HomeMy WebLinkAboutVONS LT 2AL)c.*.,(\s 4 <aw ukawo ?; Municipality of Anchorage Community Development Department Page 1 of 3 On-Site Water and Wastewater Program 4700 Elmore St. • P.O. Box 196650 Anchorage, AK 99519-6650 • http://www.muni.org/onsite • (907) 343-7904 ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP151286 PID Number: 015-081-37 ❑ New ❑✓ Upgrade Name: Mark and Deborah Moderow ABSORPTION FIELD ❑ Deep Trench ❑✓ Shallow Trench F] Bed E] Mound Address 7050 E. 99th Avenue Anchorage, AK 99507 ❑ Other Phone Number of Bedrooms Soil Rating Total depth from original grade 250-3856 4 1.2GPD/SF 13.1 Ft. LEGAL DESCRIPTION Depth to pipe invert from original grade 9.1 Ft. Gravel depth beneath pipe 4 OR Subdivision Block Lot Vons 2A Fill added above original grade 1.5-2 Ft. Gravel length 50 Ft. Township Range Section Gravel width 5Ft. Beds: Number of Lines Distance between lines I Ft. SEPARATION DISTANCES To Septic Absorption Holding Sewer Total absorption area Number of trenches Dist. between trenches From Tank Field Lift Station Tank Line 500 Ft' One Ft. Well >100' >100' >100' >75' >25, TANK El Septic ❑ S.T.E.P. ❑ Holding ❑ Other Manufacturer Existing Capacity Gal. Surface Water >100' >100' >100' >100' Material Number of compartments Lot Line >5' >10' N/A N/A NA Foundation >5' >10' N/A N/A LIFT STATION Manufacturer Capacity Curtain Drain None I Noted Gal. Remarks- Existing Septic Tank Verified Suitable for Pump on level at in. Pump off level at i FHglr alarm at in. Continued Use. Absorption Trench and Flow Diverter Valve Placed Under this Permit. Pump make and model Electrical Inspections performed by Installer PIPEMATERIAL Housetotank D3034 Tankto D3034 drainfieltl G&R Excavation Drainfield F810 CO/MT D3034 Inspector MEA BENCHMARK (Assumed elevation) 100.Oft Inspection *' $/20/15 8/21/15 Location and description dates: 2-d 3rd 8/28/15 4'° Bottom of Siding at Barn. COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL En O ay 1 F... C Conditional Approval: Date `P,••' SSR, • 491H 00 ....... .... ...... ... — j............................... 10 MICHAEt E. ANDERSON ♦ '.� CE-4381 Approved _ % Date / 1 ROFESSIO� Inspection Report_1-t-12.doc Municipality of Anchorage Page 2 of 3 DEVEOPMENT SERVICES DEPARTMENT 4700 Bragaw Street Anchorage, AK. 99519-6655 - 343-7904 On -Site Wastewater Disposal System or Well Inspection Report Permit No.: OSP151286 PID No. 015-081-37 o E 99th AVENUE M S 89'56'40"E 330.00' LOT 2A VONS SUBDIVISION a n 99,089 s.f. Z `� / N DRIVEWAY -----�--- ` FDV---Existing Absorption O C r --'-�--- System. m O O m C.-_Tttt®-- O NJ 1,2�SOtic;;allon Sepia �•ank M1 --' C2 M2 Four j Existing Bedroom ® Well Home I I A I B / I Cl 58.2 C2 100.3 / M 1 58.2 38.1 / / M2 100.0 74.3 / / FDV 60.7 16.1 Lot 4 I Well Radius I I `10' T&E EASEMENT ----- N 89'56'40 W 330.00 �4 LOT 1 LOT 1 C LEGEND: .•�•���.qs, OF q��♦♦ 0 � C1 — Cleanout SV — Septic Vent �\ ♦♦•�� ♦ p'`P •" 0 �; _ TH — Test Hole • ��•; �♦♦ M1 — Monitor Tube 49th FCO — Foundation Clean Out ` �/'� ,� i FDV — Flow Diverter Valve ........ .....................`.:-!:`.`.`moi' :.MICHAEL E -4381ANDERSON C �� NO. CE -4381 PLA^ /� 'F T N H BUILT I Lot 1 ♦rfT; •• �ti� I Well Radius ♦♦1hp111111 ESS��P�♦♦ SCALE 1" = 50' Municipality of Anchorage DEVEOPMENT SERVICES DEPARTMENT 4700 South Bragaw Street Anchorage, AK. 99519-6655 - 343-7904 On -Site Wastewater Disposal System or Well Inspection Report Permit Number: OSP151288 104.2 Om PR❑FILE No Scale EXISTING H _ 103.0 Original Ground Geotextile Fabric Drainfield Rock f — 83.0 No Groundwater 8-27-15 50'(Trench Length) AS -BUILT Page 3 of 3 PID No. 015-081-37 04 mU IM 93.9 MUNICIPALITY OF ANCHORAGE DEVELOPMENT SERVICES DEPARTMENT 4700 BRAGAW STREET ANCHORAGE, AK 99519-6650 SOILS LOG - PERCOLATION TEST LEGAL DESCRIPTION: LOT 2A, VONS SUBDIVISION PERFORMED FOR: _MARK MODEROW DATE: 8/14/2015 PROJECT No.: PARCEL ID#: TECHNICIAN: W. ROBERTS DEPTH TEST HOLE 1 (feet) 1 2 3 4 5 6 7 8 9 JO 11 12 13 14 15 I 1 OB/OG WELL GRADED SAND GW BOH @ 20' N 0 �., 49th MICHAEL E. ANDERSON SITE PLAN SEE SITE PLAN 13 WAS GROUND WATER ENCOUNTERED? No IF YES n WHAT DEP'T'H? DEPTH OF WATER AFTER MONITORING: NONE 2% DATE OF MONITORING: 8/21/2015 DATE READING GROSS TIME (MINUTES) NET TIME (MINUTES) DEPTH To WATER (INCHES) NET DROP (INCHES) TEST HOLE PRESOAKED PRIOR TO TESTING: 10/31 1 11:10/11:20 10 .75"/3.25" 2.50" 2 11:21/11:31 10 .63"/3.13" 2.50" 3 11:32/11:42 10 .75"/3.25" 2.50" 4 11:43/11:53 10 .75"/3.25" 2.50" 5 11:54/12:04 10 .63"/3.13" 2.50" 6 12:05/12:15 10 .75"/3.25" 2.50" PERCOLATION RATE: 4.0 (MIN/INCH) PERC. HOLE DIA. 6" (INCHES) TEST RUN BETWEEN: 4.5 FT. and 5.5 FT. COMMENTS: TEST HOLE PRE SOAKED PRIOR TO TEST. TEST PERFORMED BY ANDERSON ENGINEERING. I, MICHAEL E. ANDERSON CERTIFY THAT THIS WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPLE GUIDELINES IN EFFECT ON THIS DATE: 9/23/2015 On -Site Wastewater Disposal System Permit MUNICIPALITY OF ANCHORAGE Development Services Department On -Site Water & Wastewater Program 4700 Elmore Road, PO Box 196650 Anchorage, AK 99519-6650 Telephone: (907) 343-7904 Permit Number: OSP151286 Tax Code Number: 01508137000 Work Type: Septic Upgrade Permit Effective Dates: August 18, 2015 to August 17, 2016 Design Engineer: ANDERSON ENGINEERING Subdivision: VONS Site Legal Address: VONS LT 2A G:2439 OwneNAddress: MODEROW MARK R & DEBORAH C 7050 E 99TH AVE ANCHORAGE AK 995076771 Site Mailing Address: 7050 E 99TH AVE, Anchorage This permit is for the construction of: Y Disposal Field N Septic Tank N Holding Tank N Privy All construction must be in accordance with: Lot Size in Sq Ft: 99089 Total Bedrooms: 4 N Private Well N Water Storage 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80). 3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either: A. Open and Close on the same day. B. Covered, sealed, and heated to prevent freezing. Special Provisions: The Engineer needs to do an additional test hole prior to the construction of the septic field. Construction may proceed at your own risk before the 7 day water monitoring is complete. Please submit stamped and signed results with the As -built Inspection Report. If the results require a design change, construction of the system will stop pending On -Site review and approval. Test hole to be at least 19' deep. Received By: Issued By: MUNICIPALITY OF ANCH Community Development Department Development Services Division On -Site Water & Wastewater Program ON-SITE SEWER/WELL PERMIT APPLK Parcel I.D. 015-081-37 Property owner(s) Mark & Deborah Moderow Mailing address 7050 East 99th Avenue Anchorage, AK 99507 Site address Same Fax: Day phone LS -0 ` 3 B56 Legal description (Sub'd., Block & Lot) Vans, Lot 2A Legal description (Township, Range & Section) Lot Size 99089 Sq. Ft. Number of Bedrooms Four APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING: (® all that apply) Absorption Field 0 Initial El Single Family (SF) Q (w/wo ADU) Septic Tank ❑ Upgrade 0 Duplex (D) ❑ Holding Tank ❑ Renewal ❑ Multiple Dwellings ❑ Privy ❑ (SF and/or D) Private Well ❑ Water Storage ❑ THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR: Distance: I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal Codes. (Signature of property owner or authorized agent) Permit/Rush Fees: 500 i ' lyo ::91C), Waiver Fees: Date of Payment: Ag'115 t,2�2= Date of Payment: Receipt Number: 00,la iii, Receipt Number: Permit No. 05eI5 j'ZM Waiver No. Permit App_9-1 -1 2.doc August 18, 2015 Municipality of Anchorage Development Services Department On -Site Water and Wastewater Program 4700 Elmore Road Anchorage, AK 99519-6650 Subject: Lot 2A, Vons Subdivision Septic System Design and Permit Application Impacts to Adjacent Properties Dear Onsite Services Engineer The absorption system on the subject lot has failed and must be replaced. The system was originally designed and permitted along with the alternate site in 1997. We are proposing to construct the new absorption trench at the previously approved alternate site. The conditions on the lot remain the same as in 1997 and no conflicts exist with neighboring wells or septic systems. We are therefore requesting a permit be issued for the upgrade of the septic system to accommodate the four-bedroom home on the lot. The attached Site Plan and backup documentation identify the location and configuration of the existing and proposed septic systems. The existing absorption system will be connected to the new system with a flow diverter valve for possible future use. Also identified on the plans are the locations of the existing well this lot and adjacent lots. No conflicts exist between the proposed septic system and the wells or water services on this or adjacent lots. Drainage arrows are shown indicating the current drainage patterns. The drainage patterns will be maintained after construction. The test hole placed on the lot at the location of the alternate site indicated poorly graded sand (SP) in the absorption zone of the trench. The percolation rate was determined to be 4 minutes per inch. No groundwater was encountered during the placement of the test hole and none developed during the monitoring period. We have designed the new trench with an application rate of 1.2 gallons per day per square foot. We are proposing to verify the integrity of the existing 1,250 gallon septic tank and construct a 50' long trench by 5' wide with a 4' effective depth. The total depth of the system will be 13' with the distribution line at 9' below the existing surface. The ground surface on the lot in the area of the new trench slopes to the south at an Lot 2A, Vans Subdivision August 18, 2015 Page Two approximate 15% grade. The trench will be placed parallel to the contours of the ground as much as possible and in conformance with design criteria. A minimum of 100' will be maintained between all components of the septic system and the proposed well and from any surface water in the area. If the system is constructed in accordance with our design the following statements apply: 1. The system, if constructed as designed, will have no adverse impact on the wells in the area or those to be constructed in the future. 2. The system, if constructed as designed, will have no adverse impact on existing septic systems in the area or those to be constructed in the future. 3. The system, if constructed as designed, will have no adverse impact on reserve space, either surface or subsurface, on any lots located in the area. 4. The system, if constructed as designed, will have no adverse impact on drainage patterns in the area. The current drainage pattern will be maintained. Sincerely, Michael E. Anderson. P.E. Attachments 49th• ••s MICHAEL E. ANDERSON LOT 2A VONS SUBDIVISION 99.089 s.f. o E 99th AVENUE M S 89'56'40"E 330.00' 4 NOTE: -_ Verify Integrity of ��� �� �• Existing Septic Tank. z - i ti DRIVEWAY �\-----�---- ` FDV Existing Absorption r __ System. rn O p-------- -- P O Existing THDH® Milan MT U o w 1, 0 Co - Se pic �nnk---------- CO N u 50' Long x 5' Wide x Existing Four j 4' Effective Depth Bedroom Absorption Trench. ® Well Home I » I I » 1 ' r r � / No Conflicts with Well or Septic System on Lot 1 \ ' Lot 4 Well Radius L � �— i I 1 — — — — — — — — — — — Ti _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ ---------r -- ,�' 10' T&E EASEMENT ------ N 89'56'40 W 330.00' LOT 1 - LOT 1 4 C LEGEND: , OF 44 ��. - Cleanout 0 ;:0 SV !� SV - Septic Vent ' ' m �P•�j —� TH - Test Hole / MT - Monitor Tube \\ 49th ; FCO - Foundation Clean �...... ..... ... ........ ... . ..�.... Out i \ \ .............� E. ANDERSON SITE PLAN r 00.' 1 � . �:MICHAEL 0 No. CE-4381 0, ♦ I Well Radius �� SCALE 1" = 50' �I,ii;...... '�O VONS SUBDIVISION, LOT 2A DESIGN FACTORS: SYSTEM REQUIREMENTS: Four Bedroom Home 5' Wide Trench System Perc. Rate: 1-5 Min./Inch 1,250 Gallon Septic Tank Application Rate: 1.2 GPD/SF 4' Drainfield Rock 4 Bedrooms * 150 GPD/Bedroom = 600 SF Absorption Area 600 SF/1.2 GPD/SF/5 SF (Width) *.5 (Red. Factor)= 50 LF Trench Length THEREFORE: Construct a 50' Long x 5' Wide x 4' Effective Depth Absorption Trench. Flow Line Elevation in Trench to be 9' Below Original Ground Surface. Total Depth to be 13' Below Existing Ground. Verify the Integrity of the Existing Septic Tank. I 5' A TYPICAL 5' WIDE TRENCH SECTION (NO SCALE) 4 NOTE: Grade Area Over Trench to Drain Away. ie Minimum 6' Separation From Bedrock. i....! Minimum 4' Separation From Groundwater. i yl Minimum 100' Separation From Private Wells in the Area. Minimum 100' Separation From Surface Water or Streams. 49th MICHAEL E. ANDERSON NO. CE -0381 0 W.O. 97313.000 Municipality of Anchorage Page 1 of 7 DEPARTMENT OF HEALTH AND HUMAN SERVICES ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 • Anchorage, Alaska 99519-6650 • Telephone: 343-4744 On -Site Wastewater Disposal System and/or Well Inspection Report Permit Number: SW9701 23 PID Number: Lv{- -�D & P, A Name: Wastewater System: ® New ❑ Upgrade NCP Construction Ltd. Address:ABSORPTION FIELD 1118 E. Intl. Air otrt Rd. 99518 Phone: (907) 562-2283 No. of Bedrooms: 4 E) Deep Trench ❑Shallow Trench El Bed 0 Mound 6dOther LEGAL DESCRIPTION Soil Baling: Total Depth from original grade: . 1 . 2 GPD/Sq. Ft. 9' -9" Lot: Block: Subdivision'. Depth to pipe bottom tram original grade: depth beneath pipe 2A -- Vons 9 r -2" Ft. O. 58 Ft. Township: Bangs: Section: Fill added above original grade: length: 1 ' +/-ft. 4 0 Ft. WELL: ® New ❑ Upgrade width: 3 Number (lines: 3 Distance between lines: 1 0 Ft. Ft. Classification (Private. A,B,C): Total Depth: Cased To: Total absorption area: Pipe material: Private 203 Ft. 203 Ft. Trench/166 SO.F1.1 PVC 0304 Driller: Dale Drilled: Sialic Water Level: Installer: Dale installed: Hefty 6/25/97 101Ft. G.S. Express 1 8 4/97 Yield: Pump Set at: Casing Fleight Above Ground TANK 1 0 GPM 1 9 3 FI. 3 FI. SEPARATION DISTANCES Mseptic El Holding ❑s.T.E.P. To Semlc Absorption Lift Holding Public/Prlvein Manufacturer: Capacity in gallons: From Tank Field Sidon Tank Sewer Linos Anchorage Tan k 1 1 250 Material: Number of Compartments: Well 1 01 ' 1 46' -- -- -- Sreel 2 Surface >100' >100' -- -- -- LIFT STATION Water Lot140 ' 145 ' Size in gallons: Manufacturer: Line —— -- — Foundation31 ' 60' -- -- -- 'Pump oft' level al: "P ell" level at: High water alarm at: CurtainN/A N/A -- __ —_ Pump Make el I Electrical inspections performed by: Drain Remarks: Indrain system is being testeic BENCH MARK Location and Description: to operate on one trench. Finish floor Qf house *There is a total of 3 each 40'X3' Elevation = 100.0 Assumed Elevation: trenches constructed. I 100.0 Ft ENGINEER'S SEAL ®Yo ��✓d acy``4 ����'A rya ,;:d f�E��l v o i. Inspections performed by: Joe Demattia Dates: 1st 8/24/97 o�-.• �0 re d y" 2nd 8/27/97- �.eeve aeocvo donor oe�-,. Department of Healt and Hu an rvices approval DEF i1:G M1°. CE 5 07 Reviewed by: Date: I=/- and approved 72.01. (11nv 9/91) MOA 25 11 141 SEPTIC SOLUTIONS, INC. 8604 Blackberry Anchorage, Alaska 99502 Phone: (907) 243-6199 Fax: (907) 243-0653 November 24, 1997 W.O.: 97313.000 Mr. Jim Cross Department of Health and Human Services P.O. Box 196650 Anchorage, AK 99519-6650 RECEIVED NOV 2 5 1997 Municipality of Anchorage Dept. Health & I-luman Services RE: Lot 2A, Vons Subdivision / On -Site Septic System ( Permit # SW970123) Dear Mr. Cross, The septic system for the above referenced property has been installed. As you may recall, this is the property in which we were installing the Indrain System proposed by Septic Solutions, Inc.. We will be monitoring the center trench during the next twelve months. We will begin taking test samples after the system has been in use for sixty days. In the meantime, please accept the enclosed Record Drawings for your files. Please give me a call if you have any questions. ly yours, Solutions, Dee High, P. Enclosure(s) cc: Joe DeMattia 313dj24n.1tr Permit No SW970123 Municipality of Anchorage Department of Health and Human Services ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 • Anchorage, AK 99519-6650 ° Tel: 343-4744 Well & On—Site Wastewater Disposal System Legal Description: VONS SUBDIVISION—LOT 2A SYSTEM DESIGN CALCULATIONS DESIGN PARAMETERS: 1 4 BEDROOM HOUSE OF 600 GAL./DAY 2� PERCOLATION RATE= 4MIN./INCH. 3)APPLICATION RATE (DEEP TRENCH)= 1.2 GPD/SF A) STANDARD TRENCH REQUIREMENTS. AREA = # OF BEDROOMS X 150 GAL./BR. / ABSORPTION RATE AREA = 4 BR. X 150 6PD/BR = 500 SF. 1.2 B) INDRAIN REQUIREMENTS: STANDARD INDRAIN 7"H X 3'-0"W X 4'-0"L TREATMENT CAPACITY= 1.0 GPD./SF. FABRIC # OF MODULES REQUIRED FOR TREATMENT= 7 MODULES C) M.O.A. SURFACE AREA COMPARISON: 313MW Page 2 of 7 W.O. 97313.000 Date 11/24/97 REVISED PID No. 01508134 SURFACE AREA REQUIRED (INDRAIN) = 140.0 SF. SURFACE AREA REQUIRED (DEEP TRENCH) = 500 SF. NO. OF MODULES REQUIRED FOR DEEP TRENCH = STANDARD TRENCH AREA SURFACE AREA PER MODULE = 375 SF./16.6 SF./MODULE= 30.0 MODULES USE= 3 TRENCHES WITH 10 MODULES EACH, FOR A TOTAL OF 30 MODULES 24 > 22.6 THEREFORE OK NOTE: SYSTEM IS DESIGNED & IS BEING TESTED USING ONE 40' X 3' TRENCH, 2 ADDITIONAL WERE TRENCHES INSTALLED TO COMPLY W/ M.O.A. REGULATIONS. IF TESTING CONFIRMS OUR DESIGN— SYSTEM WILL BE APPROVED FOR ONE TRENCH (3' X 40') & APPROVED BY DHHS. RE�'JRD DR` WINIG Permit No SW970123 Municipality of Anchorage Department of Health and Human Services ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 • Anchorage, AK 99519-6650 • Tel: 343-4744 Well & On—Site Wastewater Disposal System Page 3 of 7 W.O. 97313.000 Date 11/17/97 Legal Description: VONS SUBDIVISION—LOT 2A PID No. 01508134 NOTES: 1 ALL CONSIRUCTION WAS IN ACCORDANCE WITH CHAPTER 15.65. WASTEWATER DISPOSAL REGULATIONS OF THE MUNICIPAL CODE AS CURRENTLY AMENDED. 2 INSTALLED NEW 1250 GAL. SEPTIC TANK. TANK MANUFACTURED BY ANCHORAGE TANK. 3 ALI. PIPE CONFORMS TO ASTM D3034. 4 LEACH FIELD CONSISTS OF 3 EA. 40' X 3' INDRAIN TRENCHES. ONE TRENCH IS BEING TESTED TO VERIFY DESIGN PARAMETERS. RECORD DRAWING 313CSDSD Permit No SW970123 Municipality of Anchorage Department of Health and Human Services ENVIRONMENTAL SERVICES DIVISION Page 4 of 7 Date 11/18/97 P.O. Box 196650 • Anchorage, AK 99519-6650 • Tel: 343-4744 On—Site Wastewater Disposal System/Well Inspection Report t• LOT 2A VONS SUBDIVISION Legal Descrlp on: I NOTE: LOCATION OF SEPTIC SYSTEM & SWING TIES TAKEN FROM AS -BUILT DRAWING PREPARED BY KENNETH LANG DATED 11/3/97. N89'56'40"W 330.00' 6 79.8 63.0 VALVE & C.O. 7 111.0 90.5 M.T. 8 119.5 99.0 C.O. 9 75.0 63.0 3 WAY DISTRIBUTION BOX 10 99.0 83.0 M.T. 11 104.0 87.5 3 SAMPLING WELL 12 119.0 101.5 C.O. 13 80.0 71.0 VALVE & C.O. 14 104.5 92.0 M.T. 15 120.0 106.0 M.T. & C.O. 16 79.6 66.6 VALVE & C.O. .••"tea OF Ak �-'O*X nTu RECORD DRAWING /♦ �DENNIS EE • ai 4; S•••• CE 580 •fc� A eye •••••••M \�1 '11 \r\�••�SAO •do �t'%�1 DATE W.9. 97 13.000 TSCALE. 1"=50' C. FILE 313CSD7D Permit No. SW970123 Page 5 of 7 W.O. 97313.000 Municipality of Anchorage Date 11/17/97 Department of Health and Human Services ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 ° Anchorage, AK 99519-6650 ° Tel: 343-4744 Well & On—Site Wastewater Disposal System Legal Description: VONS SUBDIVISION—LOT 2A PID No. 01508134 (2) 4" SHUT 40' M.T. TYP. OFF VALVES ® ®M.T. C 0 n r EIC.O. �� —4" PERF. PVC PIPE 3 WAY DISTRIBUTION BOX -SAMPLING WELLS M.T. (3 EA.) ® C O. 0C.0. 4" SHUT OFF VALVES INSTALL 1250 GAL. (8) 3' X 4' 2 -COMPARTMENT MODULES TYP. STEEL TANK C•0• DC.O._ _ (DM O .T. INSTALL 2- A O OPPOSING C.O.'S g �O LEACH FIELD DETAIL �o C.O. = CLEANOUT M.T. S.W. = MONITORING TUBE = SAMPLING WELL RECORD DRAWIN6 _ . ,, TH :•.• • ...•'•. 0 0♦ *.DENNIS DE GF{�• / CE 5 SCALE: 1"= 10'IIII �: pCi ���ere°°•••••••°°°\�� \�: ofess-��o�Yb DATE FRON Panasonic FAX SYSTEM M4 lisp Wafer - h -f 13570 IUSU A lllVp 'ANC OttiGt:, ALASKA 99 ! �'ermit Number S J tb t i .PlRte Of Issue_ tialastaried , Block a : ,+ ata; r To NO. : 5638366 Nov. 24 1997 01: 'TEt 19071 19 Wall log Prop erty 0 Iif3 ��1 1`06t -n" brandy fax transminal memmo�7671 x of pages I To GO Co. dept. Phone " 3 138 �°•° d Caeing LInOt T Casing IYn 0- lclfcl 17_ Z Static Wier Fat"P.Inj Le L� 'fid Hecow Mottiocf C fit of C t�I 1 0 Ito Well Irtia CI. Scree C t ; i Perfop, vor aroutTy bepur tr}Sm ' ^ 4� Pump intp(oe Puttgj S' welt pie 7 Method iii fob t da me : �i Woo Drill r Ni �17)CompanY� Mailing2AI dra, �U u C7 CNy 71f i Ar vvide a weii <db to the grobem 11-25-1997 12:01AM 5638366 al sppro ed petmk I Namo Ad reps: Ppb ekA- xn4�Ft A� nk t h, nwnur whnln nn .ra„ W ..e r r } �" F D NOV 25 119P P.01 MuniC;pahly QI A(wri Drage Uept. Health & Human Services Sn� PAGE 1 OF 1 MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH AND HUMAN SERVICES P.O. BOX 196650, 825 "L" STREET, ROOM 502 ANCHORAGE, ALASKA 99519-6650 ON-SITE WELL AND WASTEWATER DISPOSAL SYSTEM PERMIT PERMIT NUMBER:SW970123 DATE ISSUED: 6/05/97 DESIGN ENGINEER:DHI ENGINEERING�Jlc.�C(t-�1 EXPIRATION DATE: 6/05/98 OWNER NAME. ^L1 (v\f_,A2 ,(y�vbLVCD a OWNER ADDRESS:118 E. INTERNATIONAL AIRPORT ROAD ANCHORAGE, ALASKA 99518 p PARCEL ID: 01508134 �Q t, > iA o 1 � -- o ( � - ?-)­� �U "� L'f o 0,1 LEGAL DESCRIPTION: VONS LT 2 LOT SIZE: 99089 (SQ. FT.) NUMBER OF BEDROOMS: THIS PERMIT: ,3 / o U;. THIS PERMIT IS FOR THE CONSTRUCTION OF: DISPOSAL FIELD /SEPTIC TANK / WELL SYSTEM ALL CONSTRUCTION MUST BE IN ACCORDANCE WITH: 1. THE ATTACHED APPROVED DESIGN. 2. ALL REQUIREMENTS SPECIFIED IN ANCHORAGE MUNICIPAL CODE CHAPTERS 15.55 AND 15.65 AND THE STATE OF ALASKA WASTEWATER DISPOSAL REGULATIONS (18AAC72) AND DRINKING WATER REGULATIONS (18AAC80). 3. THE ENGINEER MUST NOTIFY DHHS AT LEAST 2 HOURS PRIOR TO EACH INSPECTION. PROVIDE NOTIFICATION BY CALLING 343-4744 ( 24 HOURS ) . (NOT REQUIRED FOR WELL ONLY PERMIT) 4. FROM OCTOBER 15 TO APRIL 15 A SUBSURFACE SOIL ABSORPTION SYSTEM UNDER CONSTRUCTION DURING FREEZING WEATHER MUST BE EITHER: A. OPENED AND CLOSED ON THE SAME DAY B. COVERED, SEALED AND HEATED TO PREVENT FREEZING 5. THE FOLLOWING SPECIAL PROVISIONS. SPECIAL PROVISIONS: A THREE WAY DIVERTER VALVE SHALLBE USED IN PLACE OF THE PROPOSED DISTRIBUTION BOX. l_;__)_� ..i RECEIVED ISSUED BY DATE: ( 7 DATE: 0`_5-J7 7-9—lir SF(E F,vC'J 19rrlycNPrp 4AfmPLvO PlFS/GN A47EP 7_0_ q7 �9Tr/9t�r�0, SEPTIC SOLUTIONS, INC 8604 Blackberry Anchorage, Alaska 99502 Phone: (907) 243-6199 Fax: (907) 243-0653 July 8, 1997 W.O.: 97313 Mr. Dan Roth Department of Health and Human Services P.O. Box 196650 Anchorage, AK 99510 RE: Lot 2A, Vons Subdivision/ Revised Septic Design Dear Mr. Roth, The owner has change the home to a 4 bedroom, added a basement and move the location of the dog kennel. The end result is that we had to redesign the system which included digging another test hole. We have stayed with the same design concept using the Indrain module as you previously approved. Let me I(now if you need anything else. truly yours, s Solutions Dee High, P1. Principal sa/dh cc: Gail High, DHI 313dr08y.ltr JOB /Ve N SHEET NO.-� / /JOF / CALCULATED BY / Awl E///1177/A' DATE 20 ` a 7 CHECKED BY DATE I ,ll 4,-) ,fc-oot .M„bz,o°ooN \N \ M � C H l � �n N z Its � IU Z 'A �w Q N 4 � 0 V a b D � cq � � F __ - _ it�cw� r"'lly�l0000N IAWWIIW-IISWY&ttp1105 U>tlNlanea" 61m" um 01111 mMEUMMl( tIn111 W215 Permit No. Page 5 of 7 Municipality of Anchorage W.O. 97313 Date 5-17-97 Department of Health and Human Services ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 • Anchorage, AK 99519-6650• Tel: 343-4744 Well & On—Site Wastewater Disposal System Legal Description: VONS SUBDIVISION PID No (2) C SHUT OFF VALVES - 3 WAY DISTRIBUTION BOX C.0 C `INSTALL 2 - OPPOSING C.O.'S INSTALL 1000 GAL. 2 -COMPARTMENT LC STEEL TANK C.O. = CLEANOUT M.T. = MONITORING TUBE S.W. = SAMPLING WELL 32' 4" PERF. PVC PIPE (8) 3' X 4' MODULES TYP. SHUT OFF VALVES LEACH FIELD DETAIL SCALE: 1"= 10' D �a T .T. Permit No. ? Page 6 of 7 W.O. 97313 Municipality of Anchorage Date 5_17-97 Department of Health and Human Services ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 • Anchorage, AK 99519-6650• Tel: 343-4744 Well & On—Site Wastewater Disposal System Legal Description: vnNQ STiRDiViSION PID No. 4" PVC MONITORING TUBE. LOWER 7" TO BE PERFORATED - ORGANICS SM -ORGANIC SILTY SAND ML/SM SILT W/ SILTY SAND LENSES THROUGHOUT LAY MODULE ON FLAT NON COMPACTED BOTTOM OF TRENCH - 4" CLEAN OUT AS SHOWN ON PLAN & PROFILE SLOPE FINISH GRADE TO PREVENT PONDING OVER TRENCH ,-ORIGINAL GROUND NON COMPACTED BACKFILL PERF. PVC STANDARD IN -DRAIN MODULE. `I LAY END TO END IN 3'-0" TRENCH (4' X 3' X 7") "- 4' PER. PVC. SAMPLING WELL. PLACE I ER . ON TOP.WRAP IN GEO-FABRIC-\ SP -FINE BLACK- - - - - - -- -; SAND W/ TRACE f,RAVFI TYPI('AI_ TPFNr H CFC'TInN:� SCALE: NTS rn NON WOVEN GEOTEXTIL.E FABRIC 4 UNDISTURBED TRENCH WALLS z Permit No Municipality of Anchorage Department of Health and Human Services ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 • Anchorage, AK 99519-6650 • Tel: 343-4744 Well & On—Site Wastewater Disposal System Page 7 of 7 W.O. 97313 Date 5-17-97 Legal Description: VONS SUBDIVISION PID No. ? D FROM HOUSE— W NEW 4" PVC *ALL ELEVATIONS ARE TO INVERT OF PIPE UNLESS OTHERWISE NOTED ooncii c 'S 57.01 C. 0. d' PERF. PVC M.T. CLEAN OUT END OF TRENCH — DIST. BOX - SCALE: HORZ.: I"= 20' VERT.: 1`'= 10' 1U'_ n' b' S 1't HOUSE F.F.=66.0 IT 2' — �0. RAIN NEW 4" PVC *ALL ELEVATIONS ARE TO INVERT OF PIPE UNLESS OTHERWISE NOTED ooncii c 'S 57.01 C. 0. d' PERF. PVC M.T. CLEAN OUT END OF TRENCH — DIST. BOX - SCALE: HORZ.: I"= 20' VERT.: 1`'= 10' -19RR 81 '97 15158 GCI , ,„ , rrrClr � NOIN((R'(S6AL „ 1. • (�"•" MuAICIPallly of Anchorage 06PARTMLNT OF HEAL�� H & IlUMAN 9ERVICf!0 526 "L" 8Ir061, AnchbraDo, Alackn 09602-0650 SOILS LOQ — PEACOLATION TUST 44- PECRORI4CD F A I S � /q p � L r oR _ OATF P6gp OfiMGO;. �e'y LOCAL (-0-1-2, 1 2• "� yrf,�i4 C. 4 s . C 7 B 9 111 I 11 , w • s� f 2 •-ws. 13 18QO�L4 PCIP 1401-15= ,s 17 le 19 20 OOMIM6NTA WA6 OROUNO WAT.. FN00VNT¢11lo1 - 0 s� a IF Y69, AT WHAT L OYPTH} I O O,FR 10 wr4r AWr McMU4142 ����� pl0i .yam q�101ep Dn. TMto 7{n n Du�l NK 86011DA: PCACOLATIONNATE1mNCN PMO HOLE i eeE DIAAACTPA .A_ TOY RUN 0rftlp" ^ IT AND Q PT PERFORL1i00Yi - r,'js f ACCORDANCE WITH ALL MT ,� 1 .. WATNN THAT Yitla TUT W ATOANP MUNICIPAL"'OCLW(SINUI-COTONTHISOATL pATC A .A:rJ /bA/ PWCNWS 794=794= (A", 4M) IN Municipality of Anchorage t DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG — PERCOLATION TEST PERFORMED FOR: )a F-. CELLn-T r DATE PE LEGAL DESCRIPTION:/ �T uQA IC � Township, Range, Section: 1111 1D H SLOPE SITE PLAN EEG -TI (�(ZfsRrulG,j � 2 • : SM - ORCFNtC sl�7y. &l*O, E11110111111�1 4 5 6 7 8 9 ; 10 11 t4��4 12 �4 13 "C" 14 15 16 17 18- 19- 20 8 19 20 COMMENTS SIt,T w� StI.-Ey SRr+D I.�NSat T{Vnuu4Hout NECOMMOREN Gross Time Net Time Depth to Water Net Drop °I (6 S HENEWHORNE S. I) AA 11■■N■■■I.■ HINNI OMMINNON :Iv ■ illommEN10001 115MENNI�IN■ 9IMONNU®■INEMM. Aviveo- ■INNEEKINEEN •, 2 IWINNINNEINNEE 6% ( 011MME■INCEM 0110"0011000 ■M■NN■M©M■ S? - NINE &t1Uc N9 WAS GROUND ER ENCOUNTERED7 l� IF YES, AT WHAT L _ O DEPTH? P E Depth to Water After ))R / p /11 96 Monitoring? - gale: 'Sxm-1 Reading Date Gross Time Net Time Depth to Water Net Drop °I (6 S t' S. I) AA :Iv Aviveo- •, 2 •. 6% ( - 1 „ PERCOLATION RATE Q(minutes/inch) PERG HOLE DIAMETER u TEST RUN BETWEEN qq �[[r - FT AND «' 3 FT eo 1.H. S 8' S E.' INEERING PERFORMED BY:verloop Road No. I CERTIFY THAT THIS T ST WAS PERFORMED IN C,, ���� .• :-2d�1 ACCORDANCE WI9#$ LPPr'kTFt'k.Atfkp199Ib7?AL GUIDELINES IN EFFECT ON THIS DATE. DATE: —Lz) r Z qS- 72-008 (Rev. 72-008(Rev. 4185) ,I dJ PERFORMED LEGAL DESCRIPTI Tkt �z 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 COMM Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG — PERCOLATION TEST S DATE PER Township, Range, Section: ROBERT C. COWAN CE -8801 S & S ENGINEERING PERFORMED BY: pa 9. CERTIFY THAT T IS TE WAS PERFORMED IN ACCORDANCE WI*Pdq 8iM AWk(UVfi AL GUIDELINES IN EFFECT ON THIS DATE. DATE: 1,71 / y 72-008 (Rev. 4/85) roe✓ Permit No.— Municipality of Anchorage Department of Health and Human Services ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 • Anchorage, AK 99519-6650• Tel: 343-4744 Well & On—Site Wastewater Disposal System Legal Description: VONS SUBDIVISION—LOT 2A SYSTEM DESIGN CALCULATIONS DESIGN PARAMETERS: 1 4 BEDROOM HOUSE OF 600 GAL./DAY 2 PERCOLATION RATE= 4MIN./INCH. 2)3) APPLICATION RATE (DEEP TRENCH)= 1.2 GPD/SF A) STANDARD TRENCH REQUIREMENTS. AREA = # OF BEDROOMS X 150 GAL./BR. / ABSORPTION RATE AREA = 4 BR. X 150 6PD/BR = 500 SF. 1.2 B) INDRAIN REQUIREMENTS: STANDARD INDRAIN 7"H X 3'-0"W X 4'-0"L TREATMENT CAPACITY= 1.0 GPD./SF. FABRIC # OF MODULES REQUIRED FOR TREATMENT= 7 C) M.O.A. SURFACE AREA COMPARISON: Page 1 of 7 W.O. 97313 Date 7-7-97 KLVIStU PID No. ? SURFACE AREA REQUIRED (INDRAIN) = 140.0 SF. SURFACE AREA REQUIRED (DEEP TRENCH) = 500 SF. NO. OF MODULES REQUIRED FOR DEEP TRENCH = STANDARD TRENCH AREA SURFACE AREA PER MODULE = 375 SF./16.6 SF./MODULE= 30.0 MODULES USE= 3 TRENCHES WITH 10 MODULES EACH, FOR A TOTAL OF 30 MODULES 24 > 22.6 THEREFORE OK v Permit No. Municipality of Anchorage Department of Health and Human Services ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 • Anchorage, AK 99519-6650 • Tel: 343-4744 Page 2 of 7 W.O. 97313 Date 7-7-97 Well & On—Site Wastewater Disposal System Legal Description: VONS SUBDIVISION—LOT 2A PID No NOTES: REVISED 1 ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH CHAPTER 15.65. WASTEWATER DISPOSAL REGULATIONS OF THE MUNICIPAL CODE AS CURRENTLY AMENDED, 2 NOT USED 3 INSTALL NEW SEPTIC TANK AS SHOWN ON THE DRAWINGS. SET TANK LEVEL & RECORD INLET AND OUTLET ELEVATIONS OF THE TANK. TANK SHALL BE PLACED ON UNDISTURBED NATIVE SOIL. PLACE OUTSIDE PROTECTIVE WELL RADIUS. 4 SITE TOPOGRAPHIC SURVEY PROVIDED BY OWNER. EXISTING STRUCTURES, WELLS, SEPTIC SYSTEMS OBSERVED WITHIN 200 FT. OF PROPOSED SYSTEM SITE ARE SHOWN ON DESIGN DRAWINGS. 5 ANY DEVIATION FROM THE DESIGN MUST BE AUTHORIZED BY THE ENGINEER PRIOR TO ITS INCORPORATION INTO THE SYSTEM. 6 CONTRACTOR TO LOCATE ALL UNDERGROUND UTILITIES, PROPERTY LINES, EXISTING WELLS, WATER WAYS, SURFACE AND SUBSURFACE DRAINAGE FACILITIES, LAKES, PONDS, AND OTHER FACILITIES REQUIRING SEPARATION DISTANCES FROM THE PROPOSED SEPTIC SYSTEM. CONTRACTOR TO STAKE PROPOSED SYSTEM PRIOR TO CONSTRUCTION. NOTIFY THE ENGINEER OF ANY OBSERVED CONFLICTS PRIOR TO CONSTRUCTION. 7 NOTIFY THE ENGINEER AND DHHS 24 HOURS PRIOR TO COMMENCING WITH CONSIRUC110N. A MINIMUM OF THREE INSPECTIONS ARE REQUIRED. THE FIRST INSPECTION SHALL BE OF THE SUBGRADE, PRIOR TO PLACING SAND FILLER. THE SECOND INSPECTION SHALL BE AFTER THE PLACEMENT OF GRAVEL, DISTRIBUTION PIPING, STANDPIPES, TANK, AND OTHER COMPONENTS AS SPECIFIED. THE THIRD INSPECTION SHALL BE AFTER THE WORK IS COMPLETED. B CONTRACTOR SHALL DELIVER TO THE ENGINEER A SET OF RED—LINED, AS—BUILT DRAWINGS SHOWING ALL DATA AS SPECIFIED IN SEC. 15.65.F.2, 3, 4, 5, 6 OF MUNICIPAL WASTEWATER DISPOSAL CODE WITHIN FIVE DAYS OF THE FINAL INSPECTION. INVERTS AND SWING TIE LOCATES SHALL BE TO THE NEAREST TENTH OF A FOOT. THESE AS—BUILTS SHALL BE USED BY THE ENGINEER TO PREPARE AND SUBMIT RECORD DRAWING TO DHHS. g STAKE ALIGNMENT OF SYSTEM WITH MARKERS SHOWING THE PROTECTIVE DISTANCES FROM WELLS AND OTHER BODIES OF WATER PRIOR TO BEGINNING INSTALLATION. 10 ALL EXCAVATION DEPTHS ARE ADVISORY. THEY ARE TO BE VERIFIED AND MAY BE MODIFIED BY THE ENGINEER IF ACTUAL FIELD CONDITIONS VARY FROM THOSE USED TO PREPARE THE DESIGN. 313CSD5D .,„,,,,Y„c.... v Permit No. Municipality of Anchorage Department of Health and Human Services ENVIRONMENTAL SERVICES DIVISION Page 3 of 7 yW,O, 97313 Date 7-7-97 P.O. Box 196650 • Anchorage, AK 99519-6650 • Tel: 343-4744 Well & On—Site Wastewater Disposal System Legal Description: VONS SUBDIVISION—LOT 2A PID No NOTES: REVISED 11 EXCAVATE THE ABSORPTION FIELD. BOTTOM OF EXCAVATION SHALL BE LEVEL AND SCARIFIED. RECORD ELEVATIONS AT BEGINNING, MIDDLE, AND END OF TRENCH BOTTOM. CONSTRUCTION EQUIPMENT SHALL NOT OPERATE ON THE FLOOR OF THE EXCAVATION. ANY MATERIAL COMPACTED BY THE OPERATION OF THE CONSTRUCTION EQUIPMENT SHALL BE RFMOVFD AND REPLACED WITH UNCOMPACTFD MATERIAL. 12 PLACE THE SEWER ROCK TO THE SPECIFIED DEPTHS. DO NOT CONTAMINATE SEWER ROCK WITH NATIVE MATERIAL OR SPOILS FROM EXCAVATION. LEVEL ROCK SURFACE TO IF 1" PRIOR TO INSTALLING THE PERFORATED PIPE. 13 ALL PIPE SHALL BE PVC CONFORMING TO ASPM D3D34 OR ENGINEER -APPROVED EQUAL. MIN SOIL COVER SHALL BE 4 FT (OR 2' SOIL AND 2" INSULATION BOARD - SEE NOTE 14) 14 ALL INSULATION BOARD SHALL BE 2" THICK DOW HI -35 INSULBOARD OR ENGINEER -APPROVED EQUAL. CENTER INSULBOARO WIDTH OVFR PIPES, FIELD, AND SEPTIC TANK. 15 GEOTEXHLE SHALL BE MIRAFI 140S OR ENGINEER -APPROVED EQUAL. LAP ALL JOINTS 2' MIN. 16 COVER THE DISTRIBUTION PIPE WITH MIN 2" SEWER ROCK, AND COVER WITH GEOTEXTILE BEFORE PLACING INSULATION AND BACKFILLING. 17 MATERIAL USED AS FILL SHALL BE CLEAN AND FREE OF ORGANICS, TRASH AND CONSTRUCTION DEBRIS. 18 SLOPE ALL FILL MATERIAL TO DRAIN AT 2% MIN. SLOPE, AND 3:1 MAX SLOPE, AND IN SUCH A MANNER THAT PONDING AT OR NEAR THE DRAIN FIELD DOES NOT OCCUR. THE FILL SHALL BE LEFT AT 6" HIGHER THAN SHOWN TO ALLOW FOR SETTLEMENT. SEED SURFACE AFTER COMPLETING INSTALLATION AS PER MUNICIPAL SPECS. 19 RECORD THE FINISH GROUND ELEVATION OVER TOP OF BED. 313DSD6D Permit No Page 5 of 7 Municipality of Anchorage W.O. 97313 Department of Health and Human Services Date 7-7-97 ENVIRONMENTAL SERVICES DIVISION REVISED P.O. Box 196650 • Anchorage, AK 99519-6650 • Tel: 343-4744 Well & On—Site Wastewater Disposal System Legal Description: VONS SUBDIVISION—LOT 2A PID No 40' TYP. C.O.'l OC.O. rnl� (2) 4" SHUTS W ®M.T. OFF VALVES --4" PERF. PVC PIPE 3 WAY DISTRIBUTION BOX (8) 3' X 4' MODULES TYP. C.O. 0C.O. ®M.T. S.W. d' SHUT OFF VALVES o > F INSTALL 1250 GAL. 2 -COMPARTMENT STEEL TANK C.O. 11 pC.O. ®M.T. O S.W. INSTALL 2- A O OPPOSING C.O.'S g �O �a LEACH FIELD DETAIL C.O. = CLEANOUT M.T. S.W. = MONITORING TUBE = SAMPLING WELL ma;� OF �iln 00 0o 0 000 00 0 0 �-.0 Ooo DE HIG CE -5s SCALE: 1"= 10' ��D ` ....... tom DATE aiarsn�n Permit No. Page 6 of 7 W.O. 97313 Municipality of Anchorage Date 7-7-97 Department of Health and Human Services ENVIRONMENTAL SERVICES DIVISION REVISED P.O. Box 196650 • Anchorage, AK 99519-6650 • Tel: 343-4744 Well & On—Site Wastewater Disposal System Legal Description: VONS SUBDIVISION—LOT 2A PID No. ? TH#1 4"' PVC MONITORING TUBE LOWER 7' TO BE PERFORATED — ORGANICS a SANDY SILTY GRAVEL ROCKS TO 5" '-- OCCASIONAL BOULDER 6 TO 24" a LAY MODULE ON FLAT 9 NON COMPACTED BOTTO OF TRENCH 4"' CLEAN OUT AS SHOWN ON PLAN & PROFILE SLOPE FINISH GRADE TO PREVENT PONDING OVER TRENCH ORIGINAL GROUND NON COMPACTED BACKFILL PERF. PVC STANDARD IN–DRAIN MODULE. LAY END TO END IN 3_O" TRENCH (4' X 3' X 7") _ 4" PER. PVC. SAMPLING WELL. PLACE PERF. ON SAND W/ TRACE TOP. WRAP IN GEO–FABRIC�� OF GRAVEL & SILT F___ — — — — -- TYPICAL TRENCH SECTIONA� SCALE: NTS 1�7J NON WOVEN GEOTEXTILE FABRIC I— ;1 UNDISTURBED TRENCH WALLS v Permit No Municipality of Anchorage Department of Health and Human Services ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 • Anchorage, AK 99519-6650 ° Tel: 343-4744 Well & On—Site Wastewater Disposal System Page 7 of 7 W.O. 97313 Date 7-7-97 KLVIJLU Legal Description: VONS SUBDIVISION—LOT 2A PID No. ? D FROM HOUSE .N NEW 4 PVC "ALL ELEVATIONS ARE TO INVERT OF PIPE UNLESS OTHERWISE NOTED PROFILE C.O.'S 61.5 - C. 0. 4' PERF. PVC M.T. 56.4 SENKPTIC D OF TRENCH TA SCALE: NTS DIST. oD'2 1Z' 18' 40' HOUSE F.F.=62.0 C. 0. Tr 2' 58.OR RAIN NEW 4 PVC "ALL ELEVATIONS ARE TO INVERT OF PIPE UNLESS OTHERWISE NOTED PROFILE C.O.'S 61.5 - C. 0. 4' PERF. PVC M.T. 56.4 SENKPTIC D OF TRENCH TA SCALE: NTS DIST. PERFORMEO LEGAL DESCRIPTION: tft I DEPTH 4�' 9 10 11 12 13 14 15 16 17 18 19 Municipality of Anchorage DEPARTMENT OF HEALTI4 & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG — PERCOLATION TEST 3' organic silts with roots to 2 feet. Sandy silty gravel slightly moist. Rock to 5" occasional boulder to 24" (angular) medium density. DATE PE a, Range, Section: SLOPE Sandy with some '- WAS GROUND WATER gravel. (2") .!lone none with trace of silt S IF YES, AT WHAT L DEPTH7 0 P Bottom 1' probed with teeth of back� hoe. 20 -� I [�_ JI PERCOLATION BATE 1- 7 5 (minotesnnch) PERC HOLE DIAMETER 6" TEST RUN BETWEEN 10' FTAND 10-5 FT COMMENTS Soils drained quickly -started test after checking twice with 12" of water. E 0eglh to Water Aller Monitoring? HOD Date: -7, 9 (ENGINEER'S SEAL) 4�0 OF ;46 h no° OOQFeAr ,. Reading Date Gross Time Net Time Depth to Water Net Drop 1 617--2-4-7-91 3 " 7:15 6TH 4 9:10 6-" --- " 10:30 6 6 " 8"30 6' 7 S 10 PERFOnmw BY: I7__ Pe_ Iij gh I Dee High CERTIFY THAT THIS TEST WAS PERFOnMEO IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFEOT ON 7HIS DATE. DATE: 6-24-97 72-000 (nev. 4/65) Septic Solutions, Inc. 8W4 BWd)e" Rd, Anciw .V%Akam995x¢ May 21, 1997 Municipality Of Anchorage On Site Services 8251' Street Anchorage, Alaska 99501 Attn:Jim Cross Re: Lots 2 & 3 Vons Subdivision Well & Septic System Dear Mr. Cross Attached is the application and design for an on-site well and septic system for NCP Construction Limited. As you are aware the design incorporates the use of our In -Drain modules in lieu of washed septic rock. Per your request the design adds additional In -Drain modules necessary to provide the soil absorption area required for a standard deep trench system. However, because a design based on In -Drain modules would require only one trench of 32 feet (8 standard modules), we have designed 3 trenches. Each new trench line has the capability to be isolated to allow loading of 1, 2 or all 3 trenches. This will allow us to test the effectiveness of the single In -Drain trench and very easily open one or both of the other trench lines if the test results warrant. Although our pilot system for Alaska is operating fine for Alyeska Ski Resort in Girdwood, and there are thousands of successful systems installed in other states, this is the first system to be installed for a single family residence within the Municipality of Anchorage utilizing the In -drain technology. I would be happy to review this design or any of the other materials we have provided you previously, should you have any questions. We plan to monitor the system once a month for 1 year using a sampling well installed in the trench. Per your request we will copy your department with sample results on B.O.D.'s, nitrates, and fecal coliform. Thank you for your continued cooperation. Sincerely, Thomas DeMattia 0 Pagel Septic Solutions, Inc. Site Narrative Project: Vons Subdivision, Lots 2 & 3 This development is combining two lots 165'x 300' each at 49,500 S.F. each. The common lot line separating lots 2 & 3 is to be vacated by the owner. The lot to the west (Vons Subdivision Lot 1), is in the process of being developed. The on site septic system as-builts have not yet been submitted to the Municipality. The lot to the east ( Vons Subdivision Lot 4), has been recently developed and records indicate no conflict with the proposed well and septic system. The lot to the south (Golden Hills Subdivision, Blk. 3, Lot 1) is separated by a 20' utility easement. The proposed on site septic system and well appear to have no impact. The lot to the north is undeveloped. Well The proposed well is located 100' east of the west property line and 100' north of the southern property line. The proposed well impacts no other properties. The location of the proposed well is west of the house. Septic System Lots to the west, south and east have existing septic systems. These systems do not affect the proposed well and septic system on the subject lot nor does the proposed septic system and its replacement area impact any other lots. There are three proposed leaching trenches designed with In -drain Modules. The three trenches are of equal length and are to be installed parallel to the contour of the site. Each trench is sized to stand alone utilizing standard In -Drain capacity criteria. The combination of the three trenches together provide the necessary infiltration area required by the M.O.A. standards for adeep trench system. Drainage The subject lot slopes generally from south to north. The maximum slope on the lot is approximately 8%. There are no steep grades or ravines on the site nor is there any running water or ponds on the site. The site topography is depicted on sheet 4 of 7. All areas disturbed will receive topsoil and seed to prevent erosion. a:\ncp\narrative.dot Page 1 of 1 5/21/97 Permit No G Municipality of Anchorage Department of Health and Human Services ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 • Anchorage, AK 99519-6650• Tel: 343-4744 Well & On—Site Wastewater Disposal System Legal Description: VONS SUBDIVISION SYSTEM DESIGN CALCULA'T'IONS DESIGN PARAMETERS: 1 3 BEDROOM HOUSE OF 450 GAL./DAY 2� PERCOLATION RATE= 4MIN./INCH. 2)3) APPLICATION RATE (DEEP TRENCH)= 1.2 GPD/SF A) STANDARD TRENCH REQUIREMENTS. AREA = # OF BEDROOMS X 150 GAL./BR. / ABSORPTION RATE AREA = 3 BR. X 150 6PD/BR = 375 SF. B) INDRAIN REQUIREMENTS: STANDARD INDRAIN 7"H X 3'-0"W X 4'-0"L TREATMENT CAPACITY= 1.0 GPD./SF. FABRIC # OF MODULES REQUIRED FOR TREATMENT= 7 C) M.O.A. SURFACE AREA COMPARISON: jlju�utu Page 1 of 7 W.O. 97313 Date 5-17-97 PID No. ? SURFACE AREA REQUIRED (INDRAIN) = 116.7 SF. SURFACE AREA REQUIRED (DEEP TRENCH) = 375 SF. NO. OF MODULES REQUIRED FOR DEEP TRENCH = STANDARD TRENCH AREA SURFACE AREA PER MODULE = 375 SF./16.6 SF./MODULE= 22.6 MODULES USE= 3 TRENCHES WITH 8 MODULES EACH, FOR A TOTAL OF 24 MODULES 24 > 22.6 THEREFORE OK Permit No Municipality of Anchorage Department of Health and Human Services ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 • Anchorage, AK 99519-6650• Tel: 343-4744 Page 2 of 7 W.O. 97313 Date 5-21 —97 Well & On—Site Wastewater Disposal System Legal Description: VONS SUBDIVISION PID No. ? NOTES: 1 ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH CHAPTER 15.65. WASTEWATER DISPOSAL REGULATIONS OF THE MUNICIPAL CODE AS CURRENTLY AMENDED. 2 NOT USED 3 INSTALL NEW SEPTIC TANK AS SHOWN ON THE DRAWINGS. SET TANK LEVEL & RECORD INLET AND OUTLET ELEVATIONS OF THE TANK. TANK SHALL BE PLACED ON UNDISTURBED NATIVE SOIL. PLACE OUTSIDE PROTECTIVE WELL RADIUS. 4 SITE TOPOGRAPHIC SURVEY PROVIDED BY OWNER. EXISTING STRUCTURES, WELLS, SEPTIC SYSTEMS OBSERVED WITHIN 200 FT. OF PROPOSED SYSTEM SITE ARE SHOWN ON DESIGN DRAWINGS. 5 ANY DEVIATION FROM THE DESIGN MUST BE AUTHORIZED BY THE ENGINEER PRIOR TO ITS INCORPORATION INTO THE SYSTEM. 6 CONTRACTOR TO LOCATE ALL UNDERGROUND UTILITIES, PROPERTY LINES, EXISTING WELLS, 'WATER WAYS, SURFACE AND SUBSURFACE DRAINAGE FACILITIES, LAKES, PONDS, AND OTHER FACILITIES REQUIRING SEPARATION DISTANCES FROM THE PROPOSED SEPTIC SYSTEM. CONTRACTOR TO STAKE PROPOSED SYSTEM PRIOR TO CONSTRUCTION. NOTIFY THE ENGINEER OF ANY OBSERVED CONFLICTS PRIOR TO CONSTRUCTION. 7 NOTIFY THE ENGINEER AND DHHS 21 HOURS PRIOR TO COMMENCING WITH CONSTRUCTION. A MINIMUM OF THREE INSPECTIONS ARE REQUIRED. THE FIRST INSPECTION SHALL BE OF THE SUBGRADE, PRIOR TO PLACING SAND FILTER. THE SECOND INSPECTION SHALL BE AFTER THE PLACEMENT OF GRAVEL, DISTRIBUTION PIPING, STANDPIPES, TANK, AND OTHER COMPONENTS AS SPECIFIED. THE THIRD INSPECTION SHALL BE AFTER THE WORK IS COMPLETED. 8 CONTRACTOR SHALL DELIVER TO THE ENGINEER A SET" OF RED -LINED, AS -BUILT DRAWINGS SHOWING ALL DAI"A AS SPECIFIED IN SEC. 15.65.F.2, 3, 4, 5, 6 OF MUNICIPAL WASTEWATER DISPOSAL CODE WITHIN FIVE. DAYS OF THE FINAL INSPECTION. INVERTS AND SWING TIE LOCATES SHALL BE TO THE NEAREST TENTH OF A FOOT. THESF AS—RUILTS SHALL BE USED BY THE ENGINEER TO PREPARE AND SUBMIT RECORD DRAWING TO -DHHS. g STAKE ALIGNMENT OF SYSTEM WITH MARKERS SHOWING THE PROTECTIVE DISTANCES FROM WELLS AND OTHER BODIES OF WATER PRIOR TO BEGINNING INSTALLATION. 10 ALL EXCAVATION DEPTHS ARE ADVISORY. THEY ARE TO BE VERIFIED AND MAY BE MODIFIED BY THE - ENGINEER IF ACTUAL FIELD CONDITIONS VARY FROM THOSE USED TO PREPARE THE DESIGN. ouuuou Permit No Municipality of Anchorage Department of Health and Human Services ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 • Anchorage, AK 99519-6650 • Tel: 343-4744 Well & On—Site Wastewater Disposal System Legal Description: VONS SUBDIVISION NOTES: Page 3 of 7 W.O. 97313 Date 5-20-97 PID No. ? 11 EXCAVATE THE ABSORPTION FIELD. BOTTOM OF EXCAVATION SHALL BE LEVEL AND SCARIFIED. RECORD ELEVATIONS AT BEGINNING, MIDDLE, AND END OF TRENCH BOTTOM. CONSTRUCTION EQUIPMENT SHALL NOT OPERATE ON THE FLOOR OF THE EXCAVATION. ANY MATERIAL COMPACTED BY THE OPERATION OF THE CONSTRUCTION EQUIPMENT SHALL BE REMOVED AND REPLACED WITH UNCOMPACTED MATERIAL. 12 PLACE THE SEWER ROCK TO THE SPECIFIED DEPTHS. DO NOT CONTAMINATE SEWER ROCK WITH NATIVE MATERIAL OR SPOILS FROM EXCAVATION. LEVEL ROCK SURFACE TO t 1" PRIOR TO INSTALLING THE PERFORATED PIPE. 13 ALL PIPE SHALL BE PVC CONFORMING TO ASTM D3034 OR ENGINEER -APPROVED EQUAL. MIN SOIL COVER SHALL BE 4 FT (OR 2' SOIL AND 2" INSULATION BOARD - SEE NOTE 14) 14 ALL INSULATION BOARD SHALL BE 2" THICK DOW HI -35 INSULBOARD OR ENGINEER -APPROVED EQUAL. CENTER INSULBOARD WIDTH OVER PIPES, FIELD, AND SEPTIC TANK. 15 GEOTEXTILE SHALL BE MIRAFI 1405 OR ENGINEER -APPROVED EQUAL. LAP ALL JOINTS 2' MIN. 16 COVER THE DISTRIBUTION PIPE WITH MIN 2" SEWER ROCK, AND COVER WITH GEOTEXTILE BEFORE PLACING INSULATION AND BACKFILLING. 17 MATERIAL USED AS FILL SHALL BE CLEAN AND FREE OF ORGANICS, TRASH AND CONSTRUCTION DEBRIS. 18 SLOPE ALL FILL MATERIAL TO DRAIN AT 2% MIN. SLOPE, AND 3:1 MAX SLOPE, AND IN SUCH A MANNER THAT PONDING AT OR NEAR THE DRAIN FIELD DOES NOT OCCUR. THE FILL SHALL BE LEFT AT 6" HIGHER THAN SHOWN TO ALLOW FOR SETTLEMENT. SEED SURFACE AFTER COMPLETING INSTALLATION AS PER MUNICIPAL SPECS, 19 RECORD THE FINISH GROUND ELEVATION OVER TOP OF BED. MUNICIPALITY OF ANCHORAGE u Department of Health and Human Services P.O. Box 196650 Anchorage, Alaska 99519-6650 Date: May 31, 1995 To: Zoning and Platting Division, CPD From:q s Cross, P.E., Program Manager, On-Site/Water Quality Subject: Request for Continents of Cases due 6/01/95. The Environmental Services Division. On -Site Services Section has reviewed the following cases and has these comments: S -9743S Vons Subdivision, L 2A. The information submitted does not satisfy the requu-ements specified by AMC 21.15 and 15.65. Specific deficiencies include, but may not be limited to: 1. Inadequate soils testing, percolation testing and ground water monitoring to conium suitability for development using on-site wastewater disposal systems. 2. Areas designated for the original and replacement wastewater disposal system sites must be identified and must meet all criteria specified in AMC �Suppor 'ng documentation on water availability must be provided. l tom! �� Ci MUNICIPALITY OF ANCHORAGE .. COMMUNITY PLANNING AND DEVELOPMENT P.O. Box 196650 Anchorage, Alaska 99519.6650 PRELIMINARY PLAT APPLICATION A. Please fill in the information requested below. Print one letter or number per block. 1. Vacation Code 2. Tax Identification No. 3. Street Address OFFICE USE RECD BY: ❑ i�l =�'�^� � 99'``' l Vf � AoV rn; I IJ,i 4. NEW abbreviated legal description (T12N R2W SEC 2 LOT 45 OR SHORT SUB BLK 3 LOTS 34). 5. EXISTING abbreviated legal description (T12N R2W SEC 2 LOT 45 OR SHORT SUB BLK 3 LOTS 34) full legal on back page. 6. Petitioner's Name (Last - First) �eeeeseee . ennJeee6eeee ©®eeeeeeee : eeee6©eee Address IBS 9 ELI L'LAnLEI-� PL City AN f; ha rzA 0 S State 4 k Phone# 2.5 8 -..3Og0 Zip 9'i/101 7. Petitioner's Representative Address City Phone # State sm 8. Petition Area Acreage 9. Proposed 10. Existing 11. Grid Number 12. Zone Number Lots Number Lots 13. Fee P � 14. Community Council /r'/C/ ��/LLS I de B. I hereby certify that (I am) (I have been authorized to act for) the owner of the property described above and that I desire to subdivide it in conformance with Chapter 21 of the Anchorage Municipal Code of Ordinances. I understand that payment of the basic subdivision fee is nonrefundable and is to cover the costs associated with processing this application, that it does not assure approval of the subdivision. I also understand that additional fees may be assessed if the Municipality's costs to process this application exceed the basic fee. I further understand that assigned hearing dates are tentative and may have to be postponed by Planning Staff, Platting Board, Planning Commission, or the Assembly due to administrative reasons, Date: `Agents must/provide written proof of authorization. zaoaa wom lae.. aas� May 2, 1995 Robert J. Bellott Barbara A. Bellott 1853 Buccaneer P1. Anchorage, AK 99501 2_7--g -3 "z a i Mr. Jerry Weaver, Platting Officer Municipality of Anchorage Community Planning and Development PO Box 196650 Anchorage, AK 99519-6650 re: Dear Mr. Weaver, short plat lot's 2 and 3 Von's Subdivision During our preliminary meetings concerning my intent to replat lots 2 and 3 of Von's Subdivision into a lot 2A, the question of improvement of 99th street was raised. I own the entire subdivision at this time consisting of four lots. I intend to build a house on the single lot 2a resulting from the re -platting of lots 2 and 3. There is access to these two interior lots from Grover along E. 99th. Beginning at the Northeast corner of lot 3 there is a logging road which is to be improved allowing access to the interior of lots 2 and 3. Lot 4 is accessible along its entire Eastern boundary. Lot 1 is accessible by way of 99th from the West. Mr. and Mrs. Lawrence B. Newby own the lot immediately to the North and have subdivided it with long lot lines parallel to 99th and accessible from Grover and or an interior cul-de-sac. They advise me that they do not wish to gain access from 99th. As noted above, I do not require access either, nor would future owners of lots 1 and 4 require it unless they preferred it. Accordingly, I would not expect to improve 99th any further then it already is on the Eastern end. Mr. Randy R. Ross, P.E. was agreeable to not developing 99th when I meet to discuss it with him. Thank you for your assistance and advice. Sincerely, Robert Bellott encls. ori,!: / { /560 I U562ox 5605 x 9685,x x J 1 15650 / P 4�. �(�•t'.rY .# 4 >4{{1�[� �t,+�f� Vlt4� }�' I.� i i �1ii,,,� _, `1 ° P 4 � Yf �.�k.iR'4"fTY✓hi w�;�r��t�ai�'sH �. .�` 4!f-y�i�i�� sV �� ,��ill.kst ��{rf .�.f Fry+�ti', °S�i 1,x1 �eV1 01 'C4, 1' ". '�(lfaF il' if r• 1 r. �' � •+ ..., r , '. + ' , 1 i� , i'.1 r�y'tiutl ,�Fii. �1 ct. 1. 1: �x.P1T,61i TR tt'197� ' ( ,f 1t ' 1111 1j16�f4f 1/ 1", ( rROPLITT OWM t FOREMOST HOMES 11 • ! - dt '� . a'6i 1 '�', '20T '>l BLOC �.' CAIr1'h'H HILLg rf ibcuknon .. r 1'1 1', t l + r n•Y .Ixpiu 01r -"MI 1421 BIAMETE1tt ,6 '_I I'1�� BRlidIIHO LOOt d - 251 . brown gravelly Olay �f 25 - 35 brownish grey slay and bond (.. 35 - 53 send and gravel .. 53 - 70 Bend, gravel and some olgy ,:,' �t•u Ir +I ,','';1 �. '•'_11 70 - 75 sand,rook, and al 75 - 92 mostly sand and grayslt tittle ,1}14 92 -109 more slay, less send and grayel'Slil; �' It!,,,�1','�; a' 109 -122 some Beapage in sandy 01aY' +; "'', 1;. 122 -137 more clay, less amid, little seepage. 1�,•' Idil �P4 1'3 137 -142 coarse Band and gravel aquiferrlargs 1 A 111`4' '1• 601 from bottom STATIC LEMI 1 /11'I h1' r i_ C201gal./min. 40" o buttom ''. � `(i i 1'i'1 / 71+F It j� f}ip 1,11 1, �''�ir•'.• TRUETP/THE BEST/10 1�KNO,p�/ o ��%%/%�e t /! _jgIILLTHO COIITRAOTOAt COOK INLET ENTERPRISES n'Li4r ( 1424 E. 71 th Ave. I Anchorage, Alaska 99504 276-2025 a 1 At 0} { �/ j�{hlf�'�. t iii 4111111 1+nt 1 � 1 I - 1 �' 11 f�'tl�� )1 1 In , n• �, 1f l Slk,! 1'`,'�7J(' ,{l1�pj ""i:'i11111r1 Jf44 ft2+f1�L� J e �•: A 1 It471C 1.t.17"L- //O> r eIF 7,1 e,41 i�/^.►°rti 11•LI"L 8(i�'� �iir/. /�'<;J�'n� .,,;, IzJt>> tr��r' rJr%;r ,��1lS7 511 a��r• s �� `.ci�,P , 711,'t PA1111 D ' 1 CJr. ml 76 �r//+rrrr , /�+� A/nz 'tiT1+N7tn yr�'rn /..C[A710/b ; l�7• / /.ilk :3 Une�CSJ ,% �J/cts '� �rSu,dA�%'',+�� 12P)II,I4 5 1P)>3n alp 6,lw•[ '!' 121. CGA/ f GI�A�['[ - 5rni1 • syr , ' • ..r + l2 ' /.zi 51t ry �iAnA • iYFPs /-la C ) APy, 1//)/ C4,41 lY GJ�Avx; 5rcT 3�) !rt 40 '�,- 1GH �L^yi GIi,PJliL SrIT y - )-7A C L/I C-10 l �. YXJ<r NA1sA a • ,21+ 5lL/7, i✓1Apy L' AY- `X�Li " 1 It471C 1.t.17"L- //O> r eIF 7,1 e,41 i�/^.►°rti 11•LI"L 8(i�'� �iir/. /�'<;J�'n� .,,;, a, [n Ar yc•,�'r �r//+rrrr , /�+� A/nz 'tiT1+N7tn yr�'rn .111Rvl���/y � �•GA/�/'l,i"LL �C,Z't r"� �yf7��al /y,2y t, a7 « /llrlo,:lyP 27G •J.o� 5 SAI 4-1 0.. 30 r ��ft•LS'n/�yi Qi?c� �i1 JdC�� ,/ �� eof , :'i , s 3Cl—CV +-�jr1i� C/C% Com'• )�� it /.i'i f, %',' ,1 all /} C ry2eW C/ /ps 0•0 1 i? e Y s (%G '/2J /��lC`i1° r/c4tr:/f utr?CI (//rryl�/14c�e� /yG /5 y' S7aur/ (/� /^ �,nC .•, : c c,/� , �mF SeY/Yt< f F , %lJ.. /6.) • /�%brior• �,h/�rcn,;5•„ Jri�r.z'� �,L+1�M � � •�Ci �� /Fc�i'�; t�/':Xr/t Y� fF�� �j!'� (?r/(,;'�'i t �. .k1 •i Piro/.c`i��-. ',y$ AA.NKIaALITr TN AWK ,. )! DIN IN MAlln 6 MUNICIPALITY OF ANCHORAGE (MOA) INVIgCrwQNIA1 PPOIICIION HEALTH AUTHORITY APPROVAL (HAA) „ I 87 CHECKLIST • FEBRUARY 1964 164.4710 RECEIVED Legal DescriptionN•__� LOt 4 - Nettleton °,,.ubd—ivieTonon A WELL DATA Writ Taasbtrt dh.n• )-r1 Va to It A B C. D E C Appro.od (Y/N) Wwi I ug 1`r esrn`I it Ni n Guar Ielad C p 9'l ,om ast 1 4 ........ rata .._4+. (.YM Toral Dr•p in AG: rox 1 ?('.;rsnd In Depth of Grouting _)I/A__- .� _ _ r.airatr..ri ( PurnpSol At Gwner_Saye_SB7 --J — Sa,.iiq roigre. AP9yn O. uor,l r I•' Sanitary Sent on Casing IY/N) I .' . •.i., n Y,.• ...; , . • a•.ii v N j C S Depression Neord Wellhead (Y/NI n0 Sru a•Al,. ,. 1, �•.rii. ,. ,r ...r.•. r.•..,:- r , i.. On Adjoining Lots ___100M__--- ' rn,e..:• 1 ,i„ j : t'ii+' On Adjoining Lots 100+' f I•. ii' .4 p•r- I.rii n`. Lill j g _ :. "n r...r ride, -.r.11, I .•; A to Neaiedl PuDbC Sewer ai W Mir ` `%ATo Nearest Sewer Service Line on Lot ,/A W.r•.a,,,..,,r r. ..o,:n, -0] :nmac Dale _Pebt-uary j.r 1987 B SEPTIC HOLDING TANK DATA Unknown I�-'Ll` r ..i •r..- ., .i.; .. Site - No pI COmparimanls __ r,lp•I' �r N ^- An Iignl Caps ,y Ni .fEF _ Foundation Cleanout (Y/N) n• - No __. _ __ 1......,,•..a., '.ai. iy N: '.� Dale Last Pumped November r•;...rI klame•nn'v_i (.unV ac' in id'. iY NI '�A for ___NIA rri i . ri yh a.ver A-,ar- n N• A Ternpo.ary Holding Tank Permit (Yi NI ;.. P.p.i'.IA.I. inU^. r a ..epliL I'011.... innv , ti. Y�nmr 5..1 r'. rnai 1 ^0+' To Building Foundelion _. 10+' iii r. t„i'vt Sr,�•' io Dsposal F•nd W a•r • Marr vir r I •••• To Stream Pond, Lake. or Major Drainage Gni✓sr• ISD+' ...... As 1-ICes no' rrnCi rY m.Imber of compartments. I In ` 1" = 60' SITE PLAN IP rc �TlznA A vmiomm-mt r'z OyZz ✓)� -rn c`m y A G x 1 UI I f \ r I I I 'O I (n M , �u ���� \�\OrTt\�\. t7 \.\N�\\�, \ no. \ �� �\r` N \ \\ \�,_ n \�\ r'Il �\�\\\\ 70 \�\ K I I I I \ I J\ za f^ N y - r DA; r O 7 n` yl s I I IP rc �TlznA A vmiomm-mt r'z OyZz ✓)� -rn c`m y A G x 1 v PERFORMED FOR: LEGAL DESCRIPTION D'H 1 yr r:a l Uf✓.G�r�lc5 2 41, 1;1:1:1:1 -VA - cac&mc. stay Stra 4 5 6 7 8 COMMENTS Mysk — Slur w/ st(_T? S," LENS6r T{IRVUpU w'L S? — &(mA . t-INr— MGIC S4,9 WAS GROUND WATER ENCOUNTERED? IF YES, AT WHAT DEPTH? JLUrt SITE PLAN Depth to Water Aller Monitoring? ')Ay Dale: ?C/9 g6 S L O P E �� MIC -2 Net Time Depth to Water Net Drop ■ �ii■ir■i■�=■ OSPAA- 1■■■®■I■■■■ nrti 6.. 17 Ao�cn a. zZ- ,1Ib����I!%1■■■ i!� �■®il�ii�■J �■I■�■!�i!■ice■ Reading Date Gross Time Net Time Depth to Water Net Drop K— OSPAA- 610 nrti 6.. 17 Ao�cn a. zZ- 2-� PERCOLATION RATE (minutes/inch) PERC HOLE DIAMETER q [ TEST RUN BETWEEN _ FT AND �(). 3 FT en T K. S & S E . •'NEERING PERFORMED BY: IMMA— CERTIFY THAT THIST ST WAS PERFORMED IN 1s pver oop Road—No. 2O4 ACCORDANCE WI9*%Y•ST�A°jE'A�All cffi9VPjI`AL GUIDELINES IN EFFECT ON THIS DATE. DATE: Y // ':t'IT.5— 72-008 (Rev. 4/85) c PER LEG F c 1c 11 12 13 14 15 16 17 18 19 20 �� TEST RUN BETWEEN 5 FT AND -I-S FT COMMENTS ZP KMFFS Cxaau?790 %c? S & S ENGINEERING PERFORMED BY: _ I ✓s<i CERTIFY THAT T IS TE T WAS PERFORMED IN 7iL P ca a /j� ACCORDANCE WITVp@L@ RiVM AWka>8 GUIDELINES IN EFFECT ON THIS DATE. DATE: —/ / I Z- �y f- 72-008 (Rev. 4/85) MUNICIPALITY. OF ANCHORAGE Development Services Department_ ``� Phone: 907-343-7904 On -Site Water & Wastewater Section - Fax: 907-343-7997 Certificate of On -Site Systems Approval Parcel I.D. 015-081-37 1. GENERAL INFORMATION Complete legal description Vons Lot2A Location (site address) 7050 E 99th Ave Expiration Date Current property owner(s) Peter Bellino & Emily Lescak Day phone Mailing address Real estate agent 2. TYPE OF DWELLING: Fx� Single Family (w/wo ADU) ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF BEDROOMS: 4 Day phone 4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Private Well 0 Private Septic 0 Water Storage ❑ Holding Tank ❑ Community Well ❑ Community ❑ Public Water System ❑ Public Sewer ❑ Waiver request for: Distance: Received by: Date: COSA to be released to the engineer, unless otherwise requested by the engineer. COSA Fee $ 550 Waiver Fee $ Date of Payment Receipt Number 9C COSA #_ 05CZl l lar Date of Payment Receipt Number Waiver # 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is (are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. In conducting an adequacy test, I attempt to provide a thorough, conscientious engineering analysis of the system in accordance with MoA COSA guidelines and regulations. The reported results describe the performance of the system under the conditions encountered at the time of the test, and separation distances measured to readily identifiable features. The operational life of all wells and septic systems depend on the local soil condition, ground water levels that may fluctuate during the year, and the water usage of the family being served by the system. These conditions are outside the control of the evaluator of this system. All systems eventually fail and satisfactory test results do not guarantee future performance of the system, nor do they guarantee that there are no hidden defects or encroachments. Therefore we cannot provide any warranty for future performance, nor can we estimate remaining life of the system. The content of this report is for the sole benefit of the owner listed above. Reliance on this report by another person is at their own risk. Pannone Engineering Services LLC highly recommends buyers hire their own engineer to evaluate this report. Name of Firm Pannone Engineering Services Address P.O. Box 1807 Palmer, AK 99645 Engineer's Printed Name Steven R. Pannone P.E. 6. DSD SIGNATURE Phone (907)745-8200 Date 2 System #1 Approved forq r, bedrooms tg •Steven •R� P'onncrie­ ICE 8149 . System #2 Approved for bedrooms Disapproved ���`D��orEss� Conditional approval for bedrooms, with the following stipulations: OF���i, ` UIN-01T WATER AND WASTILvHKC)GRA'ATER oz J t FNT SER\ I `��� Original Certificate Date: 3 –2 — The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 7. ATTACHMENTS: COSA Checklist X Septic System Advisory Well Flow Advisory COSA Checklist blue sheet Nitrate Advisory Arsenic Advisory Other 0�-%V 4e i�dtl�'SiU►'�p ,. i RY 9 COSA Checklist Legal Description: Vons Lot2A If more than 1 septic system on lot: COSA Checklist # 1 of 1 A. WELL DATA 0 Well log is filed with Onsite (or attached) Date drilled 6125/97 Total depth 203 ft Cased to 203 ft NO Sanitary seal is functioning correctly 0 Wires are properly protected Casing height (above ground) 18+ in. Date of flow test for COSA 3111/21 Static water level at beginning of test 82.2 ft. Comments B. TANK DATA 1947 Age of tank(s) 24 years Tank type/material 5"" " Measured operating fluid level in septic tank 50 0 Standpipes/foundation cleanout per record drawing Date of pumping 2-26-21 D. ABSORPTION FIELD DATA Shallow Trench Which system tested (date installed) 812012015 ❑ ALL standpipes present per record drawing Total measured depth from grade 22Q" ft (max) /g—Sa Measured depth to pipe invert from grade 188/*'ft (min)f.:r4 ❑ NIA — pressurized field ❑ Monitor tubes go to bottom of effective. If not, state depth into effective 46" 01 Code -required soil cover over field ❑ System presoaked (Required if vacant for greater than 30 days prior to date of test) Gallons introduced gallons Comments/Deficiencies: COSA Checklist yellow sheet Parcel ID: 015-081-37 Structure served by this system 1 Well production at time of test 4.5 gpm Water storage tank volume na gallons Well disinfected for coliform test? ❑ Yes ❑✓ No ❑ Coliform bacteria is Negative Nitrate mg/L FM� Nitrate less than MRL (ND) Arsenic ug/L ❑ Arsenic less than MRL (ND) Collected by Pannone Engineering Date of Sample 3/15/21 C. LIFT STATION ❑ Required maintenance completed Age of lift station years Lift station material Comments: Adequacy test date 3111/21 Results 0 Pass For 4 bedrooms Fluid depth prior to test 0/0 in Water added 600 gal New depth 7 in Elapsed time 2hrs min Final fluid depth 0/0 in Absorption rate 600+ gpd Any rejuvenation treatment (past 12 months) If yes, enter date E. SEPARATION DISTANCES From Private Well on Lot to: (Please enter distances if less than required or if community well) Septic Tank/Lift Station on Lot > 100' ✓J Yes if No Community Sewer Manhole/Cleanout > 100' F/ Yes if No ft ✓1 Yes if No ft Neighboring Tank > 100' 0 Yes if No ft Private Sewer/Septic Line > 25' 0 Yes if No ft Absorption Field on Lot > 100' E✓ Yes if No ft Holding Tank > 100' 171 Yes if No ft Neighboring Absorption Fields > 100' Yes if No Animal Containment > 50' ❑✓ Yes if No ft M Yes if No ft Manure/Animal Excreta Storage > 100' Community Sewer Main > 75' Yes if No ft M Yes if No ft From Septic/Holding Tank on Lot to: (Please enter distances if less than required) Building Foundations > 10' ®✓ Yes if No ft Surface Water > 100' Q✓ Yes if No ft Property Line > 5' ✓J Yes if No ft Wells on Adjacent Lots: Absorption Field > 5' 0 Yes if No ft Private Wells > 100' 0✓ Yes if No Water Main > 10' dQ Yes if No ft Community Wells > 200' ✓0 Yes if No • Water Service Line > 10' 0 Yes if No ft If septic tank is under driveway comment below From Absorption Field on Lot to: (Please enter distances if less than required) Building Foundation > 10' E✓ Yes if No ft if absorption field is under driveway comment below Property Line > 10' M Yes if No ft Wells on Adjacent Lots: Water Main > 10' ✓l Yes if No ft Private Wells > 100' Yes if No Water Service Line > 10' Fl� Yes if No ft Community Wells > 200' Q✓ Yes if No Surface Water > 100' ✓0 Yes if No ft F. ENGINEER'S COMMENTS G. ENGINEER'S CERTIFICATION l certify that / have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA COSA guidelines in effect on this date. 2itS_ COSA Checklist yellow sheet Steven R Pannone CE 8149 ft ft ft I, www.muni.org/onsite Septic Tank Advisory Certificate of On -Site Systems Approval #OSC 211136 Subdivision: Vons lot 2A Starting at 20 years of age the MOA issues Advisory's for steel septic tanks. The septic tank for this property is 24 years old. Typical replacement costs range from $8,000 to $11,000 This advisory must be attached to all copies of the subject Certificate of On -Site Systems Approval. This is an example of what the metal of a 20 -year-old steel tank MAY look like. • Municipality of Anchorage o� < • On-Site Water&Wastewater Program .ate-• (907) 343-7904 F•r CERTIFICATE OF ON-SITE SYSTEMS APPROVAL Parcel I.D. 015-081-37 Expiration Date: -� - cr 1. GENERAL INFORMATION Complete legal description VONS; LOT 2A Location (site address) 7050 EAST 99TH AVENUE*ANCHORAGE,AK Current Property owner(s) HAROLD AND DAWNA TOWNSEND Day phone 907-632-0374 Mailing address Real Estate Agent Day phone 2. TYPE OF DWELLING: U Single Family (w/wo ADU) Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF BEDROOMS: 4 4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Individual Well Individual On-site U Individual Water Storage ❑ Individual Holding tank ❑ Community Class Well ❑ Community On-site ❑ Public Water System ❑ Public Sewer ❑ WaiverNariance request for. N/A Distance Received by: Date: COSA to be released to the engineer,unless otherwise requested by the engineer. COSA Fee $ 55" Waiver Fee $ Date of Payment `�`I Date of Payment Receipt Number 06,993 Receipt Number COSA# 05e//3/051 Waiver# 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On-Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm GARNESS ENGINEERING GROUP, Ltd. Phone 337-6179 Address 3701 E. TUDOR ROAD, SUITE 101 *ANCHORAGE,AK,99507 Engineer's Printed Name JEFFREY A. GARNESS, P.E. Date Z/7.48 1 t 5 Engineer's Comments: In conducting this evaluation.GEG provided an engineering evaluation of the well and/or septic system in accordance with the �l�/s-�SC I m il guidelines and regulations established by the Municipality of Anchorage and industry practices.The reported results describe the .44-�(s l_/1 i , . condition of the systems on the dates of the evaluation.Separation distances were measured to readily identifiable features. . \ Hidden defects or encroachments may exist that were not identified during the evaluation.The operational life of all wells and septic systems depend on a variety of variables including,but not limited to,soil conditions,groundwater levels(that may fluctuate during i • �1.— ♦♦ the year).quality of construction(materials and workmanship).and the water usage of the family utilizing the systems.These % *J A U '/\ •.•* ♦. conditions can vary.and are outside the control of GEG.Satisfactory test results do not guarantee future performance of the 0 : If more than 1 septic system is on the lot: COSA Checklist# of Structure served by this system Certificate of On-Site Systems Approval Checklist Legal Description: VONS: LOT 2A Parcel ID: 015-081-37 A. WELL DATA Well type PRIVATE If A, B, or C provide PWSID# N/A Well Log (Y/N) YES Date completed 6/25/1997 Sanitary seal (Y/N) YES Wires properly protected (Y/N) YES Total depth 203 ft. Cased to 203 ft. Casing height(above ground) 18+ in. FROM WELL LOG AT INSPECTION Date of test 6/25/1997 9/13/2018 Static water level 106 ft. 84.8 ft. Well production 10 g.p.m. 5.5+ g.p.m. WATER SAMPLE RESULTS: Coliform NEG colonies/100 ml. Nitrate ND mg./L. Collected by: GEG, Ltd. Arsenic: ND ug./L. Date of sample: 2/18/2019 B. SEPTIC/HOLDING TANK DATA TANK LIQUID DEPTH WAS 50"ON THE DATE OF OUR INSPECTION Tank Type/Material SEPTIC/STEEL Date installed 8/24-27/1997 Tank size 1250 gal. Number of Compartments 2 Cleanouts (Y/N) YES Foundation cleanout (Y/N) YES Depression over tank (Y/N) NO High water alarm (Y/N) N/A Date of pumping 7/30/2018 Pumper A+ HOME SERVICES C. ABSORPTION FIELD DATA *BELOW EXISITNG GRADE AT MT2 Date installed 8/20-28/2015 Soil rating ..p.d./ft •r ftz/bdrm) 1.2 System type SHALLOW TRENCH Length 50 ft. Width 5 ft. Gravel below pipe 4 ft. Total depth *14.4 TO 18.3 ft. Eff. absorption area 500 ft2 Monitoring tube YES Depression over field NO Date of adequacy test 9/13/2018 Results (Pass/Fail) PASS For 4 bedrooms Fluid depth in absorption field before test 14 in. Water added 610 gal. New depth 22 in. Elapsed Time: 120 min. Final fluid depth 16 in. Absorption rate >= 600+ g.p.d. Any rejuvenation treatment(past 12 mo.) (Y/N & type) NO If yes, give date - • 1997 SYSTEM WAS SURCHARGED UPON ARRIVAL AND COULD NOT BE TESTED; HOMEOWNER SWITCH THE DV VALVE TO 2015 TRENCH ON 8/17/2018 TO"PRE-SOAK"PRIOR TO GEG INSPECTION • MT1 EXTENDS APPROXIMATELY 3.5' BELOW CO1 AND MT2 EXTENDS APPROXIMATELY 3.58' BELOW CO2 • FOR SOME UNKNOWN REASON. MT1 REMAINED DRY THROUGHOUT THE TEST, IN SPITE OF BEING AT VIRTUALLY THE SAME ELEVATION AS MT2 (14-1 1' 2Vk/ D. LIFT STATION Date installed Size in gallons Manhole/Access (Y/N) "Pump on" level at in. "Pump off' level at '• wa er alarm level at in. _ . •• Cycles tested Meets alarm &circuit requirements? E. SEPARATION DISTANCES SEPARATION DISTANCES FROM WELL ON LOT TO: Septic tank/lift station on lot 100'4- On adjacent lots 100'+ Absorption field on lot 100'+ On adjacent lots 100'+ Public sewer main 75'+ Public sewer manhole/cleanout 100'+ Sewer/septic service line 25'+ Holding tank 100'+ Animal containment areas 50'+ Manure/animal excrete storage areas 100'+ SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO: Building foundation 10'+ Property line 5'+ Absorption field 5'+ Water main 10'+ Water service line 10'+ Surface water 100'+ Wells on adjacent lots 100'+ SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO: Property line 10'+ Building foundation 10'+ Water main 10'+ Water service line 10'+ Surface water 100'+ Driveway, parking/vehicle storage 10'+ Curtain drain NONE KNOWN Wells on adjacent lots 100'+ F. COMMENTS ••4' OF 11�'♦ G. ENGINEER'S CERTIFICATION :��;, , 1• ;••• •, ♦1 I certify that I have determined through field inspections and • • review of Municipal records that the above systems are in f' r • conformance with MOA COSA guidelines in effect on this .• •�• •• ; date. ♦ fr- A. Gam ss::L= Engineer's Printed Name JEFFREY A.GARNESS �tt5 �� CE X95 �.; :� Date —Li 415l LICENSE•,4�� FES`\ -•4 #AECC884 (Rev.10/12/12) MUNICIPALITY OF ANCHORAGE DEVELOPMENT SERVICES DEPARTMENT 1 • i tk''' \ 907-343-7904 On-Site Water and Wastewater Section F`S / Fax: 343-7997 www.muni.org/onsite Septic Tank Advisory Certificate of On-Site Systems Approval # 0SC191058 Subdivision: VONS Lot: 2A Starting at 20 years of age the MOA issues Advisory's for steel septic tanks. The septic tank for this property is 22 years old. Typical replacement costs range from $6,000 to $9,000. This advisory must be attached to all copies of the subject Certificate of On-Site Systems Approval. This is an example of what the metal of a 20 year old steel tank MAY look like. -- a. • : 5. tel.. " L. A "���yt 0 gyp . `' , 2 1�. art 4.5'^!+ �► , p.. 4. Y -.!,-4.40.,„ ,1 26 •�_ • Mailing Address: P. O. Box 196650 .* Anchorage,Alaska 99519-6650 * www.muni.org a N • E 99th AVENUE 0 0 _ — — — S 89'56'40"E 330.00' • co Ki 0 CHAIN-LINK FENCE • co LU • BARN / 20.0 Z w 0 0 A,pp O O O . ' R 147.0' o o •DRIVEWAY 20° o0 N ni r- r- / 2 STORY 2.0'x6.3'\ • Pi O RESIDENCE • R AA NINr o ; 26cA 4 LA 0�� WALL oo �• iv (A. 12.0.x13.0' DECK N ..'oll'. 3° 4.0'x16.0 • 89,1' DECK --SEPTIC PIPES °0 5'2-i WOODEN FENCE `-WELL S 2.0'1 CANT J� 11.1x9.9' DECK LOT 2A o �� 1. 4'x3.8' CANT 99,089 s.f. / N oco \ QQ- 10' T&E EASEMENT - — — -r /1 I N 89'56'40"W 330.00' I n LOT 1 II inr 73 II LOT 1 I -4 \ I I I NOTE: THERE IS AN UNDEFINED DRIVEWAY ENCROACHMENT EASEMENT, FOR THE EXISTING DRIVEWAY IN THE NORTHWEST CORNER OF LOT 4, FOR THE BENEFIT OF LOT 2A (FORMERLY LOT 3) PLOT PLAN AS BUILT X SCALE 1" = 50' GRID SW 2439 Project No. 15-250/A1 Lang SC Associates, inc. 11500 Daryl Avenue, Anchorage, Alaska 99515-3049 (907)Registered Land Surveyors (907) 522-4625 Fax Phone Goop000pDO kenOlangsurvey.com / jonathanOlangsurvey.com c.. O F �%� I hereby certify that I have surveyed the following described property: ,„/..dr,:... �P' /442‘.%.. ...- � �QO LOT 2A, VONS SUBDIVISION (PLAT 96-104) 49I 1\ •.-y*Oa Anchorage Recording District, Alaska, and that the improvements situated thereon are 17 within the property lines and do not encroach onto the property adjacent thereto, that o 0 no improvements on the property lying adjacent thereto encroach on the surveyed 0 0 premises and that there are no roadways, transmission lines or other visible 0. . .KEN ••' •G. LAN' • ..,o �• easements on said property except as indicated hereon. OQ . $� (�� Q, Dated this the Day of 4p 5{20 . J k`:., at Anchorage, Alaska FpA••4-:S- 7. • 0 0 It is the responsibility of the owner to determine the existence of any easements, 40oR��5s�oNA�oa� covenants, or restrictions which do not appear on the recorded subdivision plat. ��0000� N • Municipality of A Q1pgej 2015 3 On -Site Water and Wastewa gr rogram (907) 343-7904 Certificate of On -Site Systems Parcel I.D. 015-081-37 1. GENERAL INFORMATION Expiration Date: la -,2q-/,r Complete legal description Vons, Lot 2A Location (site address) 7050 East 99th Avenue Anchorage, AK 99516 Current Property owner(s) Mark & Deborah ModeroW Day phone Mailing address Real Estate Agent 7050 East 99th Avenue Anchorage, AK 99516 2. TYPE OF DWELLING: 0 Single Family (w/wo ADU) ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF BEDROOMS: 4. TYPE OF WATER SUPPLY: Individual Well Individual Water Storage Community Class Well Public Water System WaiverNariance request Four Day phone TYPE OF WASTEWATER DISPOSAL: F-1 Individual 0 ❑ Holding Tank ❑ ❑ Community ❑ ❑ Public Sewer ❑ Date: -_ / COSA Fee $ 5 Waiver Fee $ /�aji�7. Date of Payment l /l 1 /15 Date of Payment Receipt Number d`7?A0 � Receipt Number COSA # dnuszoV Waiver # 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm Anderson Engineering Phone Address .P.O. Box 240773 Anchorage, AK 99524 Engineer's Printed Name Michael E. Anderson, P.E. Date _ 522-7773 49?H 6. DSD SIGNATURE �.................. System #1 Approved for bedroomsf OI MICHAEL E. ANDERSON o �� System #2 Approved for bedrooms ,�9 sr•. CE-43ai S y pP it- 187- Disapproved ®4411~® SI' sem Conditional approval for bedrooms, with the following stipulations: (OFt fIri yioi WATER AND WASTEWATER PRO O %A&r �/ll)))llillr\ B �(/ Original Certificate Dater TV Elul It Anchorage Development Services Division (DSD) issues Ca ;i5cates of On -Site Systems Approval (COSA) based only upon the re esentations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 7. ATTACHMENTS: COSA Checklist X Septic System Advisory Well Flow Advisory COSA blue shell r - , _ Nitrate Advisory Arsenic Advisory Other If more than 1 septic system is on the lot: COSA Checklist # _of _ Structure served by this system Certificate of On -Site Systems Approval Checklist Legal Description: Vons, Lot 2A A. WELL DATA Well type Private Date completed 6/25/97 Total depth 203 ft. Date of test Static water level Well production If A, B, or C provide PWSID # Sanitary seal (Y/N) Y Cased to 203 ft. FROM WELL LOG 6/25/97 WATER SAMPLE RESULTS 101 ft 10 9-p m. Parcel ID: 015-081-37 Well Log (Y/N) Y Wires properly protected (Y/N) Y Casing height (above ground) >18 in. AT INSPECTION 7/20/15 88 ft. 5 g.p.m. Coliform 0 colonies/100 mL Nitrate ND mg/L Arsenic ND ug/L Date of sample: 8/28/15 Collected by: And. Engineering B. SEPTIC/HOLDING TANK DATA Tank Type/Material Septic/Steel Tank size 1,250 gal. Number of Compartments 2 Date installed 8/4/97 Cleanouts (YIN) Y Foundation cleanout (Y/N) Y Depression over tank (Y//N) NHigh water alarm ((Y//N) N Date of pumping 'C'� Pumper A10rA1AnJ 19&4,i,7Dl1nl q .JCU 1, C. ABSORPTION FIELD DATA Date installed 8/21/15 Soil rating (g.p.d./ft2 or fe/bdrm) 1.2 GPD/SF Length 500 ft. Width 5 ft. System type 5' Wide Gravel below pipe 4 Total depth ft. Eff. absorption area 500 ft2 Monitoring tube Y Depression over field Date of adequacy test New Const. Results (Pass/Fail) ►■ For _ bedrooms Fluid depth in absorption field before test in. Water added gal. New depth in. Elapsed Time: min. Final fluid depth in. Absorption rate >= g.p.d. Any rejuvenation treatment (past 12 mo.) (Y/N & type) N If yes, give date D. LIFT STATION Date installed "Pump on" level at in. Datum Size in gallons "Pump off' level at in. Cycles tested E. SEPARATION DISTANCES WELL ON LOT TO: Septic tank/lift station on lot >100' Absorption field on lot >100' Public sewer main >75' Sewer /septic service line >25' Animal containment areas >50' SEPTIC/HOLDING TANK ON LOT TO: >5' >5' Manhole/Access (Y/N) _ High, water alarm level at Meets alarm & circuit requirements? On adjacent lots >100, On adjacent lots >100' Public sewer manhole/cleanout >100' Holding tank >75' Manure/animal excrete storage areas >100' Building foundation Property line Water main >10' Water service line >10' Wells on adjacent lots >100, ABSORPTION FIELD ON LOT TO: Property line >10' Building foundation >10' Water Service line >10 Surface water >100 Curtain drain Nolle Noted Wells on adjacent lots >1001 F. COMMENTS G. ENGINEER'S CERTIFICATION 1 certify that I have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA COSA guidelines in effect on this date. Engineer's Printed Name Michael E. Anderson, P.E. Date 9/11/2015 COSA brown sheet 10-10-12.doc Absorption field >5' Surface water > 100' Water main N/A , Driveway, parking/vehicle storage > 10 ITH MICHAEL E. ANDERSONa: o sf ; CE - 4381TA in. E 99th AVENUE -o M _ — — S 89'56'40"E 330.00' �i 0 CHAIN—LINK t` FENCE to N ` Zoo BARN z w o 0 0 R.A.P. DRIVEWAY 20.0 =1 (a 2 STORY �2.0'x6.3'\ RESIDENCE—� / —D &T l ,I w 12.0'x 13.0' DECK N. . N} N 4.0'x16.0. o , 89.1' DECK o 0 52° .WOODEN FENCE WELL 2.01 CANT J� 11:9x9.9' DECK oo 07 1.4'.8' CANT N 00 /O Q� �-/-19' T&E EASE+AENT PIPES LOT 2A 99,089 s.f. 1 I N 89'56'40'W 330.00' I I I I LOT 1 II m' II LOT 1 I n I I I 1 NOTE: THERE IS AN UNDEFINED DRIVEWAY ENCROACHMENT EASEMENT, FOR THE EXISTING DRIVEWAY IN THE NORTHWEST CORNER OF LOT 4, FOR THE BENEFIT OF LOT 2A (FORMERLY LOT 3) 1n t§o r PLOT PLAN AS BUILT X. SCALE , i" 50' OrtD �S'N_2439_ Prole,' No. 15-250/A1 Lang & Associates, inc. 11500 Daryl Avenue, Anchorage, Alaska 99515-3049 (907) 522-6475 Phone 000�p Registered Land Surveyors (907) 522-4625 Fax �QOF gCop�4 kenOlangsurvey.com / JonathanOlangsurvey.com �o`� ,..•••••..- 9 p 1 hereby certify that 1 have surveyed the following described properly: LOT 2A, VONS SUBDIVISION (PLAT 96-104) * 4.9J Anchorage Recording District, Alaska, and that the improvements situated thereon are.................................� within the property lines and do not encroach onto the property adjacent thereto, that no Improvements on the property lying adjacent thereto encroach on the surveyed FA ...................... Q premises and that there are no roadways, transmission lines or other visible ; KENETH G. LANG o easements on sold properly except as indicated hereon. Q nP, Dated this the Day of of Anchorage, Alasko o00�ppp'•1 -5202-•'o,��pv It is the responsibility of the owner to determine the existence of any easements, 4�R���oo covenants, or restrictions which do not appear on the recorded subdivision plat.