HomeMy WebLinkAboutGREENLAND BLK 6 LT 11MUNICIPALITY OF ANCHORAGE On -Site Water & Wastewater Program PO Box 196650 4700 Elmore Road Anchorage, Alaska 99519-6650 Phone: (907) 343-7904 Fax: (907) 343-7997 http://www.muni.org/onsite On -Site Wastewater Disposal System Permit Permit Number: OSP251069 Work Type: Septic Upgrade Tax Code Number: 01517126000 Site Legal Address: GREENLAND BLK 6 LT 11 G:2636 Site Mailing Address: 4721 Ell5TH AVE, Anchorage Owner: WIITA BRYAN Design Engineer: FORGE ENGINEERING This permit is for the construction of: Effective Date: Expiration Date: Lot Size in Sq Ft: Total Bedrooms: ��pctlp S' AM Wk f, Uepartrncnt 4/3/2025 4/3/2026 Q Disposal Field Z Septic Tank ❑ Holding Tank ❑ Privy ❑ Private Well ❑ Water Storage All construction shall be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80) 3. The wastewater code requires inspections during the installation. The engineer shall notify the Development Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather shall be either: a. Opened and Closed on the same day, or b. Covered, sealed, and heated to prevent freezing Special Provisions: A test hole is required prior to construction of the absorption field, in the location shown on the site plan, to confirm minimum separation to impermeable soil and seasonal high groundwater, as well as percolation rate. Construction may proceed at your own risk prior to 7-day groundwater monitoring. If results require a design change, construction shall stop pending approval of a change order. Please submit results with the inspection report (or change order, if required). Received By: F S -S Issued By: Date: Date: 4 MUNICIPALITY OF Development Services Department On -Site Water & Wastewater Section ON -SITE SEPTIC/WELL PERMIT APPLICATION Parcel I.D. 015-171-26 Property owner(s) Bryan Wita Day phone Mailing address PO Box 111762, Anchorage, AK 99511 Site address4721 E 11 5th Ave Legal description Greenland Block 6 Lot 11 Number of Bedrooms Engineering Firm Forge Engineering Building Permit Number Not Applicable RN APPLICATION IS FOR: APPLICATION IS AN: (Z all that apply) Absorption Field 0 Initial El Septic Tank Upgrade F] Holding Tank ❑ Renewal El Privy ❑ Well ❑ THIS APPLICATION INCLUDES A WAIVER REQUEST FOR: Permit/Rush Fees: # 6 q - Waiver Fees: Date of Payment: 3/ Z Z-5. Date of Payment: Permit No. 0 _5 P a5 106 9 Waiver No. Phone- 907-343-7904 Distance: March 25, 2025 MOA Development Services, On-Site Water & Wastewater Program 4700 Elmore Rd Anchorage, AK 99507 Subject: Greenland B6 L11 - 4721 E 115th Ave Septic system design Dear On-Site Services Engineer: The owner of the above lot needs to replace the existing lift station and septic bed on his lot. Due to small space and adjacent well locations, the only feasible option without resorting to advanced treatment is to rebuild the bed in place. The attached site plan identifies the location of the home , well, existing septic locations and information on adjacent properties. No conflicts exist between this proposed system and any other well or septic system, whether on this lot or adjacent lots. The ground surface on the lot slopes fairly uniformly toward the northwest at about 5-7%. The bed will be installed on slopes less than 10%, and there are no steeper slopes on site. Drainage arrows are shown on the site plan showing the grade and direction of flow. Stormwater drainage will not impact this septic system. While the bed is being reconstructed using the original specifications and test hole information, a new test hole has been specified to be dug prior to construction. Wells on this and adjacent lots are shown. The new system will be a minimum of 100’ from all wells and surface water, and more than 5’ away from the septic tank. Please refer to the attached test hole logs, plan and secton pages for the septic design. If this design is followed, there will be no adverse impacts to adjacent properties. Sincerely, Benjamin Schiller, PE Municipality of Anchorage On-site Water and Wastewater REVIEWED FOR CODE COMPLIANCE OSP251069, Curtis Townsend, 04/03/25 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x / / / / // Benjamin Schiller CE 12592REGISTEREDPROFESSION A L E N GINEER 1"=30' CO - CLEANOUT 2CO - DOUBLE CLEANOUT FCO - FOUNDATION CLEANOUT FS - FLOW SPLITTER VALVE MH - MANHOLE MT - MONITORING TUBE SV - SEPTIC VENT TH - TEST HOLE LEGEND TH#1 GREENLAND, BLOCK 6 LOT 11 FEET 0 30 60 4-BDRM HOME SEPTIC PLAN 4/2/25 E. 115th AVENUE GA R A G E EXISTING WELL EXISTING 1500 GAL CONC SEPTIC TANK EXISTING 500 GAL STEEL PUMP VAULT DECOMMISSION PER UPC OR REMOVE EXISTING ABSORPTION BED REBUILD IN PLACE INSTALL MT AT EVERY CORNER 1' FROM EDGE 18.0 20.0 50.0 10.0 LATERALS SPACED 5' OC 2.5' FROM ENDS EXTEND TO 1' FROM BED ENDS1.0 1.0 2.5 5.0 TH#2 PERC NEW 500 GAL EXPOY-COATED STEEL PUMP VAULT ENSURE 100' SEPARATION TO WELL ENSURE 100' SEPARATION TO ALL NEIGHBORING WELLS CONFIRMATION PERK TEST TO BE DONE PRIOR TO CONSTRUCTION 5% 5% 5% 5% Municipality of Anchorage On-site Water and Wastewater REVIEWED FOR CODE COMPLIANCE OSP251069, Curtis Townsend, 04/03/25 TYPICAL TRENCH SECTION (NO SCALE) NOTES: 1. GRADE AREA OVER TRENCH TO DRAIN AWAY 2. PROVIDE 3' OF COVER OVER TRENCHES AND 4' OVER SEPTIC TANK, OR 2' WITH 2" OF INSULATION 3. CHECK GROUNDWATER AT TIME OF CONSTRUCTION. IF LEVEL IS HIGHER THAN PREVIOUSLY OBSERVED, CALL ENGINEER IMMEDIATELY Benjamin Schiller CE 12592REGISTEREDPROFESSION A L E N GINEER DESIGN FACTORS:SYSTEM REQUIREMENTS: 600 GPD PEAK FLOW PERK RATE: 4 MIN/IN APPLICATION RATE: 0.8 GPD/SF (BED) SHALLOW BED ABSORPTION FIELD EXISTING 1500-GAL CONC SEPTIC TANK w/ NEW PUMP VAULT BOTTOM OF BED: 0.5' BELOW GRADE MAX FLOW LINE ELEVATION: AT GRADE PROVIDE MOA FILTER SAND AS NEEDED TO ENSURE TRANSMISSION TO RECEIVING SOILS 600 GPD / 0.8 GPD/SF = 750 SF BED REQUIRED (780 SF SPECIFIED) 4/2/25 PROVIDE ADDITIONAL FILL TO ACCOUNT FOR SETTLEMENT SEE PLAN FOR DIMENSIONS GREENLAND, BLOCK 6 LOT 11 6" 6" 2' TOPSOIL & SEED MAX SIDE SLOPES 3:1 1 1 4" PVC w/ 20 - 1 8" ORIFICES EVENLY SPACED @ 30" OC DRAINFIELD ROCK GEOTEXTILE FABRIC AND INSULATION MOA FILTER SAND AS NEEDED DOWN TO RECEIVING SOILS Municipality of Anchorage On-site Water and Wastewater REVIEWED FOR CODE COMPLIANCE OSP251069, Curtis Townsend, 04/03/25 — — — — -I- — — — — — — — — — — — — — — — — — — — — — WOODEN FENCE CHAIN-UNK FENCE O o F_' x —.x—.x—x—x�._ x ALLEY N - - — — — — S 89'53'20"E : 100' . Lot 11 8.8' 14.2' 18,000 s.f. WIRE FENCE SEPTIC PIPES----' GRAVEL rSEPTIC MANHOLE 1 _ 00 i 8.0' x 12.0' SHED WITH LEAN-TO Lot 10 0 o Lot 12 C) 0 - 0 O b p O 0 � O O Z / J N 2 .6' 3 40.6' W 1 STORY / * RESIDENCE N U WITH DAYLIGHT FW- BASEMENT 0 / 16.3' o a 16.0' a O OFCf- O f 24.3' 16.8' a. ASPHALT 00 PAVEMENT M N WELL 1 --- �— N 8 '53'20"W 100' — — — — - 0 M \ E. 115th AVENUE NOTES: GROUND LEVEL IMPROVEMENTS SHOWN ARE APPROXIMATE. DATE OF SURVEY: 13 MARCH 2O25 PLOT PLAN �_ AS BUILT X_ SCALE 1" 30' GRID SW 2636 Project No J25-064 Al Lang & Associates, inc,.O. urge, Alaska • Anchorage, Alaska 99521-0005 (907) 522-6476 oa�p F A Opp Professional Land Surveyors survey@langsurvey.com 0 I hereby certify that I have surveyed the following described property: LOT 11, BLOCK 6, GREENLAND SUBDIVISION (Plat No. P-268) Q Anchorage Recording District, g g Alaska, and that the improvements situated thereon are • • . .. • .. Q within the property lines and do not encroach onto the property adjacent thereto, that Q no improvements on the property lying adjacent thereto encroach on the surveyed Q • • • • • • • • • • • • • • • • • • • • • premises and that there are no roadways, transmission lines or other visible QO70�� AT AN LANG ; o easements on said property except cis ^ Indicated hereon. 7'h y--�:—=� F—� LS-9944. • ' JOD Dated this the 2 -- Da of L 2 at Anchorage, Alaska D��A dooms �44oIt is the responsibility of the owner to determine the existence of any easements, 0FfSSIONAL4pppoo covenants, or restrictions which do not appear on the recorded subdivision plat. State of Alaska AECC963 MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH AND HUMAN SERVICES Environmental Heallh Division ~9t f'- / 7 / - 825 "L" Street, Anchorage, Alaska 99502, Telephone 264-4720 ON-SITE SEWAGE DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT q7 a~ ~_ lib- .I~ / LEGAL DESCRIPTION DISTANCES ~~. SEPTIC ADSORPTION ______ TANK FIELD WELL WELL LOT LINE FOUNDATION I0 AS-BUILT DIAGRAM LShow Ioca0ou of well, sep0c system plopeHy hrles, Iounda0on, TANKS ~] SEPTIC ,~t~o,'? [] t4OLDING ~et I TYPE OF SYSTEM TRENCH ~ BED ~ ~ W. DRA~N ~ OTHER o,gJnw g¢sde + ~ U ~ O,~'- F~ 1~ FT WELLS ¢~ ~ PRIVATE ~ OTHER (Identify) FI[ FT REMARKS: ¢~ ~¢~J¢ %¢p~'c ~n~ ~un~ ~ be tn~ co~d,/~o'L Ore~co Inspecllons Porfo~ reed ~ .-, _ ~_ ' . '. ~,,~ ff/3o/~2 I .:- ~~ ~ cedify Ihat this inspection was performed according to / ,,,.~ ,~.,,,~-~ ,~. . INSP£OTIO..~ R£PO~T 3500 EAST TUDOR ROAD ¢ ADMINISTRATION (g07) 7B~8301 ~ PLBG. UNDGR. ~ ~ . ELEC, TEMP, ~ - OOTING -- -- ELEC. SERVICE-:~...~ PLBG, ROUGH FOUNDATION- '- [] ½OND BEAM [] ELEC, ROUGH -~_,~ GAS TEMP, :RAMING- ' [] ELEO. FINAL----'~,_ '~ GAS- INSULATION [] OTHER- MECHANICAL -- MECH. FINAL -- SHEETROCK ~ [] [] PLBG. FINAL STRUCT. FINAL - [] FIRE FINAL "' OTHER- [] ZONING--- [] OTHER- JO NONCOMPLIANCE oBSERVED [~ CORRECTIONS ESSENTIAL AS EXPLAINED BELOW NEXT iNSPECTION __E~ DO NOT CONCEAL UNTIL REiNSPECTED COMMENTS .,..,' / - :>','::.-'. ....... ,."."¢- ~: ,.4, "/; 1-'" ...... ~^T~ -- . :i ~ /,.,N~'PECTOR ;'f E WCiEN CORRECTIONS ARE MADE, PLEAS CALL FOR INSPECTION 84-002 (Rev 10/86) DO NoT REMOVE THIS NOTICE., MUNICIPALITY OF ANC-~o DEPt. OF HE RAGE ENVIRONM., ,~ ALTH '~ ~'~IAI. PROTEcTION JUL 2. 5.1989 RECEIVED F:'I::iI~::IBiii~L.It::;,'IL D ]: ff;'T'l::t :[ E)L.J'I" :1: C)lxl E!;Y~!i'I"E!:I"i 'T'C] }?,ii!}: :[ hlii!;"rf'fl~.l....l~i::O :[ lq AI:::I2C)I:~DAI,,ICI'~!: I~J :1: I"H !:i:l',li:..i :!: !,,ll!i:l!i:l::i ' 5~ :(:)[!i:Fi I [~.)1",1~ DI.IF!51 t:~Ei:C:l::il,'ll~'lliii:l',lDi!!l TI..I/..VI "l'Hl:ii: [:'il::il... ]: D I'::' :1: F:'li!i: I:;:'C)*L:~'T :!: OF: 'i I'fE: l"l~lq :i: F:'!::iI...D :i31ii: I'::'l::i'.li~:!!ii!i:}LIl::lli~: '1' t!ii:!!~i'l"l~i:l::) I::'1::,i :[ CIl:i 'l"!:l B6'112!<:1:::' ]: L..I... :( l".1(3 ,, NC)T I F::'¥ DIII'I!i!1 t:::'1::~ :1: CII::;,' "l'i::} f.q.I.. :t: l'".l!iiff:'t!!i:C:T' :1: C}I',I~!!i ,, TI-I ]: 51 I:::'liii:F;~l"l :[ T :1: (ii~ ]: !i!i:!BLl[ii:D I:::CII::~ Zl !31ii:D .... I::':i::)C]l"l !iiiil:N(:~l..t:~ F:Y.M"I:[I..Y I:]hlL'~"p ~l',l).:) li~:Xt:::'!:l::;:l:!i:liJ Cilq Lot 11. Block 6, Greenland S/D 4721 East 115th Septic System Upgrade Specificntions and Design Notes 1. The design of the soil absorption mound is based on a measured perc rate of 4 minutes per inch in the two foot thick SM stratum underlying the surface organic stratum. The mound is sized on the basis of 125 square feet per bedroom, which for this four bedroom residence requires (125) x (4) x (1.5) = 750 square ft. 2. The configuration of the mound shall be as shown on the plans except that minor modifications may be allowed or required by the engineer conducting the inspections. The shape of the bed may change slightly based on conditions encountered at the time of construction. 3. It is understood that all of the wells shown on the site plan are private wells serving single family residences. 4. AIl material specifications and construction practices shall be in conformance with M.O.A. regulations. 5. The existing seepage pits shall be pumped and properly abandoned by backfilling with clean soil. The septic tank shall be pumped to verify it's capacity, and the inlet and outlet exposed to enable the engineer to assess it's condition. 6. A new 500 gallon steel septic tank, equipped with an "Orenco" lift station assembly (or equal}, shall be installed after the e×is~ing septic tank on native soil outside the 100 foot radius from all wells. 7. The mound shall be constructed by carefully removing only the surface organic soil from the designated area, and a level surface created by placement of a leveling course of medium sand. 8. A total of one foot of approved sewer gravel shall be ptaced on top of the sand with the bottom of the manifold and the lateral distribution pipes located 8 inches above the bottom of the gravel. 9. The line pressurized line running from the lif~ station and the manifold shall be 2" dia schedule 40 PVC. Approximately 5'of bridging 4" angle iron shall be placed over the PVC as it exits the tank until it reaches undisturbed ground. Special care shall be taken to thoroughly compact the soil under the pipes leading into and out of the lift station. 10. The pressurized distribution laterals shall be 1.25" dia schedule 40 PVC with 3/16" dia holes drilled in the bottom side on 30" spacing. The hole spacing in adjacent rows shall be staggered. 11. The ends of each lateral shall be capped, and all pressurized pipe connections shall be glued. 12. 4" dia monitor tubes shall be installed as shown, with the perforated pipe extending to the bottom of the sewer gravel. Filter fabric shall be placed over the top of the sewer graYel. The unclassified soil cover shall have a minimum depth of 3 feet over the filter fabric, and the sides shall be sloped down at no steeper than 3:1. ' 13. Four inspection will be required during construction: (1) Initial stakeout, (2) after excavation is complete, but before placement of sand, (3) after the sand leveling course is placed, but before the gravel is placed, and (4) after the gravel is placed, the lift station is installed and all the piping i.s connected, but prior to placement of cover material. 14. The contractor shall be responsible for arranging for the necessary utility locates, electrical permits and inspections. The on, off and alarm float settings in the lift station shall be as specified by the lift station supplier. l.o7' £ I ~ ' "~, " '2 ' " ' 5" " ' ? ',u : ~. ,,,THEODORE .. LOT' I1~ r~l_OCI. C ~ ~RD~NI.,~ND 5/0 Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 625 "L' Street, Anchorage, Alaska 99502-0650 SOILS LOG -- PERCOLATION TEST '7:. H. PERFORMED FOR: d~r/L~ LEGAL DESCRIPTION: I 2 3 4 5 6 ? 8 9 10 11 12 13 14 15- 17 18 19 20 COMMENTS ~ THEODORE F. MOORE .' ~ .~?.. c~. ~ss, ...' ~.~ ~?'2~'. ....... "~,~g DATE PERFORMED: ~¢~ Township, Range, Section: WAS GROUND WATER ENCOUNTERED? SITE PLAN S IFYES, ATWHAT $~,,~/~ ~t I0' 0L DEPTH? p E Deplh to Waler Alter I 3' 0 ~/., I~onitoring? . late: Reading Date Gross Net Depth to Net Time Time (~.) Water Drop PERCOLATION RATE _ ~ (minutes/inch) PERC HOLE DIAMETER TEST RUN BETWEEN ._.~.,'7~" FTAND. 8. 8~.~"_FT ACCORDANCE WiTH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: 72-008 (Rev, 4/85) Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG -- PERCOLATION 'TEST PERFORMED FOR= '~'\"-14 ' ' ' '~ ,~ 4E GINEEI~S ~:,"~'~ ~ ..' DATE PERFORMED: ~/~ ~ LEGAL DESCRIPTION: ~.,.I/./ ~'.~ 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20- COMMENTS Township, Range, Section: -r'/~/,f~ ~ ~,t,~ 5'~,c ~,~ SLOPE SITE PLAN WAS GROUND WATER ENCOUNTERED? IF YES, AT WHAT SE ~t~'~ ~'' oL DEPTH? p E Depth Io Water Aller I/~? fit.(/,n ~.~, Monitoring? Date: Reading Date Gross Net Depth to Net Time Time Water Drop PERCOLATION RATE __ TEST RUN BETWEEN __ (minutes/inch) PERC HOLE DIAMETER FT AND _ FT ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES JN EFFECT ON THiS DATE. DATE: _ ~/~/~'~ 72-008 (Rev. 4/85) : ,..,, "::~: !'' .,/~,~ MUNICIPALITY OF ANCFIORAGE ,~'4.~ ~.' :' .-..i.. ,' [ eJ/~,-,-,\ Department of Hea th & Human Services · '~;~,~:,~.~:~:~'~-~...:CERTiFiCATE OF INSPECTION FOR HEALTH AUTHORITY APPROVAL OF. r~.~,. :.~?.?: ? · /'~-~:. ~L' ON-SITE SEWER AND WATER FAC LITY FOR SINGLE FAMILY DWELONG ,'. ¢~'~i:'l.'D'.:/#'~%- ~ ~' ~ '.. HAA ~ · ~~.'~ '; - -'-' '" .... ,1. GENERAL INFORMATION (Must ue completed prior to submittal) .... ...- (a).Legal Description (include lot, block, subdivision, section, township, range) Location (address or directions) (b) Property owner [~o¥ ~c F~T~DEI'J Mailing Address ¢-{7 (c) Lending Institution Mailing Address (d) Real Estate Company and Agent Telephone: (home) 3 ¥¢- ?.¢'¢ ¢_ Business Address Telephone (e) Mail the HAA to the following address: (or check here I~, if hold for pick up.) List contact person and day phone number below: 2. TYPE OF RESIDENCE Single-Family {~ Number of bedrooms 3. WATER SUPPLY Individual Well ¢ Community [] Public [] : NOte: If community well system, must have written confirmation from the State Department of Environmental "'C0'nseCvation attesting to th legality and status. ' ' 4. SEWAGE DISPOSAL On-site [~ Public [] Community [] Holding Tank [] ' ' Note: If ~0mmunity well system, must have written confirmation from the State Department of Environmental Conservation attesting to the legality and status, .. 72-025 (Rev. 7/88) Page 1 of 2 IPUOB!puoo IPeS s,Jeeu!Su3 ,.?S%1 ~_~& euoqdeleJ. 5¢;IA;~E5 qiY'~INH~.L ci0£L~'~;I ~J!=jjoe~PN · uo?,oedsuj s!q~ jo e),Pp eq~, uo ),oejje u! suop, PlnSeJ pup 'seouPu!pJo 'sepoo e),P),S pup IPd!o!unlAI lip q~,!~ eoue!ld~oo u! $! ~e~s,~s lesodsip Je~,P~e~,sP~ Jo/pup/~lddns ~elP~ e~!s-uo eq), 'uoBoedsu! pup uoBPSp, se^u! /~w ~oJJ pup seHJ eSPJoqouv jo ,~!lPd!o!unl/4 eq~, ~oJj peu!elqo uoBe~oju! sql uo pesPq 3PLI3 ,~J!Je^ Jeq~,Jnj I 'uleJeq pe~,Po!pu! eJn),on~ls Jo ed,~, pus s~ooJpeq jo Jeqwnu eq3 Joj e~,enbepP puP' leUOBOun~ 'sips s! ~e~s,~s IPsods!p JelP~e~,sP~ ~o/puP ,~lddns ~e~,P~ e),!s-uo eq~, ~,Pq~. s~oqs IP^o~ddv ,~lpoq~.nv q~lPeH s!q~ jo uoBeSBse^u!/~ ~Pq),,~pe^ I '~oleq u~oqs elPp uo!iPp!lPA eq~ Jo sP pup o),eJeq pex!jJP IPeS ,~ ,~q pe!j!),Jeo sV NoImvINBO4NI ON'~ VJ.'¢Q 'HOEIV3$ ::1']1-1 'S.i.$:4 l 'SNOI.LO:IdSNI ONIOl^O~ld I,Ni:IIJ 9NII:I3:~NION3 .cj ~ MUNICIPALITY OF ANCHORAGE (MOA) (~j~r,_~j/ Health Authority Approval (HAA) ~.~,.~,¢.jf// CHECKLIST- FEBRUARY 1984 MU N ici pA[':t.~E~ ANCHORAGE 343-4744 ENVIRONMENTAL SERVICES DtVIS[ON Legal Description: :',,~v,/I 4 1!)90 A. WELL DATA O [ t'~ r l Well Classification _ /'"r"t Well Log Present (Y/N) ~ Date Completed I?d '7 Total Depth c20' Casecl to ~- ?~' Depth of Grouting N,A Static Water Level ~ ' Casing Height Above Ground _ I~ c, Electrical Wiring in Conduit (Y/N) SEPARATION DISTANCES FROM WELL: To Septic/Holding Tank on Lot To Nearest Edge of Absorption Field on Lot To Nearest Public Sewer Line /'4, ,4, To Nearest Sewer Service Line on Lot If A, B, C, D.E.C. Approved (Y/N) Yield Z.~ ~o ~,P,~ N N, 4. Pump Set At ~ ,5'? / Sanitary Seal on Casing (Y/N) Y' Depression Around Wellhead (Y/N) ; On Adjoining Lots '~ f'oo ' ; On Adjoining Lots __:> (oo ' To Nearest Public Sewer Cleanout/Manhole ~ ~r Water Sample Collected by r='(~ ('/--~? T~c/~ ~',.. cr ; Date WaterSampleTestResults -~¢<f,x.~C~c/~'t'/k' - ca Comments _qJ-¢cxe-..f)/ ,/~,',~;~¢' o:(" cz,elf ~ /'~¢~,,m~/~ B. SEPTIC/HOLDING TANK DATA Date Installed 7/ (-7 Size Standpipes (Y/N) )/ Depression over Tank (Y/N) Pumping/Maintenance Contact on File (Y/N) Holding Tank High-Water Alarm (Y/N) 15-¢~9..~, No. of Compartments / Air-tight Caps (Y/N) Y Foundation Cleanout (Y/N) _Ix/. I"/ Date Last Pumped ¢'/tZ/~-¢ /~y /~o1~ -f-¢oolc¢,~ /"/, ~. ; for Temporary Holding Tank Permit (Y/N) SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK: To Water-Supply Well ~,~-' To Property Line To Water Main/Service Line To Stream, Pond, Lake or Major Drainage Course Comments ~'¢;(a To Building Foundation To Disposal Field 72-026 (Rev. 7/88) Fronl Page 1 of 2 C, ABSORPTION FIELD DATA Soils Rating in Absorption Strata Date Installed ~' / ..~ ~" //~ Width of Field /,¢t ' Square Feet of Absortion Area Depression over Field (Y/N) Results of Last Adequacy Test ~',/'¢,:~'¢'~ Type of System Design Length of Field Depth of Field Gravel Bed Thickness Statndpipes Present (Y/N) Date of Last Adequacy Test SEPARATION DISTANCE FROM ABSORPTION FIELD: To Water-Supply Well I Oo' To Property Line IO ' To Building Foundation ~'O' To Existing or Abandoned System on Lot ~ i¢' ~ ~f,~^cfo,~.X ¢-.,¢-,d¢~X ?',t' ; On Adjoining Lots ~:> ~' To Water Main/Service Line ;~ ~,*f To Stream, Pond, Lake, or Major Drainage Course To Driveway, Parking Area, or Vehicle Storage Area Comments To Cutback (if present) ~ ¢oo ' D. LIFT STATION Date Installed Size in Gallons "Pump On" Level at High Water Alarm Level at Tested for /~,~. Meets MOA Electrical Codes Comments Dimensions Manhole/Access (Y/N) "Pump Off" Level at Vent (Y/N) Cor~ (~ :TI,5'" Pumping Cycles during Adequacy Test. **Check Permitted Bedroom Rating Against HAA Request** I certify that I have checked, verified, or conformed to all MOA and HAA g~.j~¢J,J~.e.~in effect on inspection. Signed ,~-~~~ ~. ~ Date ~ /[I / ¢0 MOANo, ~¢ -o[~ O ~'~ Receipt No, r~ /~Z,5~'- ~ Receipt No. e.te of -¢-/¢ W.ive ee: Amount: $ /~ '~ Date of Payment 72-026 (Rev. 7/88) Back Page 2 of 2 the date of this Engineer's Seal GREATER ANCHORAGE AREA BOROUGH Department of Environmental Quality 3330 %" Street, Anchorage, Alaska 99503 274-4561 Date:Received ~.~2.~/- Time of Inspection \0~ O0 ~'~e' of Inspection 1. Approval requested by: Mailing Address: 2. Property Owner: REQUEST FOR APPROVAL OF INDIVIDUAL SEWER & WATER FACILITIES Phone: 4. 5. 6. e Mailing Address: Legal Description: ~ ~ .. Type of facility to be inspected ~ No. of bedrooms / Wel 1 Data: A. Type.~_J_~¢~ B. Depth ?0/ C. Construction D. Bacterial Analysis Sewage Disposal System: (,..4~ ~(--~/--~c.~/~_~ ~ A. Installed~~¢i /~(~ B. Installer ¢. Septic Tank: 1. Size 2. Manufacturer D. Seepage Pit: 1. Absorption Area 2. E. Disposal Field: Total length of lines Distances: ~)~' ~'~'?"~'::].1 A. Well to: Septic tank j. ' 0.?¢ , Absorption area Nearest lot line /P//~- , Other contamination B. Foundation to septic tan~-'-" ?(~' i , Absorption area C. Absorption area to nearest lot line Material _, Sewer Lines FF)- (1~4 (117Z1~ ~ Page 2 of two pages - F Illegal Description lest for Approval of Individual ~wer & Water Facilities Approved r.i~ .,,.: ,, ~'. :/]?+ /.,,~.,,,.>,-Disapproved Date Approval ..Valid for one year from date signed Greater Anchorage Area Borough, Department of Environmental Quality DIAGRAM OF SYSTEM Ap?to:, :~o1~ t:,: Zo/ ['certify that the ~nformot~on contained ~n this ~equest for app~ow] to be a t~ue and accurate representation of the subject sewer and water facilities and these facilities are operating satisfactorily~ SIGNED (::~:A%Q.~ Date GREATER ANCHORAGE AREA BOROUGH Department of Environmental Quality 3330 "C" St., Anchorage, Alaska 99503 - 274-4561 REQUEST FOR APPROVAL OF INDIVIDUAL SEWER & WATER FACILITIES 1. Type of Inspection: CMRO VA FHA 2. Property Owner: )P,~$1~'~ <i. LIc)~:2tL~' Mai-ling Address: ~/.?~t ~>~ //'~}~ A}/~'A._Day Phone 3. Name of Buyer: co N v %- Mailing Address: 4. Name of Lending Institution: Mailing Address: 5. Name of Realtor or Agent: Mailing Address: D~.,y Phone Phone Phone o Legal Description: Location: ' .... 7. Type of Facility to be inspected: ~,"7,~ ~ No. Bdrms. 8. ~ater Supply Type of Supply: Public Utility Individual If Individual, number of dwellings presently served ~f Zndividual, depth of well ':~:' 9. Sewage Disposal System Type of System: Public Utility If Individual, date of installation Individual (on-site) EQ-037 (]/74) AFFIDAVIT STATE OF ALASKA ) THIRD JUDICIAL DISTRICT) ss , being first duly sworn on oath, deposes and says: 1. That I am employed by Jack Benny's and Anchorage Cesspool Pumping Service, Star Route A, Box 144, Anchorage, Alaska 99502. 2. That on the 23rd day of July, 1975, Les ~,~C , a driver for this company, pumped the ceptic tank at the residence of Carl B. Elsenbast, Lot , Block , Greenland Subdivision, and it is my information that on that date the meter indicated that he pumped 1,500 gallons from 'the 'tank. 3. That Les ~--~ is currently honeymooning out of state; however, my information is based on the attached statement completed by him on the day of pumping. FURTHER your affiant saith not. DATED at Anchorage, Alaska, this ~Z~ day of August, 1975. Jack Benny's~ 6nd Anchorage Cesspool Pumping Service SUBSCRIBED AND SWORN to before me this August, 1975. day of Notary Public in and for the State of Alaska~ My Con~ission Expires: