:
TXCMAS J, MOCuLER
��nDRESS:
6257 WEST TREE DR. IVE tt
4mG11-10RA9E, 79516
y.
�
iEGAi PFSCIRTP:
SURDJVISION: VALLI VVE LOT: 27 BLOCK: 4
SErTT[�N: 14 TOWNSHIP: 12N RANGE: 3W
LJT SIZE;
0.75A OR ACRES}
I cer+i[y that:
�
1. I em familiar
kmith the requirements for on-site sewer= and set �
forth by
the of Anchorage (MVA> and the State oi Alaska.
2. I will install
the system in ac�-ordance with all MnA codes and regulations, �
�
and in compli=nce with the design rriteria of this permit.
3. .1.
S�ate o� Alas�a r��back
o uiremen!s �or the set
distances
"rom any exist.ing well, wastewater disposal system or puhlic
sewerage
system on zn�Ulm..-,or any aoJacenz or nearb y lat.. �
I17 A LIy�T STATIO% IS INSTALLED IN AN AREA CDVE�En RY MOA BUIL�JNG CODES,
THFM (1) �N ELECTR�CAL PF�MIT AND INSPECTIUN �UST BE �BTAINED; (2> AS-CU�LTS
WILL NOTDE APFRj.VED WITHOUT AN ELFCT��ICAL IN�PECTION PEPORT; AND (3> THE
ELECTRICAL WORK MUST BE DONE 9y A LICENSED ELECTRICIAN^
SI0NED ' DATE:
---�-C��-^�--^�~=~�~~~------------------ ---------------
APPLICANT: THnMAS J. MOCKLER
ISSU[�D DY /1 ` DATE: //.-c�/^
^—.--77-----------/-------------------- ------------
v
4�
'p-leT \J
2-4
u
�
U
Municipality of Anchorage
DEPARTMENT OF HEALTH & HUMAN SERVICES
825 "L" Street, Anchorage, Alaska 99502-0650
SOILS LOG — PERCOLATION TEST
PERFORMED FOR: '%arn Mocicte DATE PERFORMED: R Z '(
LEGAL DESCRIPTION: Va!/� ✓/4e Na ruck Township, Range, Section: S« nt T /zN 23CJ-
SLOPE SITE PLAN
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
0'-J""c so;(
-Al s;7fij.ra,Jj
/0.yC.S W 074, /ayes o{'
�.vre Sancll layr•i u'r S/7?/
tpw/�eh or' amu' 9"avel
p�ketofs-,�ry,a,.eC
C ace firlly ran �e!'ra tafi'orr_
j -es t ,'-k� wo,--s'!- 90fy
(ayc�
WAS GROUND WATER
ENCOUNTERED? No
(S"11 seep S
.7a lafed
IF YES, AT WHAT roar -Ke -f /ens oi' O
DEPTH?P
E
Depth to Water After
Monitoring? /�PcY -/' /3' Date: z9 Oc><
Reading Date Gross
Time
Net
Time
Depth to
Water
Net
Drop
/ 23 /02 s
-
E s
-
/0g` -
30
15-0
. /S'
1125-
65.
-
per, ��l<hn.,
ham/ c' j[1en
r cQa-L.
20
lul PERCOLATION RATE 22%;7 (minutes/inch) PERC HOLE DIAMETER � rr
�I
TEST/ RUN BETWEEN 6 FT AND G Z FT
COMMENTS Ste;-/ ar ,Z �p /; H .^a?'ed +7.2 �' •rr. %.�%r l%'ul.. Srota/I .fee p clued 4p
G e r1,-aund wakes-' �-rowo-,ti�� i;/ a� e9 -�ve •i c/t .S '�-t. ra..n/c<(/ etc r�, .<fu.- .r�io „! C Ge to w {�'otis �. h d.. /CeeP ,.
t
PERFORMED BY: /Y 2—�10 CERTIFY THAT THIS TEST WAS PERFORMED IN
ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT q THIS DATE. DATE:
eye a �-, mepr,_ b.y.rs/w Gcd c.n'i( Gc
72-008 (Rev. 4/85) Rn y aj'
GREA,cR ANCHORAGE AREA BOR, JGH
omgphg))�
Department of Environmental Quality
3330 C Street
Anchorage, Alaska 99503
INSPECTION REPORT ON-SITE SEWAGE DISPOSAL SYSTEM
NAME
I. MAILING ADDRESS ��+�' u,y;(- /'%)���! ��,, PPHHONE
LOCATION LEGAL DESCRIPTION /,9 -7 A T (L�'�'-� r �'u'�r
SEPTIC TANK
DISTANCE//'' ����J44,,,�,,�ii(� NUMBER OF
FROM WELLi_MANUFACTURE MATERIALCOMPARTMEE,�vNQQ��TS
INSIDE LENGTH INSIDE WIDTH LIQUID DEPTH LIQUID CAPACITYGvOGALLONS.
TILE DRAIN FIELD:
� I I TOTAL LENGTH
DISTANCE FROM WELL FOUNDATION �f/' NEAREST LOT LINE e OF LINES ? �)
NUMBER OF LINESDISTANCE BETWEEN LINES941'AATRENCH WIDTHN. TOTAL EFFECTIVE
ABSORPTION AREA `Y SQ. FT. LENGTH OF EACH LINE
P DEPTH OF FILTER
r.r nr, ,. rnn nr r„ r Tn rinncu !_o nr1F -14 MATFRIAI RFNFATH TO F V IIsi ABOVE TILE IN.
WELL:
TYPE
9d)
INSTRUCTION
BUILDING NEAREST NEAREST SEPTIC SEEPAGE
FOUNDATION LOT LINE , SEWER LINE , TANK , SYSTEM_
CESSPOOL
OTHER SOURCES
APPROVED DISAPPROVED REMARKS
DISTANCES
DIAGRAM OF SYSTEM
INSTALLED BY: �(
� f
SEWER LINE DEPTH:_-�'--'�--- qhs'
r
PIPE MATERIAL:�c
LOT SLOPE:
REMARKS
DATEi9*t?J ! I APPROVED
Form EQ -032
DISTANCE FROM:
G.A.A.B. _ )
DEPARTMENT HEALTH AND ENVIF:CiNMENTAL 10TECTION
825 `' I_' STREET, ANCHORAGE, Fit:::. 99501 Ln - 3 - 1 `7 �p
27' +-'2511 A, ., � i, ht
I't -IF EO On FF=.GE_�.F:! F= F 'F�``a'1 :R I.
PERMIT NO- 771.70
APPLICANT BOB LUT TE SRA BOX 31-L 344-4602
i_2
LOCATION L•aEST TREE DR
LEGAL L27 B4 VAL.LI VUE LOT 'SIZE 22113 SQUARE FEEL"
TYPE OF SOIL AB S ORBT I ON SYSTEM IS: TRENCH
H
MAXIMUM NUMBER OF BEDROOMS. = - SOIL RATING <SO FT/BR)= 1.80
THE REQUIRED SIZE OF THE 501L ABSORPTION SYSTEM IS:
E-" °"8`�= - @__ 3•�e -T =_ C3F1FA"IE=L._. EVA E=F'
THE LENGTH DIMENSION IS THE LENGTH ON FEET) OF THE TRENCH OR D1=RAINFIELD.
THE DEPTH OF H TRENCH OR PIT IS THE DISTANCE. BETWEEN THE SURFACE OF THE
GROUND AND THE BOTTOM OF THE EXCAVATION (IN FEET).
THERE IS NO `_,ET WIDTH FOR TRENCHES.
THE GRAVEL DEPTH IS THE MINIMUM DEPTH OF GRAVEL BETWEEN THE OUTFALL. F'IF'E
AND THE BOTTOM OF THE: EXCAVATION (IN FEET).
F °FAC F= -I FAC3 E= F=° L _ F:T T -A "T_ a=: 0" C l Lf a F F r_" Mao CA/
EITHER A CLASS I OR II NSF APPROVED PLANT MAY BE INSTALLED.
A CONTINUOUS MAINTENANCE AGREEMENT IS REQUIRED. IF A MAINTENANCE
AGREEMENT IS NOT KEPT CURRENT YOU MAY BE REQUIRED TO ENL..ARGE. THE SOIL.
ABSORPTION SYSTEM AND/O6 YOU MAY BE. SUBJECT TO PROSECUTION.
IF R 66AQ9 I.
Z E-rr%A95 11 - i STEM 19 UlEr THE
S NJ ED wj § = s 3E V -J F=" FE JE ED VA on d-4 F<" E- lE l_ -a @._B 1 F' EE L.. -'q
BACKFILLING OF ANY SYSTEM WITHOUT FINAL INSPECTION AND APPROslAL. BY THIS
DEPARTMENT WILL BE SUBJECT TO PROSECUTION.
MINIYU_M DISTANCE BETWEEN A WELL AND ANY ON-SITE SEWAGE DISPOSAL.- SYSTEM I:.,
100 FEET FOR H PRIVATE_ WELL OR 200 FEET FOR H PUBLIC WELL.
SPECIFICATIONS AND CONSTRUCTION DIAGRAMS ARE AVAILABLE TO INSURE PROPER
INSTALLATION.
F=" L=` fy" f-1 I T °_"i" 1=1 E__ I Ex F= C h Fes" u �®VA EE "e° E= fA Fp_ F= FQ C a VI 1 so 45 k j F_*
I CERTIFY THAT
1: I AN FAMILIAR WITH THE REQUIREMENTS FOR ON-SITE SEWERS AND WELLS AS SET
FORTH BY THE MUNICIPALITY i iF ANCHORAGE.
I WILL. INSTALL THE SYSTEM IN ACCORDANCE: WITH THE CODES.
3: I UNDERSTAND THAT THE ON-SITE SEWER SYSTEM MAY REQUIRE ENLARGEMENT IF THE.
RESIDENCE I_. REMODELED TO TpJ+�4-.UC:• MORE THAN <: BEDROOMS.
AF• _ I �_ Atdl" E:C�E; I....I_' '.7'F_
ISSUED BY.. --------- ATE --
_._..__..._..__..-_._
TABLE A
Lot 27, Block 4
W.O. #8585
Depth in Feet
From To
Soil Description
0.0' 1.0'
F-4, brown, peat, Pt, damp, soft
1.0' 12.0'
F-4, tan, gravelly sandy silt, ML,
damp, stiff, NP, maximum particle
size 6"
12.0' 16:0'
F-2� brown, slightly silty sand, SM,
15%- silt at 12.51, 10%m silt at
15.01, damp to saturated, medium
density
16.0' 20.0'
F-4, tan, sandy silt, ML, damp to
saturated, stiff, NP
Bottom of Test Hole:
20.0'
Frost Line:
None Observed
Free Water Level:
15.0'
Type of
Sample Depth
of Sample Unified
1 2.5'
G ML
2 5.0'
G ML
3 7.5'
G ML
4 10.0'
G ML
5 12.5'
G ML
6 15.0'
G SM
7 20.0'
G SM
JEST
�'E E
:i P -
A/0
2Vs��
w+/lS w iA•d Zcci'
?u ffAJ 4V_L _
0 00 /
`/
iVA
9 ' O
��`dS6, 6 • Z6 ,
Zo - Srer��
MOTE:
This As -built shall not be used for
oily Purp9se ottor than financing -
raQJlrEfl!"BtS. no circumsta!iceS
Sil�ilid Apy [:'.^:3 f3r5Cn bo Used for
construction or for es
tab lisititng
beune,ary or fence lines.
Recerf%{'ed 10-16 A61ij
4. v �
07
F:,g,r..f NTS Of r..CCiC "_•': sTTliFN
aOSE Si'.:; K't• Gca .-_ .._'•[CEC
- AT ARE NOT S-
OR
I hereby certify that I have surveyed the following
described property: (.0 7 % -7 - R L= 4 -
YQl-fel VUa TESTA -TFL V'';JT• 2
Anchorage Recording Precinct, Alaska, and that the
improvements situated thereon are within the property
lines and do not overlap or encroach on the property
lying adjacent thereto, that no improvements' on pro -
erty lying adjacent thereto encroach on the premises to
question and that there are no roadways, transmission
lines or other visible easements on said property except
as indicated hereon. -
Dated at Anchorage, Alaska
thise8tL day of . il)LV 19_J..i
FRED WALATKA & ASSOCIATES
`F!—:-',,-' and Cnr-
'<�
,�..7err
0
_
O
Ve9raa"n
l
z , A�
I
9 ' O
��`dS6, 6 • Z6 ,
Zo - Srer��
MOTE:
This As -built shall not be used for
oily Purp9se ottor than financing -
raQJlrEfl!"BtS. no circumsta!iceS
Sil�ilid Apy [:'.^:3 f3r5Cn bo Used for
construction or for es
tab lisititng
beune,ary or fence lines.
Recerf%{'ed 10-16 A61ij
4. v �
07
F:,g,r..f NTS Of r..CCiC "_•': sTTliFN
aOSE Si'.:; K't• Gca .-_ .._'•[CEC
- AT ARE NOT S-
OR
I hereby certify that I have surveyed the following
described property: (.0 7 % -7 - R L= 4 -
YQl-fel VUa TESTA -TFL V'';JT• 2
Anchorage Recording Precinct, Alaska, and that the
improvements situated thereon are within the property
lines and do not overlap or encroach on the property
lying adjacent thereto, that no improvements' on pro -
erty lying adjacent thereto encroach on the premises to
question and that there are no roadways, transmission
lines or other visible easements on said property except
as indicated hereon. -
Dated at Anchorage, Alaska
thise8tL day of . il)LV 19_J..i
FRED WALATKA & ASSOCIATES
`F!—:-',,-' and Cnr-
TO �1
�- L _
%}
SUBJECT � r
MESSAGE
e
FROM
N
DATE
013°
d�-�.� �� Com` -f .:'- 7 'G.'�a��'• i`e�' A s SY��:f�� "" F��^ �'' •�-' I4 ��F�6 �/J
REPLY 14AX
L
1 f �•`
/ bT
(ZeAkUK i;6is� OohA
t (s ! 0
t� i`
RstdiSEND PAR75 1 AND 3 WITH ARGON INTACTA- PARTS WILL `BEE RETURNED WITH REPLLY..
91 45 472 V, P +��y p t- IJ C.-f.1T � �,e `� /�7. �(p• 6,/ ,,
PDly Pak(50sels)4P4]] v.
September 8, 1975
W.O. #8585
Mr. Carl Pruett
Valli-Vue Estates
P.O. Box 4-1141
Anchorage, Alaska 99509
,_V
E"IVED S 9 s5i
4040 "B" STREET,
ANCHORAGE, ALASKA 99503
PHONE: 907-279.2581
!ti®i P4AA)r-`P--PNet(
11 Dl I it
RE: Subsurface Investigation for On -Site Sewer Systems
Lots 26, 27, 28, 29 and 30, Block 4, Valli-Vue Estates
Dear Mr. Pruett:
Transmitted herein are the results of the subsurface investigation
performed on the above referenced lots, August 25 and 26, 1975.
The drilling was done with a Mobile Drill B-50 drill rig mounted
on a Flextrack-Nodwell track vehicle, owned and operated by
Denali Drilling, Inc. The test holes were logged and the drilling
supervised by Mr. O.M. Hatch, senior technician/staff geologist
with Alaska Testlab. The locations of the test holes are sketched
on the attached Figure 1.
Table A is the logs of the test holes drilled. The standard
explanatory information contained in the back of this report
will be helpful in interpreting the data contained on the test
hole logs.
Classification of the soils is by the unified soil classification
system, but was done visually. It would therefore be prudent
to keep in mind that the classifications are not necessarily
exact and the silt contents listed were estimated.
All five (5) of the test holes drilled showed a considerable
amount of silt to a depth of 10.0 to 15.0 feet below the ground
surface. Therefore the holes were all taken to a depth of 20.0
feet below the ground surface.
On Lots 28, 29 and 30 no water table was encountered for the
full depth of the test hole. These holes were filled with water,
let set over night, refilled and monitored.
Over a period of 1-1/2 hours, the percolation rate for Lot 28
was 2.8 minutes per inch; the percolation rate for Lot 29 was
5.5 minutes per inch and the percolation rate for Lot 30 was
3.3 minutes per inch. Using the data contained in Table A -
"Absorption Area Requirements for Individual Residences" on
page 8, of the "Manual of Septic Tank Practice", published by
3�b
Mr. Carl
Page 2
September
Pruett
8, 1975
the U.S. Department of Health, Education and Welfare, the absorp-
tion area requirements per bedroom for a seepage pit placed
in the material represented by these test holes would be 100
square feet, 130 square feet and 115 square feet for Lots 28,
29 and 30, respectively.
We would like to point out, that though these percolation rates
are for the entire hole being percolated, �t is our feeling_
that most of the p-�_colation�took_2lace in the more c{x a ulama
materia -s below tkle We would therefore recommend that
the ---above mentioned absorption requirements be utilized only
if the seepage pits are placed down in the more granular strata.
If this is not done, a more conservative value for the absorption
area requirements should be utilized.
l.0\ V'y
On Lot 26 the water table was encountered at 17.0 feet, while
on Lot 8/the water table was encountered at 15.0 feet. Recogniz-
ing a if�e Greater Anchorage AreaWBorougii; Department of Environ-
mental Quality will not allow the bottom of a seepage pit to
be any closer. to the water table than 4.0 feet, we redrilled
a hole adjacent to the existing test holes on Lot 26 and 27
to a depth of 4.0 feet above the water table - - - f3.0 feet
on Lot 26 and 11.0 feet on Lot 27.
These second test holes were filled with water, left to saturate.'.
over night, refilled and percolated. This was done on _September
4, 1975. The percolation rate for Lot 26 was 5.0 minutes per
inch while the percolation rate for Lot27 was 6.7 minuestper
inch. _..
Again utilizing the published data previously referenced, the.
absorption area requirements for a seepage pit placed on Lot
26 would be 125 :s -quare feet per bedroom while the absorption
area requirements on Lot 27 would be 175 square feet per bedroom.
It is our feeling that the absorption area requirements listed
in the above paragraph for Lots 26 and 27 are probably a little
low. The bottom of each test hole on the lots just did penetrate
a more granular layer below the silt (see the test hole logs).
The high percolation rates may be a reflection of this granular
material in the bottom of -the holes. With this in mind, it
would be prudent to use a more conservative value for the absorp-
tionn areq_requirements on both lots. we would suggest a value
more on the order of 250 square feet per-b�dr
Also, we would like to note that the values for the water table.
listed on the logs are for the date of exploration only. The
water table will fluctuate with seasonal and climatic changes.
Mr. Carl Pruett
Page 3
September S, 1975
We hope that this information is sufficient for your present
needs. If we can offer any clarification or be of further service
or help to you, please do not hesitate to contact us.
Very truly yours,
ALASKA TESTLAB
g - ?, L
4-C� Q
", L
Melvin R. Nichols, C.E. Approve .
Laboratory Supervisor Harry Lee, P.E.
MRN/HRL/vms
4040 "B" STREET,
ANCHORAGE, ALASKA 99503
PHONE: 907-279-2581
May 17, 1976
W.O. 17667
Grid 2538
Timberline Homes
SRA Box 31-L
Anchorage, AK
Attention: Mr. Bob Lutje
Subject: Subsurface Investigation - Lots 9 and 27, Blk 4
Valli-Vue Estates
.Dear Mr. Lutje:
Transmitted herein in accordance with your instructionsare
the results of the above referenced investigation as performed
by us on May 11 and 12, 1976. The scope of this project is
invest;_gat9_oi, for suitability of on-site sewerage systems.
Included in this transmittal are:
Vicinity Map Figure 1
Test Hole Location Sketch Figure 2
Test Hole Log Table A
Explanatory Information Sheets 1-3
The exploration was conducted using a Nodwell mounted Mobile
Drill model B-50 drill rig with a continuous flight solid
stem auger. The rig is owned and operated by Denali Drilling Inc.
Drilling was supervised, the test holes logged,.and the percolation
test run by Mr. R. Mark Hansen, engineer with Alaska Testlab.
The test holes were placed at the approximate locations shown
on Figure 2. Logs of these test holes are included as Table A
of this report. In interpreting the logs it would be helpful
to utilize the explanatory information contained in sheets
1 to 3 of this report.
When drilling was completed a 3/4" slotted PVC pipe was inserted
in the hole to aid in determining the free water level. For
the percolation test, the test hole was filled with water
a
Timberline Homes
May 17, 1976
Page 2
and left overnight to saturate. On returning, the hole was
refilled with water and the drop in the water level carefully
monitored over the next 60 minutes.
This procedure is not a standardized percolation test, however,
we understand that the Anchorage Department of Environmental
Quality prefers tests performed in this manner to evaluate
a site for a proposed on-site sewerage.system.
Using the above test, the observed minimum percolation rate
for Loi. 9 was 10 min. per inch, and for Lot 27 it was 12 min.
per inch. No water table was observed during drilling, but
it should be noted that the free water level normally fluctuates
seasonally and with precipitation.
We hope this report meets your present needs. If we can be
of further service, please feel free to contact us.
Approved:
c�
.kelvin R. Nichols, CE
Laboratory Supervisor
RMH: mm
Attachments
Very truly yours,
A L A S K A T E S T L A B
R. Mark Hansen
t
a . ' F MCMAUTY OF
11 . �a
Development Services Department
On-Site Water & Wastewater Section
Certificate of On -Site Systems Approval
Parcel I. D. 015-322-30
1. GENERAL INFORMATION
Phone: 907-343-7904
Fax: 907-343-7997
Expiration Date: 7-z3 Z OZ�
Complete legal description VALLI VUE ESTATES #2 BLOCK 4, LOT 27
Location (site address) 6257 WEST TREE DRIVE, ANCHORAGE, AK 99507
Current property owner(s) TRACY CHRISTOPHER & AARON WELLS
Mailing address
Real estate agent
Day phone
6257 WEST TREE DRIVE, ANCHORAGE, AK 99507
2. TYPE OF DWELLING:
® Single Family (w/wo ADU)
❑ Duplex
❑ Multiple Dwellings (Single Family and/or Duplex)
Day phone
3. NUMBER OF BEDROOMS:
3
4. TYPE OF WATER SUPPLY:
TYPE OF WASTEWATER DISPOSAL:
Private Well
❑
Private Septic
Water Storage
❑
Holding Tank
❑
Community Well
®
Community
❑
Public Water System
❑
Public Sewer
❑
Waiver request for: Distance:
Received by:
COSA to be released to the engineer, unless otherwise requested by the engineer.
COSA Fee $ 5 5 b
Date of Payment 7�Z6�z l
Receipt Number 71626 '2—
COSA #
COSA# n5CV1 x{30
Date:
Waiver Fee $
Date of Payment
Receipt Number
Waiver #
5. STATEMENT OF INSPECTION BY ENGINEER
As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based
on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the
on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of
bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the
Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater
disposal system is (are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in
effect at the time of installation. I acknowledge that On -Site staff may visit the site to verify the information submitted.
Name of Firm FIRST WATER CONSULTING Phone 907-350-9566
Address 13030 SUES WAY, ANCHORAGE, AK 99516
Engineer's Printed Name CURTIS HUFFMAN, PE Date 7/24/2021
Comments: This investigation was completed in compliance with MOA guidelines, regulations,
and best industry practices / methods. The assessment of the condition of the well and septic
applies only to the conditions as of the day tested. The flow and absorption rates may change
due to subsurface conditions that may not be observed from the surface, changes in land use,
local soil characteristics, groundwater levels that may fluctuate during the year, quality of
construction (workmanship & materials), the water usage of the family being served by the
system and maintenance. The operational life of all well and septic systems are subject to
these various and dynamic characteristics and are outside the control of the evaluator of the
well and septic system. Therefore, any estimate of how long a system will function satisfactory
for current or future occupants or guarantee that no unseen encroachments, deficiencies or
discrepancies exist can be given by First Water Consulting & FWCS
6. DSD SIGNATURE
System #1 Approved for 13 --bedrooms
System #2 Approved for bedrooms
Disapproved
.s
i g�P 711-111-
• • ' . • ,. •
Curtis Huffman' �
r�¢ FFG,/•, CE 128991 Aw/
PROF SS00P�Fe�...
Conditional approval for bedrooms, with the following stipulations:
-2q-I`i giovk
CY i'' �N��P `t—rti IM P C'�1 �`�-�� OF
c
leb 4P_4 i, Jk-u (Al
47n Re ON-SITE
WATER AND Z
NSI
By' . �...•� Original Certificate Date: V 1
The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the
representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is
not responsible for errors or omissions in the professional engineer's work.
7. ATTACHMENTS:
COSA Checklist X Nitrate Advisory
Septic System Advisory Arsenic Advisory
Well Flow Advisory Other
Legal Description: VALLI VUE ESTATES #2 BLOCK 4 LOT 27 Parcel ID: 015-322-30
If more than 1 septic system on lot: COSA Checklist # _of _ Structure served by this system _
A. WELL DATA — COMMUNITY CLASS A
❑ Well log is filed with Onsite (or attached)
Date drilled
Total depth _ft
Cased to ft
❑ Sanitary seal is functioning correctly
❑ Wires are properly protected
Casing height (above ground) _in.
Date of flow test for COSA
Static water level at beginning of test _ft.
Comments
B. TANK DATA
Age of tank(s) 7 years
Tank type/material STEP / STEEL
Measured operating fluid level in septic tank
® Standpipes/foundation cleanout per record drawing
Date of pumping 7/19/2021
D. ABSORPTION FIELD DATA
Which system tested (date installed) 9/20/2014
® ALL standpipes present per record drawing
Total measured depth from grade 11.6 ft (max)
Measured depth to pipe invert from grade ft (min)
® N/A — pressurized field
❑ Monitor tubes go to bottom of effective. If not, state
depth into effective
Well production at time of test _gpm
Water storage tank volume_ gallons
Well disinfected for coliform test? ❑ Yes ❑ No
❑ Coliform bacteria is Negative
Nitrate _mg/L ❑ Nitrate less than MRL (ND)
Arsenic ug/L ❑ Arsenic less than MRL (ND)
Collected by
Date of Sample
C. LIFT STATION
® Required maintenance completed
Age of lift station 7 years
Lift station material STEEL
Comments: *FLOAT LEVELS
Adequacy test date 7/23/2021
Results Z Pass For 3 bedrooms
Fluid depth prior to test 52 in
Water added 500 gal
New depth 74 in
Elapsed time 1400 min
® Code -required soil cover over field Final fluid depth 52 in
❑ System presoaked Absorption rate 450 gpd
(Required if vacant for greater than 30 days prior to Any rejuvenation treatment (past 12 months) N
date of test) If yes, enter date
Gallons introduced gallons
Comments/Deficiencies: FIELD OPERATING IN THE TOP HALF OF THE EFFECTIVE DEPTH (8.3' ED TOTAL).
E. SEPARATION DISTANCES
From Private Well on Lot to: (Please enter distances if less than required or if community well)
Septic Tank/Lift Station on Lot > 100'
❑ Yes
if No
Community Sewer Manhole/Cleanout > 100'
❑ Yes
if No
ft
❑ Yes
if No
Neighboring Tank > 100' ❑ Yes
if No
ft
Private Sewer/Septic Line > 25' ❑ Yes
if No
Absorption Field on Lot > 100' ❑ Yes
if No
ft
Holding Tank > 100' ❑ Yes
if No
Neighboring Absorption Fields > 100'
if No
ft
Animal Containment > 50' ❑ Yes
if No
❑ Yes
if No
ft
ft
If septic tank is under driveway comment below
Manure/Animal Excreta Storage > 100'
Community Sewer Main > 75' ❑ Yes
if No
ft
❑ Yes
if No
From Septic/Holding Tank on Lot to: (Please enter distances if less than required)
Building Foundations > 10'
❑ Yes
if No
*5+ ft
Surface Water > 100'
® Yes if No
Property Line > 5'
® Yes
if No
ft
Wells on Adjacent Lots:
® Yes
Absorption Field > 5'
® Yes
if No
ft
Private Wells > 100'
® Yes if No _
Water Main > 10'
® Yes
if No
ft
Community Wells > 200'
® Yes if No _
Water Service Line > 10'
® Yes
if No
ft
If septic tank is under driveway comment below
From Absorption Field on Lot to: (Please enter distances if less than required)
Building Foundation > 10'
® Yes
if No
ft
If absorption field is under driveway comment below
Property Line > 10'
® Yes
if No
_ ft
Wells on Adjacent Lots:
Water Main > 10'
® Yes
if No
ft
Private Wells > 100' ® Yes if No ft
Water Service Line > 10'
® Yes
if No
ft
Community Wells > 200' ® Yes if No
Surface Water > 100'
® Yes
if No
ft
F. ENGINEER'S COMMENTS
*PER CODE AT INSTALL.
G. ENGINEER'S CERTIFICATION
l certify that l have determined through field inspections and review
of Municipal records that the above systems are in conformance
with MOA COSA guidelines in effect on this date.
TH
.. .... ....t......
Curtis Huffman
�� �'•��, •. CE 12899104;1
AW
e * -.7124/21.-* <c�-'.
���F�pROfESS10NP
ft
ft
ft
ft
ft
ft
ft
ft
MUNICIPALITY OF AN(NICYAGEE
3�1111
-SAIdge love!
l
Lift stat an:
}Pumz
.) 13 -9 s k e I c Ie a rj e-
PCOMW foats chaned n
Maintenatrice Log
9
Qumping: requInd yag 4g!
c- r f I o et ti,
c-! c c t 1- i c a I a I a 7 91r ca 111 GRI w Judd"e -in,-,!
DIT, aq n hKodlee SRI! icer
-Ground voVer riser to tank conn.c.,c-Jon
-Ground water iritr-i_.sbn around pipe penetratio.. :5-
i
-Ivianhole lid',:
Rjrvctional noc,
Insulatec,
P
es o
,Ith-7cp hole s �,- -1o,
Toperw Swourso
o,q)er
-All ma?'!!, ractturer inspections arid rnainfc-nvan(wa corriplated
4 t,r.r,.r"mm+,w-
T12
Qualified NVaintonance Pr ori er
A
I.
10,ratc of rnainLenance.
C 0 rar) P a r, y
Parcel I.D� 015-322-30
Municipality of Anchorage
On -Site Water and Wastewater Program
(907)343-7904
Certificate of On -Site Systems Approval
1. GENERAL INFORMATION
Complete legal description
Expiration Date: 9 " 2 ®'e /
VALLI VUE ESTATES #2 BLK 4 LT 27
Location (site address) 6257 WEST TREE DRIVE
Current Property owner(s) DAVID PRINCE
Mailing address
Real Estate Agent
Day phone
Day phone
2. TYPE OF DWELLING: Su"ITTAL
Q Single Family (w/wo ADU) RUSH!
❑ Duplex I SEP 2 5 2014
❑ Multiple Dwellings (Single Family and/or Duplex)
3. NUMBER OF BEDROOMS:
3"ter
2
4. TYPE OF WATER SUPPLY:
TYPE OF WASTEWATER DISPOSAL:
Individual Well
❑
Individual Q
Individual Water Storage
❑
Holding Tank ❑
Community Class A Well
®
Community ❑
Public Water System
❑
Public Sewer ❑
WaiverNariance request for: NONE Distance: --
Received by: Date: ?
COSA to be released to the engineer, unless otherwise requested by the engineer.
COSA Fee $ X09 .5z> Waiver Fee $
Date of Payment Iq
r Date of Payment
Receipt Number _ _ �� �Y Receipt Number
COSA # OJU4 1,510 Waiver #
5. STATEMENT OF INSPECTION BY ENGINEER
As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation,
based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application,
shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate
for the number of bedrooms and type of structure indicated herein. I further verify that based on the information
obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water
supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes,
ordinances, and regulations in effect at the time of installation.
Name of Firm SPURKLAND ENGINEERING
Address 203 W. 15TH AVE.,STE.202A, ANCHORAGE, AK 99501
Engineer's Printed Name LARS SPURKLAND
6. DSD SIGNATURE
System #1 Approved for 3 bedrooms
System #2 Approved for bedrooms
Disapproved
Conditional approval for bedrooms,
Phone 279-3916
Date 9/22/14
a f �4�1��
Q7, •
9TI-ic
�...:..O
�����CCCnnn E. SPUFKLAND,w //
c}'
i,1 FQ . • 1150f 4. •�F�c'l�
Ekk`"�IYOFESSiON�=
with the following stipulatiblR�9.����
By: [�{/ Original Certificate Date: 9-30-114
The unit; ality o- nchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only
upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality
of Anchorage is not responsible for errors or omissions in the professional engineer's work.
7. ATTACHMENTS:
COSA Checklist X Nitrate Advisory
Septic System Advisory Arsenic Advisory
Well Flow Advisory Other
COSA blue aheel L . ( c
If more than 1 septic system is on the lot:
COSA Checklist # 1 of 1
Structure served by this system 1
Certificate of On -Site Systems Approval Checklist
Legal Description: VALLI VUE ESTATES #2 BLK4 LT 27
A. WELL DATA
Well type A If A, B, or C provide PWSID # 210605
Date completed Sanitary seal (Y/N)
Total depth ft. Cased to ft.
FROM WELL LOG
Date of test
Static water level ft.
Well production 9 -
P.m -WATER SAMPLE RESULTS:
Coliform colonies/100 mL Nitrate mg/L
Arsenic _ ug/L Date of sample:
B_ SEPTIC/HOLDING TANK DATA
Tank Type/Material STEP/STEEL
Tank size 1250 gal. Number of Compartments
Foundation cleanout (Y/N) Y Depression over tank (Y/N) N
Date of pumping NEW Pumper
Parcel ID: 015-322-30
Well Log (Y/N)
Wires properly protected (YIN)
Casing height (above ground) in.
AT INSPECTION
ft.
E! raw
Collected by: _
Date installed 9/19/14
Cleanouts(Y/N) Y
High water alarm (YIN) 'T
C. ABSORPTION FIELD DATA
Date installed 9/20/14 Soil rating (g.p.d./ft2 or felbdrm) 0.8 System type TRENCH
Length 40 ft. Width 3 ft. Gravel below pipe 8.3 ft.
Total depth 11.5 ft Eff. absorption area 664 fl2 Monitoring tube Y Depression over field N
Date of adequacy test NEW Results (Pass/Fail) For _ bedrooms
Fluid depth in absorption field before test in. Water added gal. New depth _ in.
Elapsed Time: min. Final fluid depth in. Absorption rate >= g.p.d.
Any rejuvenation treatment (past 12 mo.) (Y/N & type) If yes, give date
D. LIFT STATION
Date installed 9/22/14
"Pump on" level at 25 in.
Datum TOP PUMP VAULT
E. SEPARATION DISTANCES
WELL ON LOT TO:
Septic tank/lift station on lot
Absorption field on lot
Public sewer main
Sewer /septic service line _
Animal containment areas
Size in gallons 1250
"Pump off" level at 44.5 in
Cycles tested NEW
Manhole/Access (Y/N) Y
High water alarm level at 22'5
Meets alarm & circuit requirements? YES
On adjacent lots _
On adjacent lots _
Public sewer manholetcleanout
Holding tank _
Manure/animal excrete storage areas
SEPTIC/HOLDING TANK ON LOT TO:
Building foundation 5+ Property line 5'+
Water main 10+ Water service line 10'+
Wells on adjacent lots 200+
ABSORPTION FIELD ON LOT TO:
Property line 10+ Building foundation 10+
Water Service line 10+ Surface water 100+
Curtain drain 50'+ (N.O.) Wells on adjacent lots 200+
F. COMMENTS
`EXISTING WAIVER
G. ENGINEER'S CERTIFICATION
I certify that 1 have determined through field inspections and
review of Municipal records that the above systems are in
conformance with MOA COSA guidelines in effect on this date.
Engineer's Printed Name LARS SPURKLAND
Date 9/22/14
cosA brown sheet 10-10-12.doc
Absorption field 51+
Surface water 94
Water main NA
Driveway, parking/vehicle storage 100
in.
7525E
;o c
ZON r m WEST TREE DRIVE
OQ
U) II
5O5n
-iO
=
mA
Aa
;o M
O
O2
A
Z0� oT
O ? U)
a m
cn _
� c
T Q
W � 20
d\� R=50.00 L=50.00
�► Y6��3�,� � .S' �, Z 7 � q
Q. FI oo a� g r „`.
Q.
006
5 .000
00 00
00
00
\ OOD
� o co
,f iGRA +• �� rn 0) 7 �$� 'm \\ N
SF' o
r
N x \m
M
r
N \
o w?L WEr 0- m 3 m C/) r \
a o O
rnrn a� mm53=mm
OOH, O 3 0 09 3N o
O dtP \ N ma6eule;0
H S
_ O' Z£aUl
ace
ls'B.mnao A 1u�M,� 00'Vmm mfi
'amo Za n, m 00--o 's 2, m 0
vm,
m
�S m ido 3.ma m
5-1
-oa
0
`o cn No n$ca,z 'oma W D
0 OmUlm
M F'�-'c '� A Ili
MUNICIPALITY OF ANCHORAGE
DEPARTMENT OF HEALTH AND ENVIRONMENTAL PROTECTION
DIVISION OF ENVIRONMENTAL HEALTH nn''
CERTIFICATE OF INSPECTION FOR HEALTH AUTHORITY APPROVAL L'; q -I on
OF ON-SITE SEWER AND WATER FACILITY
264-4720
Application Date
1. GENERAL INFORMATION
(a) Legal Description (include lot, block, subdivision, section, township, range)
Va Ili (/ke *z Blecr- 4 Lot Z.� S-,, 1� ?t IN P-sU
Location (address or directions)
6 zsi We'st'Tre�
(b) Applicant Name Telephone: Home 3`l6 f 4k Business
Applicant•Address 6 zS �` Wes'f gree AActy A} _ 1Y5 -l6
(c) Applicant is (check one): Lending Institution ❑ ; Owner/builder Buyer ❑ ; Other ❑ (explain);
(d) Lending Institution Telephone
Address
(e) Real Estate Company and Agent
Address
NAS
Telephone
(f) Mail the HAA to the following address:
2. TYPE OF RESIDENCE,',
Single -Family Multi -Family ❑ Other
,
Number of Bedrooms ,3
3. WATER SUPPLY
Individual Well ❑ \ Community Public ❑
Note: If community well system, must have written confirmation from the State Department of Environmental Conservation
attesting to the legality and status. .
4. SEWAGjE%ISPOSAL
Onsite Public ❑ Community ❑ Holding Tank ❑
Note: If/community well system, must have written confirmation from the State Department of Environmental Conservation
attesting to the legality and status.
Page 1 of 2 72-025 0;iM
^�`1 Vrtiivvt .-
5. ENGINEERING FIRM PROVIDING INSPECTIONS, TESTS, FILE SEARCH, DATA AND INFORMATION
91
As certified by my seal affixed hereto and as of the validation date shown below, I verifythat my investigation of this Health
Authority Approval shows that the on-site water supply and/or wastewater disposal system is safe, functional and adequate
for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained
from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or
wastewater disposal system is in compliance with all Municipal and State codes, ordinances, and regulations in effect on
the date of this inspection.
Name of Firm R Fe S' Telephone s'-6 r 3ro �/O
Address
Date
Loo r f 3 �'� /%. 14,
//—S"'.F-6
//Cc - 2251 ti .9'ory�
Y e'
DHEP APPROVAL
Approved for bedrooms byDate
Approved Disapproved Conditional
Terms of Conditional Approval
CAUTION
The Muncipality of Anchorage Department of Health and Environmental Protection (DHEP) issues Health Authority
Approval certificates based solely upon the representations given in paragraph 5 above by an independent professional
engineer registered in the State of Alaska. The DHEP does this as a courtesy to purchasers of homes and their lending
institutions in order to satisfy certain federal and state requirements. Employees of DHEP do not conduct inspections or
analyze data before a certificate is issued. The Municipality of Anchorage is not responsible for errors or omissions in the
professional engineer's work.
Page 2 of 2
72-025 (11/84)
PN OWp,GE
p1,uN1GDE t` t W PR0 EOt10N
EN'J1W�M
A. WELL DATA�CC�`
Well Classification
Well Log Present (Y/N)
Total Depth Cased to
Static Water Level
Casing Height Above Ground
Electrical Wiring in Conduit (Y/N) —
Separation Distances from Well:
To Septic/Holding Tank on Lot
MUNICIPALITY OF ANCHORAGE (MOA)
HEALTH AUTHORITY APPROVAL (HAA)
CHECKLIST - FEBRUARY 1984
264-4720
Legal Description: 1/a ((' Vke 11 1 8104 y Lo 2 }
Sec 1-( 7-/2-N R3Wr
If A, B, C, D.E.C. Approved49N)
Date Completed Yield
To Nearest Edge of Absorption ' d on Lot
To a:anou
t PuEnhle
ine
Waple by
Water Sample Test Results
Comments
B. SEPTIC/HOLDING TANK DATA
Depth of Grouting -
Pump Set At
Sanitary Seal asing (Y/N) —
)epr on Around Wellhead (Y/N)
cotnmunk 1
Wei\ On Adjoining Lots
On Adjoining Lots
To Nearest Public Sewer
To Nearest Sewer Service Line on Lot
Date
Date Installed 6-6-77 Size 1000 No. of Compartments
Standpipes ON) Air -tight Caps &N) Foundation Cleanout (9/N)
Depression over Tank (Y/10 Date Last Pumped l0 -I a -fr6•
Pumping/Maintenance Contract on File (Y/N) NA ; for /vAl
Holding Tank High -Water Alarm (Y/N) ^v R Temporary Holding Tank Permit (Y/N) NA
Separation Distances from Septic/Holding Tank:
To Water -Supply Well Zoo To Building Foundation
To Property Line r `!& To Disposal Field So'•fa new -/re,,,/
To Water Main/Service Line Gr /O To Stream, Pond, Lake, or Major Drainage
Course
Comments wavee regvesfeeL--1e*e, a/factied.
Page 1 of 2
72-026(11/84)
C. ABSORPTION FIELD DATA Uu)17U rc 2 Blo R LoT 2 F.
Soils Rating in Absorption Strata 2q3 ad -1 usW) nrw 6cu4 Type of System Design 7renc4
Date Installed Length of Field 361 Olt/ y/ new
Width of Field 36 .1d 30"- yz' A!w Depth of Field I2""ld /3' new
Gravel Bed Thickness
gt 0U 6 ne
Square Feet of Absorption Area 5qo p' olJt y qZ ra %rw Standpipes Present (9N)
Depression over Field (Y/I0 Date of Last Adequacy Test to -7 V- $G
Results of Last Adequacy Test ur'S ysreM
frfnel, wu"tA
Separation Distance from Absorption Field:
To Water -Supply Well 2001
ecf 7,9'. / 6edr-00, r only, t6c
rWMS W< -X
To Property Line
To Building Foundation /l new
Lot SO < + % o!,/ sK1%a1 On Adjoining Lots
. To Existing or Abandoned System on
3 "} r
To Water Main/Service Line 10" To Cutbank (if present) IV A
To Stream/Pond/Lake/or Major Drainage Course /0O7+ iu ^ew /, ,,, y) 9�/ A, V WA
To Driveway, Parking Area, or Vehicle Storage Area /Y r Aram Aew ^� cPr, K 0"' n.�
-Y1zc/ ear, -s
6e L' fry cf r.r
Comments w<a ve.- re veS kai -- /efk.
D. LIFT STATION
Date Installed
Size in Gallons
Pump On" Level at
Dimensions
Off' Level at
High Water Alarm Level at N A Vent (Y/N)
Tested for
Electrical Codes (Y/ )
f`nm mcnf
** Check Permitted Bedroom Rating Against HAA Request **
Pumping Cycles during Adequacy Test. Meets MOA
I certify thatJI h hecked, verified, or conformed to all MOA and HAA guidelines in effect on the date of this inspection.
Signed ` Date //-S'-eK a®pq
Company /tF S MOA No. 51 8c n zc ¢ �` o•A<9 ®?
Receipt No.
/op/
Date of Payment
Amount: $ ¢
f'R ply,,,
Page 2 of 2 wa/V� se� ver F
72-028 (11/84)
LER6Y C. REID, JR. � L
CE - 2251
lc
unicipalityP.O. BOX 196650
ANCHORAGE, ALASKA 99519-6650
Anchorage ®f `` (907) 264-4111
Archor age TONY KNOWLES,
MAYOR
DEPARTMENT OF HEALTH 8 HUMAN SERVICES
November 7, 1986
Darcy Bevens
Alaska Environmental Control Services
1200 West 33rd Avenue, Suite B
Anchorage, Alaska 99503
Subject: Lot 27 Block 4 Valli Vue
Waiver Request WR86-153
Dear Ms. Bevens:
Your request for a waiver of the 100 foot separation distance
required between the septic tank and a stream to the east has
been granted. The distance between this tank and stream was
measured at 94 feet.
This waiver is valid for the existing three bedroom single
family dwelling only.
Sincerely,
Stephen S. Morris
Civil Engineer
On -Site Services
DEPT. OF ENVIRONMENTAL CONSERVATION
ANCHORAGE/WESTERN DISTRICT OFFICE
437 "E" STREET, SUITE 303
ANCHORAGE, ALASKA 99501
DATE: November 6, 19
PWS I.D.# 210605
To Whom it May Concern:
RILL SHEFFIELD, GOVERNOR
Telephone: !9071
Address:
274-2533
According to records on file in this office the Valli View Subdivision
Water Regulations
Water System is in compliance with the State Drinking
Sincerely,
Michael P. Lewis
Environmental Engineer
ALASKA HUIROWnTAL COnTROL
Engineering & Cnuironmental Studies
Municipality of Anchorage
825 L Street
Anchorage, Alaska 99501
Attn: Steve Morris
Dear Steve,
SCflUICes, Inc.
November 5, 1986
This is in regards to Valli Vue #2, Block 4, Lot 27. On June 6, 1977, a 1000
gallon septic tank and a 36 foot long trench were installed. Recently this
septic system passed an adequacy for a one bedroom house, so a two bedroom
upgrade trench was added, for a total of a three bedroom system.
Now, the new septic system is the proper distance from the stream. But
unfortunately, the exsisting tank and field are 94 feet from the stream. The
slope from the tank to the stream is 7%. The tank has a caulder coupling on
the outlet, and the inlet was sealed with tar. No leaks were observed so it
is apparently water tight. In addition, the soil is a silty sandy gravel
which will no doubt help to filter out any effluent before it reaches the
stream.
We are asking for a waiver of the separation distance between the existing
septic tank and the stream, and the existing 1977 trench and the stream to be
94 feet.
If you have any questions, please feel free to call 561-5040. Thank you.
Sincerely,
Darcy Be, ns
Engineering Geologist
Approved:
40
j >.e•
AP.
* i W�4 e• td 00
eee• eae• eseo so
o °
°e°e ee see en° ae°e0 ee�
IEROY C.
CE 251
-r .. •.....•. t y
1200 West 33rd Auenue, Suite B • Anchorage, Alaska 99503 • (907) 561-5040
60541
ALASKA HUIR0WWAL COnTROL SCRUIRS, InC.
Engineering & Enuironmental Studies
TOM MOCKLER
6257 WEST TREE DRIVE
ANCHORAGE ALASKA
99516
SELLER—TOM MOCKLER
LEGAL:VALLI VUE #2 BLOCK 4 LOT 27
ADEQUACY TEST FOR SEWER SYSTEM
ADEQUACY TEST DATE -10/24/86
10/30/86
TOM MOCKLER
6257 WEST TREE DRIVE
ANCHORAGE ALASKA
99516
THE TYPE OF ABSORPTION SYSTEM IS A TRENCH WITH AN AREA OF 540 SQFT.
THE SYSTEM IS CAPABLE OF ACCEPTING 200 GALLONS OF WATER PER DAY.
THE SURGE CAPACITY OF THE SYSTEM IS 139 GALLONS,
BASED UPON THE TEST DATA THE SYSTEM IS NOT ACCEPTABLE FOR A
HOME OF 3 BEDROOMS.
SEPTIC TANK ADEQUACY
THE EXISTING SEPTIC TANK VOLUME OF 1000 IS ADEQUATE FOR
THIS 3 BEDROOM HOUSE.
THE SEPTIC TANK/PACKAGE PLANT WAS PUMPED ON 10/17/86 .
THIS REPORT DOES NOT VERIFY THE INTEGRITY OF THE PIPING FOR THE WATER
SUPPLY OR WASTEWATER SYSTEM.
be
i0•aue
C. REID,
.2251
'Pr�fe�i'na�
1200 West 33rd Auenue, Suite 6 • Anchoraqe, Alaska 99503. 907) 561-5040
ALASKA ENVIRONMTAL
CONTROL SERVIC. INC.
1200 West 33rd Avenue, Suite B
ANCHORAGE, ALASKA 99503
(907) 561.5040
JOB
SHEET NO. OF
CALCULATED BY DATE
CHECKED BY DATE
MUNICIPALITY OF ANCHORAG-"
DEPARTNi T OF HEALTH AND ENVIRONMEF)L PROTECTION
825 L Street, Anchorage. Alaska 99501
264-4720
#1: Time
Date
3_g-
�L�
—\s
Insp
#2: Time
Date
Insp
Date Received: (,(n_nch a\Ong
#3: Time
Date
Insp
REQUEST FOR APPROVAL OF INDIVIDUAL SEWER AND WATER FACILITIES
1. Lending Institution Request: l rn r5A�i�c
Mailing Address: (�i1 1�i1 n L� P� c� J� Phone:
2. Property Owner: QM n Phone:
Mailing Address: 'mn�\
3. Legal Description: k L7 , �J�%� 994 k 2
4: Single Family Residence: Number of Bedrooms:_
Multiple Family Residence: ( ) Number of Bedrooms: /
5. Well System: Individual Well ( ) Community/Public System (�
Permit # _� Depth of Well �- Well Log on File yY�y
Construction yu e�/ Bacterial/Analysis �1
6. Sewage Disposal System: On-site /System (/� Public Utility ( )
Permit # % 7128/ &
Installed e17 Installer
Septic Tank Size 000 Manufacturer
Absorption Area _Sc( O Soils Rate A K ) Material
7. Distances: Well to Septic Tank �200(�I- to Absorption Area
to Sewer Line /(9O _-/- Nearest Lot line 4- Absorption Area
to Nearest Lot Line /Q
Page Two
Department of Health and Environmental Protection
Request for Approval of Individual Sewer and Water Facilities
Legal Description:
Comments:
Affadavit Attached: ( )
Approved:
Disapproved:
Department Worksheet:
Letter Attached: ( )
Date:
Date:
1.
2.
3
rd
5.
MUNICIPALITY OF ANCHORAGE
epartment of Health and Environmental Protection
825 L Street, Anchorage, Alaska 99501
264-4720
for Approval of Individual Sewer and Water Facilities
Property Owner:
Robert Lutje, dba Timberline Homes
Mailing Address: SRA, Box 31-L Phone: 344-4602
Name of Buyer:
Mailing Address:
Lending Institution:
Mailing Address!
Realtor/Agent:
Thomas $ Sharon Mockler
6257 West Tree DRive Phone: 344-2868
Coast Mortgage
Anch. Business Park phone: 279-0665
Totem Realty, Inc. / Bonnie Mehner
Mailing Address: 724 E. 15th Ave. Phone: 272-0571
Legal Description:
Lot 27, Block 4, Valli Vue Estates
Street Location: 6257 West Tree Drive
6. Single Family Residence: (x) Number of Bedrooms: 3
Multiple Family Residence: ( ) Number of Bedrooms:
7. Water Supply: *Individual Well ( ) Public/Community System (x)
I£ Individual Well, well depth
If Community System, name of system Valli Vue
8. Sewage Disposal System: *'On-site System (x) Public System ( )
If On-site System, date of installation: 1977
*NOTE: A well log is required on ALL wells drilled since 6/75.
**If on-site sewer system is over two(2) years old, an adequacy
test is required by this department.
A fee of $25.00 must accompany each request before processing
can be initiated.
3/77