CERTIFICATE OF ON-SITE SYSTEMS APPROVAL
FOR A SINGLE FAMILY DWELLING
Parcel I.D. 050-611-25 COSA# Q Q 03 H0
Expiration Date: / 0 - a S - / O
1. GENERAL INFORMATION
Complete legal description HAMANN BLOCK 1, LOT 5
Location (site address) 24636 Coleman Circle, Eagle River, AK 99577
Current Property owner(s) Wilma L. Hamann Trust Day phone
Mailing address
Lending agency
Mailing address
Real Estate Agent
Mailing Address
PO Box 770617 Eagle River, AK 99577
Day phone
Audrey Mason Day phone
Unless otherwise requested, COSA will be held by DSD for pickup.
2. NUMBER OF BEDROOMS: 5
3. TYPE OF WATER SUPPLY:
Individual Well ❑
Individual Water Storage ❑
Community Class Well ❑
Public Water System ❑
TYPE OF WASTEWATER DISPOSAL:
Individual On-site
Individual Holding Tank
❑
Community On-site
❑
Public Sewer
❑
The Municipality of Anchorage Development Services Department (DSD) Issues Certificates of Onsite Systems
Approval (COSA) based only upon the representations given in paragraph 4 by an Independent professional civil
engineer registered in the State of Alaska. Certificates of Onsite Systems Approval are required for the transfer of
title (except between spouses) for properties served by a single-family on-site wastewater disposal and/or water
supply system. DSD also Issues.COSAs _upon request to homeowners._ Certificates of On -Site Systems Approval
are valid for 90 days from the date of issue for properties served by a private or Class C well and may be reissued
with new water sample results. (Certificates may be reissued for a period of up to one year with valid water
samples.) Certificates are valid for one year for properties served by Class A or B wells or a public water system.
The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work.
4. STATEMENT OF INSPECTION BY ENGINEER
As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation,
based on procedures outlined in the Certificate of Onsite Systems Approval Guidelines for this application,
shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate
for the number of bedrooms and type of structure indicated herein. I further verify that based on the information
obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water
supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes,
ordinances, and regulations In effect at the time of installation.
Name of Firm _ArcTerra Consulting. Inc. Phone 868-3792
Address 20441 PTARMIGAN BLVD., EAGLE RIVER AK 99577
Engineer's Printed Name KENNLTII M. DUFFUS Date 1 011 6/2 0 0 9
Engineer's Comments: This investigation was completed in compliance with ADEC and MOA regulations. The
assessment of the condition of the well and septic applies only to the conditions as of the day tested. The flow
and absorption rates may change due to subsurface conditions that may not be observed from the surface,
changes Inland use, local soil characteristics, groundwater levels that may fluctuate during the year and the
water usage of the family being served by the system. The operational life of all well and septic systems are
subject to these various and dynamic characteristics and are outside the control of the
evaluator of the well and septic system. Therefore, `
ArcTerra can not give any estimate of how long a r!�'
system will function satisfactory for current or future OF
occupants or can ArcTerra guarantee that no unseen
encroachments, deficiencies or discrepancies exist.
�* 4 * �.
5. DSD SIGNATURE I
ZH tw�Approved for bedrooms. Q it Qf
Disapproved. �` sslokii-, -W
\rl.�
Conditional approval for bedrooms, with the following stipulations:
Attachments:
COSA Checklist X
Septic System Advisory
Well Flow Advisory
Nitrate Advisory
WATERAND
Arsenic Advisory ; WASTEWATER
Maintenance Agreements � M �
Supplemental Engineer's Rei'
. l �
Other ���ii,,. •...,����
By: n�//%�� u%. Original Certificate Date: /O Oq
Municipality of Anchorage
• Development Services Department
/ Building Safety Division
On -Site Water & Wastewater Program
4700 Bragaw Street
P.O. Box 196650
Anchorage, AK 99519-6650
www.muni.org/onsite
(907) 343-7904
CERTIFICATE OF ON-SITE SYSTEMS APPROVAL CHECKLIST
Legal Description: (IAMANN BLOCK 1, LOT 5 Parcel ID: 050-611-25
A. WELL DATA– WATER PROVIDED BY NATURAL SPRING
Well type If A, B, or C provide PWSID # _ Well Log (YM) N (See attached letter)"
Date completed 1969 Sanitary seal (Y/N)_ Wires properly protected (Y/N) Y
Total depth _ft.
Date of test
Static water level
Well production
Cased to _ft. Casing height (above ground) _in.
FROM WELL LOG AT INSPECTION
ft.
WATER SAMPLE RESULTS:
Coliform 0 colonies/100mi- Nitrate ND mg/L Other bacteria 0 colonies/100 mL
Arsenic: ND mgll Date of sample: 09/21/2009 Collected by: Doug Kenley, PL
B. SEPTIC/HOLDING TANK DATA
ft.
Tank Type/Material Septic/Steel Date Installed 1969 Tank size 1500 gal.
Number of Compartments 2 Cleanouts (Y/N) Y Foundation cleanout (Y/N) N" Depression over tank (YM) N
High water alarm (Y/N) N Date of pumping 06/09 Pumper JR's Pumping
C. ABSORPTION FIELD DATA
Date installed 1969 Soil rating (g.p.d.fft2 or ftx/bdrm) 125 System type Crib
Length 20 ft. Width 20 ft. Gravel below pipe -12.3 ft. Total depth 2.4 ft. (bottom of effective)
Eff. absorption area 9A4 ftZ Monitoring tube Y Depression over field N
Date of adequacy test 10/13/2009 Results (Pass/Fail) PASS For 5 bedrooms
Fluid depth in absorption field before test 0 in. Water added 750 gal. New depth 0 in.
Elapsed Time: __L min. Final fluid depth 0 in. Absorption rate >= 750+g.p.d.
Any rejuvenation treatment (past 12 mo.) (YM & type) N If yes, give date _
D. LIFT STATION
Date installed
"Pump on' level at _in.
Datum
E. SEPARATION DISTANCES
Size in gallons Manhole/Access (Y/N)
'Pump off" level at _in. High water alarm level at _in.
Cycles tested Meets alarm & circuit requirements?
SEPARATION DISTANCES FROM WELL WATER SPRING ON LOT TO:
Septic tank/lift station on lot 10(Y+
Absorption field on lot 100'+
Public sewer main 75'+
Sewer /septic service line 25'+
Animal containment areas 50'+
On adjacent lots 10(Y+
On adjacent lots 100'+
Public sewer manhole/cleanout 1001+
Holding tank 100'+
Manure/animal excrete storage areas 1001+
SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO:
Building foundation 4.2'+ Property line 51+ Absorption field 5'+
Water main 10'+ Water service line 101+ Surface water 95'+/-***
Wells on adjacent tots 100'+
SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO:
Property line 10'+ Building foundation 10'+ Water main 101+
Water Service line 101+ Surface Water 1001+ Driveway, parking/vehicle storage 10'+
Curtain drain 50'+ (None Known) Wells on adjacent lots 1001+
F. COMMENTS
* Water system source is a spring with a cistern. " No outside foundation cleanout In -floor cleanout in garage to
tank. "'Meets surface water separation for date installed—ore 1973
G. ENGINEER'S CERTIFICATION OF AZ
I certify that I have determined through field inspections and
review of Municipal records that the above systems are in t �!
conformance with MOA COSA guidelines in effect on this date.
Engineer's Printed Name KENNETH M. DUFFUS r AUNNrn ���C
Date IQ/1N2009 i
°j�rtrno��
COSA Fee $490.00
Date of Payment /0
Receipt Number
(Rev. 11105)
Waiver Fee $
Date of Payment
Receipt Number
Municipality of Anchorage
� 4
Development Services Department
i Building Safety Division •• "
- On-Site Water and Wastewater Program, 4700 S. Bragaw St.
P.O. Box 196650 Anchorage, AK 995196650 Page of
www.ci.anchorage.ak.us (907) 343-7904
ON-SITE WASTEWATER DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT
- -
Permit Number: PID Number. 050-611-25
N•n`lmn
!Z
Wastewater System: ❑ New ❑ Upgrade
Ad"" Qlypr AV qckq77
ABSORPTION FIELD
phahe Nuneer of Betrooms
O Deep Ttehhi O Shadow Trrandh Cl Bw O Mand ®Other 0o0
Sal Resp
Tdal Depth from "e al grade.
LEGAL DESCRIPTION
rPnTl
20-4
Bka9r Loc Slodmsan:
Depm lopipe Donato tram appal Pads
Gnval depth beneath pqa'.
Town" Raps. Sedan'.
Fol added above orp.hal Wade
unk Ft
Grave Lanplh.
20 Ff.
Well: ElNew El Upgrade
Grave walk
Fl
Number a Yost
Dhaenca between InstWell:
FI
CMstfh =(Prnee. A B. Ct:
Taal Depth:
Caw w
Tote absaplm eat
P" Masted
4 Ff
D3034
Adler
Dae Dnkd
SlatCYARMLevel.
Installer
Das Installed.
Unknown
you,
pump sat at
Catng Hayti Above Grana
TANK
SEPARATION DISTANCES
®Septic ❑ Holding ❑ S.T.E.P.❑ Other.
To
Septic
Absorption
Lift
Holding
lubliclPrivate
Mae,ta .
caprny
From
Tank
Field
Station
Tank
Sewer Line
Unkown
1500"
well
100'+
100'+
NA
25'+
MeteredMnhe.rofCmWotets
Steel
2
S.fea,wae
50'+
100'+
NA
NA
LIFT STATION
Sao
Mahaaausr
Let Lee,5'+
10'+
NA
NA
Get
4.2'+
10'+
NA
NA
-puhM ow towel at
•Pump dr level a.
Hph water tem a
Fandeon
n
N
F
NA
NA
NA
NA
P'••p Maks a Mode
Eloc:V c Inspection. Wormed by
cutan Dram
Reneka
BENCH MARK
Looaon ea DewphM
Bottom of sidin
Attuned Elevation:
100 FL
1re` S��'a�
.�K`4,,
Consulting tat 1 o/1 3/og
Inspections performed by: Arcterra Dates:
.2nd
♦ KENN 777 e
DUFFUS
Development Services Department Approval
♦♦c
CE 11
♦ Jf 0�,�
Reviewed and approved by: Date:
♦♦��'�/�
(Rad I%=)
October 13, 2009
Wilma Hamann
P.O. Box 770617
Eagle River, AK 99577
RE: fIAMANN S/D, ADD //1 LOT 5, BLOCK 1
Dear Wilma,
Per your request, we have inspected the on-site water and wastewater systems of the
above referenced property. This investigation was based on observations of the day in
which the septic adequacy was performed, information from others and available
Municipality of Anchorage (MOA) record documents. Based on the above information
it appears that the property was developed between 1958/59 and no record documents
of the existing systems were. found at ADEC or the Municipality of Anchorage
(MOA). This is not uncommon for this area within the time this property was
developed.
The property has an existing single-family 5 -bedroom I -story structure with a walk out
basement. The property is served with a 1500 -gallon septic tank with crib disposal field
and a spring fed concrete cistern (see attached photos). Discussions with DSD Staff
indicate that since it is not a well they can not certify the system even though the water
meets current water quality standards. Others performed the water quality testing, with a
sample collected on September 21, 2009, and attached to this report.
On October 13, 2009 the septic adequacy test was performed. Prior to testing JRs
Pumping pumped the 1,500 -gallon septic tank. The absorption field monitoring tube
was dry at the start of the test and 750 gallons of water were added at the monitoring
tube. The septic field readily absorbed the water and was dry at the end of the test. The
system absorbed the required amount of 150 gallons per bedroom per day for a 5 -
bedroom residence. It is my opinion that the system's absorption capacity exceeds that
of a 5 -bedroom house.
It appears that the existing, undocumented septic system is sized as a 5 -bedroom
system. Feld measurements were taken and a testhole performed by Doug Kenley, PE
documents that the system does not encroach bedrock or ground water. Please see
attached drawings. The septic tank is approximately 95'+/- to surface water (see
attached as -built) and conforms to separation distances required at the time of
installation from the information obtained from municipal records. Presently the tank is
less than 5 feet from the building foundation, but met the current separation distances
`
Al2CT1:1Z1ZA
CONSULTING, INC
If
212 E. 51° Ave, Anchorage, AK. 99503
f
Office (907) 868-3791, Fax (907) 868-3793
October 13, 2009
Wilma Hamann
P.O. Box 770617
Eagle River, AK 99577
RE: fIAMANN S/D, ADD //1 LOT 5, BLOCK 1
Dear Wilma,
Per your request, we have inspected the on-site water and wastewater systems of the
above referenced property. This investigation was based on observations of the day in
which the septic adequacy was performed, information from others and available
Municipality of Anchorage (MOA) record documents. Based on the above information
it appears that the property was developed between 1958/59 and no record documents
of the existing systems were. found at ADEC or the Municipality of Anchorage
(MOA). This is not uncommon for this area within the time this property was
developed.
The property has an existing single-family 5 -bedroom I -story structure with a walk out
basement. The property is served with a 1500 -gallon septic tank with crib disposal field
and a spring fed concrete cistern (see attached photos). Discussions with DSD Staff
indicate that since it is not a well they can not certify the system even though the water
meets current water quality standards. Others performed the water quality testing, with a
sample collected on September 21, 2009, and attached to this report.
On October 13, 2009 the septic adequacy test was performed. Prior to testing JRs
Pumping pumped the 1,500 -gallon septic tank. The absorption field monitoring tube
was dry at the start of the test and 750 gallons of water were added at the monitoring
tube. The septic field readily absorbed the water and was dry at the end of the test. The
system absorbed the required amount of 150 gallons per bedroom per day for a 5 -
bedroom residence. It is my opinion that the system's absorption capacity exceeds that
of a 5 -bedroom house.
It appears that the existing, undocumented septic system is sized as a 5 -bedroom
system. Feld measurements were taken and a testhole performed by Doug Kenley, PE
documents that the system does not encroach bedrock or ground water. Please see
attached drawings. The septic tank is approximately 95'+/- to surface water (see
attached as -built) and conforms to separation distances required at the time of
installation from the information obtained from municipal records. Presently the tank is
less than 5 feet from the building foundation, but met the current separation distances
Hamann Add L5, a l
October 13, 2009
Page 2 of 3
at the time of development. An in -floor drain within the structure acts as a cleanout for
the mainline in the house to the tank. All other separation distances conform to present
code requirements. From available data and visual observations, it appears that this
system poses no health or safety threat to adjoining properties or other individuals.
The assessment of the condition of the septic applies only to the conditions as of the
day tested. The absorption rates may change due to subsurface conditions that may not
be observed from the surface, changes in land use, local soil characteristics,
groundwater levels that may fluctuate during the year and the water usage of the family
being served by the system.
The operational life of all septic systems is subject to these various and dynamic
characteristics and are outside the control of the evaluator of the septic system.
Therefore, ArcTerra cannot give any estimate of how long a system will function
satisfactory for current or future occupants nor can ArcTerra guarantee that no unseen
encroachments, deficiencies or discrepancies exist.
If after review of these records you or any of the underwriters have any questions
regarding the adequacy of this system or the methods and/or procedures employed
during our inspection or evaluation, please feel free to contact me at (907) 696-
6111/Fax (907) 696-8111.
Respectfully,
ArcTerra Consulting, Inc.
Kenneth M. Duffus, P.E.
Attachments: As Noted
AS -BUILT SYSTEM DETAILS/SITE PLAN Permit# PRE -1963
HAMMAN S/D#1, LOT 5, BLOCK 1 PID# 050-611-25
6SPS49.
HDPE
IV \ X
4,4
/ ti3�s2
t 2 .�
A -C=31.2'
B -C=29.9'
A -D=34.7'
C'
B-D=33.2'm�
A -E=80.7'
b1500
B-E=51.1'A-F=N/A
:IC
SEWER ROCK
B-F=N/A
AZ9s �
Alf �r 1
9 T *�l
' KENNETH M. /
CE -7116
qb' FESSIO�=
\\Server\etoroce\WELL & SEPTIC - Filed By Le
.f
Lot 5
o
40.�y O
� PN
2
»cre/e
=Ez.. 20x20
d 'l
SCALE- NTS
1• =
72.8 a
FINISHED GRADE
r9l
vwnROCK
1
20••/ -
PREPARED FOR:
WiLMA L HAMANN TRUST
PO BOX 770617
EAGLE Rl1•ER. AK 99577
(907)694-2776
FIELD BOOKS CpeVTED.
saINDMtLOS tcK0'M-
:
STA"I* NA KMDASBULT.LOS 10 20 09DeG ' SW161ACRD ntE: " 09-060
09-M SEPDMdwq
Hammon SubA\AOan/1\Block 1\Lot 5\Hcmonn.c�9
"/twee"
// L6t L
GRAPHIC SCALE- 1 Inch - 80 f«r
40 zo 6 20 40 go t 0
FOR: _ r 10/ -1s -= --
20/2009 Lot5
Block 1
Little Bear Services Grid AS -BUILT
2951 Carriage Drive 161 HAMANN $UBD.
Anchorage, Alaska 99507 Drawn by Field Book ADDITION NO. 1
(907) 350-5541 r
I hereby certify that the property described hereon has been surveyed �
by me, or. OF, at my direction, and that the improvements situated thereon A�\
,, 11
are within the property lines and do not overlap or encroach on the ���••"' "�is1
property lying adjacent thereto unless otherwise shown. That no �/ �, '•.fj`
improvements on the property lying adjacent thereto encroach on the GS
A A
mises in question and that there are no roadways, transmission 9
* :'f
lines or other easements on said property except as shown.
It is the responsibility of the owner or builder, prior to construction,
to verity proposed building grade relative to finish grade and utility // BOBBY F. BUBNErr
an
connections and to determine the existence of any easements, covents, 19-6464
Joe
or restrictions which do not appear on the recorded subdivision plat.
AW
listed distances prevail over scaling. SSIONIY
\ Reproduction may cause distortion.
Sent By: KENLEY CONSTRUCTION SERVICES; 907 248 5774; Oct -18.09 5:28PL1;
p,RrLtitU_U FCR N1:UA HAIA.ALN — — — — — — — —
LECAL DLS(R'PTI'kl. HAUANr S/D. D10CY 1, LOI 5 _ — — —CA IE: 10/03/09 _
DLpTH
z-
cn — —Solt S LOG
a
FtFCOLAf10P! TLSf
pi7ac.
TCST HULF
Cp/CM cn�e haw!des
to 21
B o.1t.
� �1'�yN7y�•�J'A`
//7'Yul a
c;
i r mcy
DEVTII 10 DAlL
GROU\0'A.\�tR _
n0!4 IV/03/09
10/12/099
Page 2/2
1
OF A4 11
L
r
� r
r:rl rin I wAIER ItVEL n_1 uFOa
HEAMG (M.)
PE'tCV.ATV,I RATr _ (UINJIN.)
TESL RUN 6UBEEN_ — rl. AND_ _
FIU;DAKtD FL'; FUDR mfxrs vs — . NC — —
PERC. 141 E D'A. — . (HI )
Aiia Dr IFFU— I
CJV!!FNI Hrl PEI+.00lA B0tl IrST I'lC.r(MVFD. T-Sf uC�Y0 P:F. G't1:Cra7 NA' 8
_U FCCR C0A7�APrp To SiNEAa P1T
E WAS
TNA- ff.4'nS.TAU,U Of kOnckT HAUAl15.— — — — — — — — — — — —
�rH.,WA'iU F.Y r8:C Hr1::FY CIItT,F" irfA.i 11+5 'FA; PLkFCI+N'G R! ACCVii)AF:::F.
VIM ALL $FAr 3 FACN'UI'AL I;UIE'EI IqS IN rFt tv CR lml' DAIT. I�Z�
AS I KCNLCY C k. 1876
Ye
Sent By: KENLEY CONSTRUCTION SERVICES; _.907 2`46 5774;
5615301 SOSEMrCMMrtal
wvi
SOS ReLd
10951I9001
Ck"t flame
Douglas Kenley P.E.
?reject Waalala
09110
Cliest Sample i0
Hamarm SID# 1111, 1.5
Matti.
Dr6nkinit Water
SamOk Remarks:
Oct -9.09 1C:20AM; Page 1
06.56.32 a m 10-07-2009 2 M
Plotted Datdl'iene
Cdktted DdclTimo
Receind betemmt
Teckn(eal Dicacter
106'06/2009 1214
OMI/2009 17A5
09/228009 11:10
Strobe" C. fAe
NlcrobloloaY Laborato
Colony Count 0 m0100mL i42092220 A (<2W) 09/22/09 DLC
Total Colircm 0 M1100mL 3.42092211) A (41) D9/27)09 ULC
Fecal C0lirorm 0 ce0100mL ;42092220 A 403 o9t22/09 DIC
Allwoble
Ren Aealyus
Pwwcw
Rnulu POt.
Ureu
4Med CoataimlD Limits
Dar Dote Imt
mettle by LGP/M!
Arsenic
ND SOD
utL
5P2%8 C (<lo/
I0f02l0910101M NRB
Matas DaparGaant
Total Nitrtic/Nit i't-N
ND 0. IOU
mtJL
1M2D450CN03-Y 0 (<IO)
10/03109 ICE
NlcrobloloaY Laborato
Colony Count 0 m0100mL i42092220 A (<2W) 09/22/09 DLC
Total Colircm 0 M1100mL 3.42092211) A (41) D9/27)09 ULC
Fecal C0lirorm 0 ce0100mL ;42092220 A 403 o9t22/09 DIC
M Mn.'...
October 13, 2009
ARrV
CIERRA
ENGINEERING AND SURVEYING, INC.
Municipality of Anchorage
Development Services Department
On -Site Water and Wastewater Program
P. O. Box 196650
Anchorage, Alaska 99519-6650
RE: HAMANN S/D ADDN #1, BLOCK 1, LOT 5 — ON-SITE WATER &
WASTEWATER SYSTEM
The owner has requested we proceed forward to obtain a COSA on the subject lot. As
part of the process of reviewing the files and investigating the property it was determined
that the house was constructed in 1968/69 and no record documents of the existing
system were found at ADEC or the Municipality of Anchorage (MOA).
The existing structure is a single-family 5 -bedroom 1 -story structure with a walk out
basement. The property is served with a 1500 -gallon septic tank with crib disposal field
and a spring fed concrete cistern. We tested and passed the septic system. Discussions
with DSD Staff indicate that since the water supply is not a well, they could not certify
the system even though the water meets current quality standards. Testing for the water
quality was performed by others and is attached to this letter.
In addition to the above information we arc providing the following:
• Survey as -built.
• Septic as built documenting the system and separation distances.
• Testholc verifying depth to water table and bedrock
• Current water samples
• Inspection Report
• COSA Form
• COSA Checklist
Civil Design ; On-site Well/Septic; Land Development; Planning
Hamann Add L5, B I
October 13, 2009
Page 2 of 2
We were unable to locate any public or private wells within 200' of our proposed system
location except as noted. There is no surface water within 50' of the existing system as
required at the time of construction or any known curtain drains within 50'. From
available data and visual observations, it appears that this system poses no health or
safety threat to adjoining properties or other individuals.
If after review of the attached information you have any questions, please contact me at
696-611 UFAX 868-3793.
Respectfully,
ArcTerra Consulting, Inc.
Kenneth M. '.E.
Attachments: Septic as built
COSA Checklist
COSA Form
Septic Inspection Report
Survey as built - Little Bear Services
Water Samples - Doug Kenley, P.E.
Testhole - Doug Kenley, P.E.
20441 PTARMIGAN BLVD • EAGLE RIVER, AK 99577-8736 • Pit (907) 868-3792 • FAX (907) 868-3793
� rte\ .,:.. ,� � -• �., r
�\Y
AS -BUILT
I hereby certify that I have surveeyyed the following described
property: L- O T S,$/ e L. J,
H2,nn r o% !7(, i ,i.. f .y„
r' -F f5�, i'l44). k'i k•, ...�.
Anchorage Recording Precinct, Alaska, and that the improve-
ments situated thereon are within the property lines and do not
overlap or encroach on the property lying adjacent thereto, that
no improvements on property lying adjacent thereto encroach
on the premises in question and that there are no roadways,
transmission lines or other visible easements on said property
except as indicated hereon.
Dated at Eagle River, Alaska
this1 Y— ' Jay of 200__
ROBERT C. JOHNSON
SCALE: Registered Land Surveyor No. SWLS
1' :`, o Box 77.0456, Eagle River, Alaska 99577
Phone (907) 694:2543
October 13, 2009
AR ERRA
ENGINEERING AND SURVEYING, INC.
Municipality of Anchorage
Dept. of Health & Human Services
On -Site Services Section
P. O. Box 196650
Anchorage, Alaska 99519-6650
RE: HAMANN S/D ADDN $1, BLOCK 1, LOT 5 -- ON-SITE WATER &
WASTEWATER SYSTEM
The owner has requested we proceed forward to obtain a HAA and COSA on the subject
lots. As part of the process of reviewing the files and investigating the property it was
determined that the house was constructed in 1958/59 and no record documents of the
existing system were found at ADEC or the Municipality of Anchorage (MOA).
The existing structure is a single-family 5 -bedroom 1 -story structure with a walk out
basement. The property is served with a 1500 -gallon septic tank with crib disposal field
and a spring fed concrete cistern. We tested and passed the septic system. Discussions
with DIIHS Staff indicate that since it was not a well they could not certify the system
even though the water met current quality standards. Testing for the water quality was
performed by others and is attached to this letter.
In addition to the above information we are providing the following:
• Survey as -built.
• Septic as built documenting the system and separation distances.
• Testhole verifying depth to water table and bedrock
• Current water samples
• Inspection Report
• COSA Form
• HAA Form
We were unable to locate any public or private wells within 200' of our proposed system
location except as noted. There is no surface water within 50' of the existing system as
Civil Design •F On-site Well/Septic •I- Land Development + Planning
required at the time of construction or any known
available data and visual observations, it appears that
safety threat to adjoining properties or other individuals.
Hamann Add L5, B 1
October 13, 2009
Page 2 of 2
curtain drains within 50'. From
this system poses no health or
If after review of the attached information you have any questions, please contact me at
696-6111/FAX 868-3793.
Respectfully,
ArcTerra Consulting, Inc.
Kenneth M. Duffus
Attachments: HAA Form
COSA Form
Septic Inspection Report
Testhole - Doug Kenley, P.E.
Water Samples — Doug Kenley, P.E.
Survey as built — Little Bear Services
Septic as built
Owners Report