HomeMy WebLinkAboutPATRICIA BLK 2 LT 20Patr'icia Block 2 Lot 2:0 #012-464-01 Municipality of Anchorage Development Services Department ,~'~ Building Safety Division On-Site Water and Wastewater Program, 4700 Elmore Road ~'~ P.O. Box 196650 Anchorage, AK 99507 Page of www.ci.anchorage.ak.us (907) 343-7904 ON-SITE WASTEWATER DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT Permit Number: SW090133 PID Number: 012-464-01 Name: Ali Family Trust Wastewater System: [] New [] Upgrade Address: 3705 Arctic Blvd., Ste. 1334 Anchorage, AK 99503 ABSORPTION FIELD Phone: Number of Bedrooms: 727-2912 3 [] Deep Trench if} Shallow Trench [] Bed [] Mound [] Other: Soil Rating: Total Depth from original grade: LEGAL DESCRIPTION 1.2 GPD/Ft2 3 Ft. Block: 2 Lot: 20 Subdivision: Depth to pipe bottom from odginal grade: Gravel depth beneath pipe: Patricia 1 Ft. 2 Ft, Township: Range: Section: Fill added above original grade: Gravel Length: 1-2 Ft. 53 Ft. Well: [] New [] Upgrade Gravelwidth: 5 Ft. Numberoflines:l I Distance between Ii_ .... Ft. Classification (Private, A, B, C): Total Depth: Cased to: Total absorption area: Pipe Material: AWWU Water System Ft. Ft. 378.5 Ft2 ASTM D3034 PVC Ddller: Date Drilled: Static Water Level: Installer: Date Installed: Ft. Glacier Excavating 10/15-20/09 Yield: GPM Pump Set at: Casing Height Above Ground: Ft. Ft. TANK SEPARATION DISTANCES [] Septic [] Holding [] S.T.E.P. [] Other: T~ To Septic Absorption Lift Holding )ublic/Private Manufacturer: Capacity: From~ Tank Field Station Tank Sewer Line Anchorage Tank 1,250 GaL Material: Number of Compartments: we, N/A N/A N/A N/A N/A Steel Two (2) surface water >100' >100' >100' N/A ~ / LIFT STATION Size: Manufacturer: Lot Line >5' 2 .... >5' N/A 1250 STEP Gal, Anchorage Tank/Orenco "Pump on" level at: "Pump off" level at: in. High water alarm at: Foundation >5' >10' >5' N/A 42 in. 42 44 in, Pump Make & Model Electrical Inspections performed by: Curtain Drain None Noted OS1-P2005-11 Municipality of Anchorage Remarks: ***See Lot Line Waiver. BENCH MARK Location and Description: Absorption Trenches Covered with 2" Direct Bury Insulation. Lower Level Concrete Slab. Assumed Elevation: Ft. Inspections performed by: T. Kimbrough Dates: 1st 10/15/2009 2nd 10/20/2009 ~' (-/2.' ~ · ~'~'-~ Development Services Department Approval Conditional Approval Date: Reviewed and approved ~' Date: (Re,. 04/06) OLYMPIC STREET ~7:~-~'.. .... · '. :: ..'..'. ;. :- ~ ~ ...' S O0'02'O0"E 75.00' . :'.. , :. :- I I ' '.' '- ' I ii ...- · I ~ ~ ~ ,.: ... I ~ : I NN I ~ : ~ ~ E ~ I ~ · o I o o~ ~ ~ =, ~0 z ~ , ~ ........ ~ ~ al!S OiDU~o I I I ~ x I 30.0' * ' = ' X ~ ,O0'SL ~.00~0.00 N c ~ - ~ ~c o o ~ ~ ~ ~c ~~~ = o~ E ~3~ ~l~ ~ ~ ~ ._ .. : ._ ~ ' ' ,o 0 Permit Number: SW090133 Municipality of Anchorage DEVEOPMENT SERVICES DEPARTMENT 4700 Elmore Road Anchorage, AK. 99519-6655 - 343-7904 On-Site Wastewater Disposal System or Well Inspection Report Page 3 of 3 PID No. 012-464-01 STEP Tank .0_/ ~ 100.7 3:_ ;~ 100.4 / 98.5 / Finished Grade // / ........... Odginal Grade / Geotextile Fabdc & 2" Insulation 97.6 Drainfield Rock 95.5 ---' 95.5 J 88.5 53' (Trench Length) Groundwater @ 91.4 97.6 30 - 5/16" Diameter Holes @ 1.75' PROFI.LE AS-BUILT No Scale Inspection Report Municipality ,of Aritho ~,, Building Safety Di ision 4700 E!m, ore Road ,V 1NFO & HI~P [907) 3'43-82t 1 INSPECTION: VOICE (907) 343-8~i?0i, FAX (907)249-7777' www.muni.org Name Bill " Company Brickwell, Inc. ~ _~? ,..~. ,-- ~,llj~ · 440-9351 Address 10012 OLYMPIC ~ ' Sul~divlslon PATRICIA t LOT 20 B~ 2 TR n/a Work Deecrtptlor~ 1840 sqft living area, 484iSqft gararge Insp. performed/prepaid 24 / 23 Permit Technician STULLER, GRETCHE~ J. Comments or Directions Early AM Please... Call to h~eet- Thanks Inspection Type Electrical:Final Electrical ~ !. Comments (for inspector use only) Inspector Date MUNICIPALIT~ OF ANCHORAGE Development Services Department On-Site Water & Wastewater Program 4700 South Bragaw Street P.O. Box 196650, Anchorage, AK 99519-6650 (9O7) 343-7904 ON-SITE WASTEWATER DISPOSAL SYSTEM PERMIT Initial Date Issued: Jul 31, 2009 Expiration Date: Jul 31, 2010 Permit Number: SW090133 Legal Description: PATRIClA SUBDIVISION BLOCK 2 LOT 20 Design Engineer: 0014 ANDERSON ENGINEERING Owner Name: ALI FAMILY TRUST Owner Address: 3705 ARCTIC BLVD #1334 ANCHORAGE, AK 99503- Parcel ID: 012-464-01 Site Address: NHN GEBHART DRIVE Lot Size: 7020 SQ. FT. Total Bedrooms: 3 Permit Bedrooms: 3 This permit is for the construction of: [] Disposal Field [] Septic Tank [] Holding Tank [] Privy [] Private Well [] Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations ( 18AAC72 ) and Drinking Water Regulations ( 18AAC80 ). 3. The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 ( 24 hours ). ( Not required for a Water Supply Permit only ). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must be either: A. Open and closed on the same day. B. Covered, sealed, and heated to prevent freezing. 5. The following special provisions. A. Waiver WR090045 allows a 2' drainfield to south lot line separation distance. B.THE ENTIRE SUBSURFACE DISPOSAL FIELD AND ALTERNATE IS NOT WITHIN A 30 FOOT RADIUS OF A PERCOLATION TEST. THE ENGINEER NEEDS TO DO AN ADDITIONAL PERCOLATION TEST PRIOR TO THE CONSTRUCTION OF THE SEPTIC FIELD. PLEASE SUBMIT STAMPED AND SIGNED RESULTS WITH THE AS-BUILT INSPECTION REPORT. IF THE RESULTS REQUIRE A DESIGN CHANGE, CONSTRUCTION OF THE SYSTEM WILL STOP PENDING ON-SITE REVIEW AND APPROVAL. Date: Municipality of Anchorage ~650 ® 4~ Anchoraqe, Alaska 99519-6650 · (907) 343-7904 · Fax {907) 343-7997 ~" .http:l/www.mun orqlOnslte Department Development Services Department On-Site Water and Wastewater Proqram **** VARIANCE/WAIVER REVIEW **** WPJh .WR090045 HA//: PID//: 012-464-01 Legal Description: .Patrlcla B2 L20 Engineer. Anderson Enqineerinq Permit//: 090133 Applicant: Ali Fatally Trust Your request for a waiver of the required 10 feet horizontal separation from the absorption field to the property line has been approved. The approved separation distance is 2 feet from the south property line. This waiver approval applies to the existing absorption field to property line separation only. Any future upgrade to the on-site wastewater disposal system will require all separation distances be met or another approval from this department. Waiver Is Granted: X Waiver is not Granted: Date: 7/31/2009 Approved by .~/J.~g~-~3,fr]~ ( ~/Name of Reviewer Rec//: ,024449 Amount: $200.00 Date Paid: ?~13/09 **** VARIANCE/WAIVER REVIEW **** Municipality of Anchorage Development Services Department Building Safety Division On-Site Water and Wastewater Program 4700 Bragaw Street P.O. Box 196650 Anchorage, Alaska 99519-6650 www.muni.org/onsite (907) 343-7904 ON-SITE SEWER/VVELL PERMIT APPLICATION FOR A SINGLE FAMILY DWELLING Parcel I.D. 012-464-01 Properbj owner(s) Ali Family Trust Mailing address 3705 Arctic Boulevard No. 1334 Anchorage, AK Site address GebhartDrive Anchorage, AK .Day phone 727-2912 .Zip Code 99503 .Zip Code 99516 Legal description (Sub'd,, Block & Lot) Lot 20, Block 2, Patricia Subdivision Legal description (Township, Range & Section) Lot Size 7,020 .Sq. Ft. Number of Bedrooms Three (3) THIS APPLICATION IS FOR (~;~ all that apply): THIS APPLICATION IS AN: Absorption Field [] Initial [] Septic Tank [] Upgrade [] Holding Tank [] Renewal [] Privy [] Private Well [] Water Storage [] I certify that the above information is correct. I further certify that this application is being made for a Single Family Dwelling and is in accordance with applicable Municipal Codes. (Signature of property owner or authorized agent) Permit/Rush Fees: "~ Date of Payment: Receipt Number: (Rev. 11/05) Waiver Fees: Date of Payment: Receipt Number;. ~,00 ANDERSON ENGINEERING P.O. BOX 240773 ANCHORAGE, AK 99524 522-7773 677-7766 (FAX) July 13, 2009 Municipality of Anchorage Development Services Department On-Site Water and Wastewater Program 4700 South Bragaw Street Anchorage, AK 99519-6650 Su~e~: Lot 20, Block 2, Patricia Subdivision Septic System Design and Permit Application Impacts to Adjacent Properties Dear Onsite Services Engineer: The owner of Lot 20, Block 2, Patricia Subdivision intends to construct a new three- bedroom home on the lot. We are therefore requesting a permit be issued for the construction of a septic system to accommodate the home. The lot and subdivision is served by the AWWU water system. The attached Site Plan and backup documentation identify the location and configuration of the proposed septic system along with the alternate site. No conflicts exist between wells or septic systems in the area. The lot is very small with only 7,020 square feet of surface area. The absorption trench must be placed within 2' of the south property line. A lot line waiver request accompanies this permit application. Drainage arrows are shown on the site plan showing the grade and direction of flow on the lot. The drainage pattern will not be changed as a result of this project. The test holes placed on the lot in the area of the absorption trench and alternate site indicated sand with gravel and silt (SM/SP). The percolation rate of the soil was determined to be between 1 and 5 minutes per inch. No groundwater was found during the placement of the test holes but was noted at 7' during the monitoring period. An application rate of 1.2 gallons per day per square foot was used in the design of the absorption system. We are proposing to place a new 1,250-gallon STEP tank and a 70' ;pmh by 5' wide by 2' effective depth absorption trench to treat and dispose of the effluent generated in the house. The elevation of the distribution line in the absorption trench will be 1' below the surface and the total depth will be 3'. A minimum of 3' of fill or 2" of insulation and 2' of fill will be placed over the absorption trenches and 4' over the STEP tank. The ground surface on the lot in the area of the absorption trenches is fiat with little or Lot 20, Block 2, Patricia Subdivision July 13, 2009 Page Two no slope in any direction. The new trench will be constructed parallel with the contours of the surface as much as possible in conformance with Municipal requirements. The new septic system will be constructed a minimum of 100' from any surface water and 10' from the proposed and existing water services in the area. If the system is constructed in accordance with our design the following statements apply: The system, if constructed as designed, will have no adverse impact on the wells in the area or those to be constructed in the future. The system, if constructed as designed, will have no adverse impact on existing septic systems in the area or those to be constructed in the future. The system, if constructed as designed, will have no adverse impact on reserve space, either surface or subsurface, on any lots located in the area. The system, if constructed as designed, will have no adverse impact on drainage patterns in the area. The current drainage pattern will be maintained. Sincerely, Michael E. Anderson, P.E. Attachments ANDERSON ENGINEERING P.O. BOX 240773 ANCHORAGE, AK 99524 522-7773 677-7766 (FAX) July 13, 2009 Municipality of Anchorage Development Services Department On-Site Water and Wastewater Program P.O. Box 196650 Anchorage, AK 99519-6650 Subject: Lot 20, Block 2, Patricia Subdivision Separation Distance Waiver Absorption Trench to Lot Line Dear On Site Services Engineer: Lot 20, Block 2, Patricia Subdivision has a surface area of only 7,020 square feet which greatly limits the space available for a septic system. It is surrounded by subdivisions currently served by AWWU water and sewer systems. It is also surrounded by 60' and 93' rights of way on two sides. We are therefore requesting a waiver allowing the absorption system to be placed within 2' of the south lot line. We are also requesting the alternate site be placed within 2' of the south property line. Soils at this location are well to poorly graded sand with silt which is normally effective in the absorption and treatment of septic effluent. Placement of the absorption trench and alternate site within 2' of the south lot line will not adversely affect neighboring lots. All adjacent lots are served by the AWWU water system. We hereby recommend a lot line waiver be issued allowing placement of the absorption systems within 2' of the south lot line. Sincerely, Michael E. Anderson, P.E. o00'0~ OLYMPIC STREET n I--J OLYMPIC STREET il N O0'02'O0"W 75.00' LOT 20, BLOCK 2, PATRICIA SUBDIVISION DESIGN FACTORS: SYSTEM REQUIREMENTS: Three Bedroom Home 5' Wide Pressurized Trench System Perc. Rate: 1-5 Min./Inch 1,250 Gallon STEP Tank Application Rate: 1.2 GPD/SF 2' Drainfield Rock 3 Bedrooms X 150 GPD/1.2 GPD/SF (Application Rate) = 375 SF Absorption Area 375 SF/5*.7(Red. Factor) = 52.5 LF Trench Length THEREFORE: Construct a 53' Long x 5' Wide x 2' Effective Depth Absorption Trench at the Location Shown. Flow Line Elevation in Trench to be 1' Below Odginal Ground Surface. Total Depth to be 3' Below Existing Ground. Provide 4' Cover Over Septic Tank and 3' Cover Over Absorption Trenches. Maintain 10' Separation from Water Services in the Area. ckfill Geotextile -- Fabdc 1" Perforated PVC (Holes Down) 3/16" Dia. Holes @ 1.75' O.C. Drainfield Rock TYPICAL 5' WIDE TRENCH SECTION (NO SC^LE) ,~;.~..~...~., NOTE: Grade Area Over Trench to Dram Away. ~ 49~ Minimum 6' Separation From Bedrock. ~...~...........~...~....[....~ Minimum 4' Separation From Gmund~ter. Minimum 10' Separation From Water Sewices in ~e Area. ~'~ Minimum 100' Separation From Su,ace Water or Streams' ~;, No .¸ 5- 6- 7- 11- 12- 13- 14- 15- 16- 17- 18- 19- Performed For:. Municipality of Anchorage Development Services Department Rullding Safety Division On-Site Water and V~stewater Program 4700 South Bragaw St. P.O. Box 19~650 Anchorage, AK 995t9-6650 www.munLo*'g/onslte (907) 343-7904 Soils Log - Percolation Test Gazmend Arapi Date Perfon~ed: 4/30/05 Legal Description: Patrida S/D. BIk 2, Lot 20 lO, O 1 '~C5 Slope IIIII I Township, Range, Section: Site Plan WAS GROUND WA~R ENCOUNTERED? Yes $ L IFYE$,ATIM-Ut, TDEPI'H?·7 O Depfl~ to Water After p Reading Date Gross Time Net Time Depth to Water Net Drop 1 - 2 4130/05 10:4s- 10:5e 10 s- 0 6 3-4 10:59-11:06 10 6-0 6 5-6 11:07-11:14 7 6-0 6 7-8 11:15-11:23 8 6-0 6 9 - 10 11:24 - 11:34 10 6 - 0 6 11-12 11:35- 11:44 9 6 - 0 6 13 - 14 11:45- 11:53 8 6-0 6 PERCOLATION RA1E 1.5 n~.r. ch) PERC HOLE DIAMETER e 'n[STRUNBE'~/~EEN 2 FT AN{) 2.5 FT COMMENTS, SP ~an~l PERFORMED IN ACCORDANCE WITH ALI. STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: ON-SITE WASTEWATER DISPOSAL SYSTEM CONSTRUCTION AND MATERIAL SPECIFICATIONS SUBJECT: LOT 20, BLOCK 2, PATRICIA SUBDIVISION GENERAL: The scope of this project includes the furnishing and installing of a new 1,250 gallon STEP Tank at the location shown on the site plan. Work also includes the construction of a new 53' long by 5' wide by 2' effective depth absorption trench also shown on the Site Plan. A 1.25" PVC line must be placed between the lift station and the new absorption trench. The distribution pipe for the trench will be placed at 1' below the ground surface. The total depth of the trench will be 3'. A minimum of 3' of cover must be placed atop the trench. A minimum of 4' of cover is required over the Septic Tank and Lift Station with 3' of cover over the absorption trench. In lieu of cover 2" of direct bury insulation and 2' of cover may be placed. Construction shall be in accordance with the approved site plan, design drawings, Municipal Permit with any special provisions or conditions, and all applicable State and Municipal Wastewater Disposal Regulations. o The Contractor shall be responsible for obtaining all underground utility locates and for the layout of the septic system and verification of the location of all lot lines. Contractor is also responsible to verify the separation distance from the well on this and adjacent lots. Unless specifically agreed otherwise, the contractor shall be responsible for final grading areas subsequently depressed from soil settling. Property owner shall be responsible for revegetation of affected areas unless specifically agreed otherwise. Contractors installing wastewater disposal systems must be certified by the Development Services Department Building Safety Division On- Site Water and Wastewater Program for system installations. Owners installing their own systems must receive prior approval from the On- Site Water and Wastewater Program before beginning system installation. SEPTIC TANK/LIFT STATION INSTALLATION 1. The 1,250-cjallon STEP Tank must be obtained from a Municipally approved septic tank manufacturer. 2. The septic tank shall be sufficiently bedded to prevent settling or shifting of the tank. Lot 20, Block 2, Patricia Subdivision July 13, 2009 Page 2 of 3 3. All standpipes on the septic tank shall extend a minimum of 12 inches above final grade. 4. Tanks installed without 4' of cover shall have a minimum of 2" of direct burial insulation. A foundation cleanout shall be installed one to four feet from the building foundation. Two cleanouts are required between the tank and the drain field. 6. Final grading over the tank shall be such that a positive slope exists away from the septic tank. DRAIN FIELD CONSTRUCTION: 1. The drain field shall be constructed to the dimensions shown on the design. The bottom of the bed shall be within 2" of level. Distribution piping must be placed level with perforations down atop a level bed of drain field rock. Rock should then be placed over the pipe to provide a minimum of 2" of cover. 3. A silt barrier or geotextile fabric must be placed between the drain field rock and the natural soil backfill. Monitor tubes must be 4" in diameter and installed at the locations shown on the design. The portion below the distribution line must be perforated. Contractor shall verify the septic tank and drain field are a minimum 100' away from any private water wells in the area, 150' from a Class "C" Well or 200' from any community well. Direct bury insulation must be placed over the distribution system if less than 3' of backfill depth is available. Finish grade over the trench must be mounded to prevent settlement or depressions. 7. Grade area surrounding the absorption trenches to drain away. o A minimum 2' of accepting soil is required below the drain field rock for a 5' wide trench. All pockets of unacceptable materials must be removed and replaced. MATERIAL SPECIFICATIONS: 1. The lift station must be constructed by a municipally approved septic tank manufacturer. An Orenco 20 OSI 05 HHF-5 pump is recommended. Lot 20, Block 2, Patricia Subdivision July 13, 2009 Page 3 of 3 The following pipe materials are approved for use in septic system installations in the Municipality of Anchorage: Cast Iron (perforated and solid), ASTM D3034 or P.V.C. (perforated and solid), ASTM F810 or H.D.P.E. (perforated, but not solid) and ASTM D2662 or A.B.S. (perforated and solid). Insulation shall be at least 2" thick extruded direct burial polystyrene (Dow Chemical Co. Styrofoam HI or equal). Septic tank inlets and outlets shall be fitted with watertight couplings (Caulder, Fernco, or equal). 5. A permeable geotextile fabric (Typar, Mirafi or equal) must be installed between the final drain rock layer and the native soil layer. 6. All drain rock shall be .5" to 2.5" in diameter with less than 3% passing the #200 sieve. FILTER SAND SPECIFICATION: 1. Material for Filter Sand must be classified as a masonry sand and meet the following gradation: 50% or More Passing the No. 4 Sieve 2% or Less Passing the No. 100 Sieve 1% or Less Passing the No. 200 Sieve INSPECTIONS: Municipal Ordinance requires a minimum of two inspections. These inspections must be conducted under the supervision of a professional engineer registered in the State of Alaska. The first inspection must be conducted after the excavation of trenches, beds or pits and before the installation of any gravel. A septic tank may be set in place, but may not be backfilled. The second inspection must be conducted after the placement of the geotextile fabric, gravel, distribution piping, standpipes, cleanouts and insulation. No backfill should be in place at the time of inspection. Contractor shall provide a copy of all field survey layout and construction notes for use in preparing the certified as-built of the completed system. MUNICIPALITY' OF ANCHORAGE Development Sen/ices Departmont On. Site Water & Wastewater Program 4700 South Bragaw Street P.O. Box 196650, Anchorage, AK 99519-6650 (907) 343-7904 ON-SITE WASTEWATER DISPOSAL SYSTEM PERMIT Renewal Date Issued: Oct 06, 2008 Expiration Date: Oct 06, 2009 Permit Number: SW080221 Legal Description: PATRICIA BLOCK 2 LOTS 1 & 20 Design Engineer: 0014 ANDERSON ENGINEERING Owner Name: ALI FAMILY TRUST Owner Address: 3705 ARCTIC BLVD STE 1334 ANCHORAGE, AK 99503- Parcel ID: 012-464-20 Site Address: 10031 GEBHARDT DRIVE Lot Size: 0 SQ. FT. Total Bedrooms: 4 Permit Bedrooms: 4 This permit is for the construction of: [] Disposal Field [] Septic Tank [] Holding Tank [] Privy [] Private Well [] Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal Cede Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations ( 18AAC72 ) and Drinking Water Regulations ( 18AAC80 ). 3. The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 ( 24 hours ). ( Not required for a Water Supply Permit only ). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must be either: A. Open and dosed on the same day. B. Covered, sealed, and heated to prevent freezing. 5. The following special provisions. THE MOA L~- ~ I ER OF NON-OBJECTION TO ENCROACHMENT MUST BE SUBMITTED PRIOR TO THE ASBUILT INSPECTION REPORT BEING APPROVED. THE UPPER 6" OF THE MOUND SYSTEM IS TO HAVE TOP SOIL AND BE VEGETATED SUFFICIENTLY TO PREVENT EROSION. Received By;. ~ Issued By: ~ Municipality of Anchorage Development Services Department Building Safety Division On-Site Water and Wastewater Program 4700 Bragaw Street P.O. Box 196650 Anchorage, Alaska 99519-6650 www.muni.orglonsite (907) 343-7904 ON-SITE SEWER/VVELL PERMIT APPLICATION FOR A SINGLE FAMILY DWELLING Parcel I.D. 012-464-20 Property owner(s).Ni Family Trust Mailing address 3705 Arctic Boulevard, Suite 1334 Anchorage, AK Site address 10031 Gebhardt Drive Anchorage, AK Day phone ,727-2912 ,Zip Code .99503 Zip Code 99516 Legal description (Sub'd., Block & Lot) Patricta Subdivision, Block 2, Lots 1 & 20 Legal description (Township, Range & Section) Lot Size 14,040 (Comb~ne~) Sq. Ft. Number of Bedrooms Four (4) THIS APPLICATION IS FOR ([] all that apply): Absorption Field [] Septic Tank [] Holding Tank [] privy I--I Private Well [] Water Storage [] THIS APPLICATION IS AN: Initial [] Upgrade [] Renewal [] I certify that the above information is correct. I further certify that this application is being made for a Single Family Dwelling and is in accordance with applicable Municipal Codes. (Signature of property owner or authorized agent) Permit/Rush Fees: t~60 Date of Payment: Receipt Number. (~/.~ ~- I (Rev. 11 ~5) Waiver Fees: Date of Payment: Receipt Number. October 3, 2008 Municipality of Anchorage Development Services Department On-Site Water and Wastewater Program 4700 South Bragaw Street Anchorage, AK 99519-6650 Su~ect: Lots 1 and 20, Block 2, Patricia Subdivision Septic System Design and Permit Application Impacts to Adjacent Properties Dear Onsite Services Engineer: The owner of Lots I and 20, Block 2, Patricia Subdivision intends to COnstruct a new four-bedroom home on the lot. The septic system was originally designed by Watkins Engineering in May of 2006 with a permit issued at the time. The permit has since expired. We are therefore requesting a new permit be issued for the construction of a new septic system to accommodate the home. The subdivision is served by the AWWU water system with sewer service also provided on lots to the north. The attached Site Plan and backup documentation completed by Watkins Engineering identify the location and configuration of the proposed septic system along with the alternate site. No existing wells or septic systems are closer than 100' from the proposed septic system. The majority of the lots surrounding the lot to the south and the east are currently vacant. The lot is fairly fiat in all directions. The drainage pattern will not be changed as a result of this project. The test holes placed on the lot in the area of the absorption bed and alternate site indicated clean sand (SM/SP) material with some silt at the 8' level. The percolation rate of the soil was determined to be 1.5 minutes per inch. Groundwater was found during the placement of the test hole at 7' below the surface and remained at that level during the monitoring period. An application rate of .8 gallons per day per square foot was used in the design of the absorption system. We reviewed the design completed by Watkins Engineering and agree the most effective system for the lot is a 15' wide by 50' long shallow bed system constructed in an east-west direction. A 1,500 gallon STEP tank will be required to collect the sewage from the house and transport the effluent to the absorption bed. The elevation of the distribution line in the absorption bed will be 2' below the surface and the total depth will be 2.5'. A minimum of 3' of fill or 2' of insulation and 2' of fill will be placed over the absorption bed and 4' over the STEP tank. Lot 20, Block 2, Patricia Subdivision October 3, 2008 Page Two The STEP tank will be placed on Lot I along with the house, The absorption bed will be on Lot 20. Letters of non objection and encroachment permits from the utility companies have been obtained and previously submitted since the distribution line from the tank will cross the lot line and utility easements. The ground surface on the lot in the area of the absorption trench is nearly flat' with a slight bias to the south. The new bed will be constructed parallel with the slope as much as possible in conformance with Municipal requirements. The new septic system will be constructed a minimum of 100' from all wells and any surface water and 10' from the proposed and existing water services in the area. If the system is constructed in accordance with our design the following statements apply: The system, if constructed as designed, will have no adverse impact on the wells in the area or those to be constructed in the future. The system, if constructed as designed, will have no adverse impact on existing septic systems in the area or those to be constructed in the future. The system, if constructed as designed, will have no adverse impact on reserve space, either surface or subsurface, on any lots located in the area. The system, if constructed as designed, will have no adverse impact on drainage patterns in the area. The currant drainage pattern will be maintained. Sincerely, Michael E. Anderson, P.E. Attachments GEBHARDT DRIVE 75.00 · ~-:~° ~Id l I I I '1 I I I I OLYMPIC STREET h~c Performed For:. Legal Description: 5- 6- 7- 8- 11- 12- 13- 14- 15- 16- 17- 18- 19- 20- ~,0 I0, O Municipality of Anchorage Development Services Department Builcling Safety Division On~ite 1/~ter and Wastewater Program 4700 South Bragaw St. P,O. Sox 196650 Anchorage, AK 99519.,6650 www.muflLorg/onsite (9o7) 343-79o4 Soils Log - Percolation Test Gazmend Arapi Patricta S/D, BIk 2. Lot 20 Date Pet?on'ned: 4/30/05 Township, Range, Section: S;te Plan WAS GROUND WA3E R ENC(XJNI~RED? Yes $ L IF YES, AT V~AT D~Pll'~? 7 o Depth to Wate~ A~er Mo~ltodng? "7. 0 P E 0.,o: ~.7- 05 Reading Date Gross Time Net Tlme Depth to Water Net Drop ;1 -2 4/30105 10:48-10:58 10 6-0 I 6 13-4 10:59-11:06 10 6-0 6 5-6 11:07-11:14 7 6-0 6 7-8 11:15-11:23 8 6-0 6 9 - 10 11:24 - 11:34 10 6 - 0 6 11-12 11:35- 11:44 9 6-0 6 13 - 14 11:45- 11:53 8 6-0 6 COMMENTS SP ~ar~d from 3' to 8' exceBenl qualf~. PERFORMED IN ACCORDANCE W1TH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: Municipality of Anchorage Development Services Department Building Safety Division On-Site Water and Wastewater Program 4700 Bragaw Street P.O. Box 196650 Anchorage, AK 99519-6650 www.muni.org/onsite (907) 343-7904 CERTIFICATE OF ON-SITE SYSTEMS APPROVAL FOR A SINGLE FAMILY DWELLING Parcel I.D. 012-464-01 GENERAL INFORMATION Complete legal description Location (site address) Lot 20, Block 2, Patricia Subdivision Olympic Street COSA# O.~ C l g l3.OO Expiration Date: Current Property owner(s) Ali Family Trust Mailing address 3705 Arctic Boulevard, Suite 1334 Lending agency Day phone 727-2912 Anchorage, AK 99503 Day phone Mailing address Real Estate Agent Mailing Address Unless otherwise requested, COSA will be held by DSD for pickup. NUMBER OF BEDROOMS: Three (3) Day phone TYPE OF WATER SUPPLY: Individual Well [] Individual Water Storage [] Community Class ~ Well [] Public Water System [] TYPE OF WASTEWATER DISPOSAL: Individual On-site [] Individual Holding Tank [] Community On-site [] Public Sewer [] The Municipality of Anchorage Development Services Department (DSD) issues Certificates of On-Site Systems Approval (COSA) based only upon the representations given in paragraph 4 by an independent professional civil engineer registered in the State of Alaska. Certificates of On-Site Systems Approval are required for the transfer of title (except between spouses) for properties served by a single-family on-site wastewater disposal and/or water supply system. DSD also issues COSAs upon request to homeowners. Certificates of On-Site Systems Approval are valid for 90 days from the date of issue for properties served by a private or Class C well and may be reissued with new water sample results. (Certificates may be reissued for a period of up to one year with valid water samples.) Certificates are valid for one year for properties served by Class A or B wells or a public water system. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 4. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On-Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is {are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm Anderson Engineering Address P.O. Box 240773 Anchorage, AK 99524 Engineer's Printed Name Michael E. Anderson, P.E. DSD SIGNATURE '~/'" Approved for -~ Disapproved. Conditional approval for bedrooms. Phone 522-7773 Date 11/7/2010 A bedrooms, with the following stipulations: Attachments: COSA Checklist X Septic System Advisory Well Flow Advisory Nitrate Advisory .,,:, ./ / Arsenic Advisory Maintenance Agreements Supplemental Engineer's Report Other Original Certificate Date: (Rev. 11/05) Municipality of Anchorage Development Services Department Building Safety Division On-Site Water & Wastewater Program 4700 Elmore Road P.O. Box 196650 Anchorage, AK 99507 www.muni.org/onsite (907) 343-7904 CERTIFICATE OF ON-SITE SYSTEMS APPROVAL CHECKLIST Lot 20, Block 2, Patricia Subdivision Legal Description: A. WELL DATA Well type AVVVVU Date completed __ Total depth __ IfA, B, or C provide PWSID # Sanitary seal (Y/N) ... Cased to ft. FROM WELL LOG Date of test static water level Well production WATER SAMPLE RESULTS: Coliform colonies/100 mL Arsenic: ug/I B. SEPTIC/HOLDING TANK DATA Tank Type/Material STEP/Steel Tank size 1,250 gal. Foundation cleanout iY/N) Y Date of pumping New C. ABSORPTION FIELD DATA Date installed 10/15-20/2009 Length 53 ff. Tota! depth 4-5 ft. Parcel ID: 012-464-01 g.p.m. Nitrate ~ mg/L Date of sample: ~ Well Log (Y/N) Wires properly protected (Y/N) Casing height (above ground) __ AT INSPECTION Number of Compartments Two Depression over tank (Y/N) Pumper Construction g.p.m. Other bacteria Collected by: Date of adequacy test New Const. Results (Pass/Fail) __ Fluid depth in absorption field before test in. Water added Elapsed Time: __ min. Final fluid depth Any rejuvenation treatment (past 12 mo.) (Y/N & type) Soil rating (g.p.d./~ or ft2/bdrm) 1.2 GPD/SF Width 5 ft. Eft. absorption area 378.5 ft2 Monitoring tube System type 5' Wide Trench Gravel below pipe 2.o ft. Y Depression over field N For bedrooms ~ gal. New depth in. in. Absorption rate >= .g.p.d. N If yes, give date Date installed 10/15/09 Cleanouts (Y/N) Y N High water alarm (Y/N) Y ~ colonies/100 mL LIFT STATION Date installed 10/15/2009 "Pump on" level at 42 in. Datum Bottom of Tank SEPARATION DISTANCES SEPARATION DISTANCES FROM WELL ON LOT TO: Septic tank/lift station on lot Absorption field on lot Public sewer main Sewer/septic service line Animal containment areas None Siz~ in gallons ..,3~e~ ~'T'~-1~ Manhole/Access (Y/N) Y "Pump oR level at 42 in. High water alarm level at 44 Cycles tested 2 Meets alarm & circuit requirements? in. On adjacent lots On adjacent lots Public sewer manhole/cleanout Holding tank · Manure/animal excrete storage areas None SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO: Building foundation >5' Property line >5' Water main >10' Water service line >10' Wells on adjacent lots >200' SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO: Property line 3 .... Water Service line >1o' Curtain drain None Noted Building foundation >1o' Surface water >1oo' Wells on adjacent lots >200' Absorption field >5' Surface water >100' Water main >1o' Driveway, parking/vehicle storage F. COMMENTS: Property is Served by AWWU Water System. ***See Lot Line Waiver. G. ENGINEER'S CERTIFICATION /certify that I have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA COSA guidelines in effect on this date. Engineer's Pdnted Name Michael E. Anderson, P.E. Date 5/27/2009 COSA Fee $ Date of Payment Receipt Number (Rev. 11/05) O q ll '5 Waiver Fee $ Date of Payment Receipt Number FOUND 5/8" REBAR'--~Ii:::). WEST 100TH AVENUE N 89'58'50"E 120.00' LOT 1 16.5' PUBUC USE EASEMENT // // //--- // // // // Icoot ~ / ~.o' COVERED IO. I J 15.0' ~ ENTRY I WOODEN FENCE--J ~ ~J / b 2.0' J ~ ~1 ~ I ' 7,020 S.f. ~ . ~ MH-- ~ ~.o 2 STORY lO.5'?.~- :.:.:. :::JL :.~.-'21 I ' '--g I~J~ RESIDENCE h coo WOODEN FENCE~~_ ~ ~ S 89'58'50"W 120.00' ~ 10' UTILITY EASEMENT LOT 2 lO' DRAINAGE & UTILITY EASEMENT LOT 19 PLOT PLAN __ AS BUILT ~X SCALE 1" = 30' GRID 2528 Project No. 09-068 La ng (907) 522-6476 Registered Land Surveyors (907) 522-4625 kglanglsOalaska.nef / JclanglsOalaska.nef & Associates, inc. 11500 Da~/I Avenue, Anchoruge, Alaska 99515-5049 Phone Fax I hereby certify that I have surveyed the following described properly: LOT 20, BLOCK 2, PATRICIA SUBDIVISION (PLAT No. 69-54) Anchon3ge Recording District, Alaska, and that the Improvements elfuafed thereon are within the properly lines and do not encroach onto the properb/ adjacent thereto, that no improvements on the property lying adlacenf thereto encroach on the surveyed premises and fhaf there are no roadways, fmnsmlssion lines or other visible easemenf~ on said property except aa Indicated hereon. Dated this the 3% Day of :::~'~ , ~[o , af Anchorage, Alaska It is the responsibility of the owner fo determine the exi~fenoe of any easemenf~, covenants, or resfrlctions which do not appear on the recorded subdivision plat.