Loading...
HomeMy WebLinkAboutFASSLER LT 1F si r' Lot I #051-531-32 Municipality of Anchorage Page 1 Building Safety Division On-Site Water and Wastewater Program 4700 South Bragaw Street P.O. Box 196650 A~chomge. AK 99519-6650 wv,'w.cLanchorage.ak.us (907) 343-7904 ON-SITE WASTEWATER DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT Permit Number: ' SW010083 PID Number: 051-531-33 '~'~: Wastewater System: New MM&M Contracting P.O. Box 670495 Chugiak~ AK 99567 ABSORPTION FIELD ~,: ~ ,~ s.~..~: Deep Trench 688-1236 Three (3) LEGAL DESCRIPTION 1.2 c~o~e 8.0 - I Fassler Subdivision 2.0 n. 6 1.5 - 6 n. 32 Well: New 3 R. 1 Private 181 n. 181 n. 384 Fe ASTM D3034 PVC Sullivan Water Wells 7/20/2001 150 F,. MM&M Contracting 7/27.29/01 ~"~: I ""'~ .'~":n Ic~' '~' ***'' c'~''~ TANK 20 c,~u . >2 n SEPARATION DISTANCES Ei septic n Holding I-] S.T.E.P. n Other:. T~__~....,.~To Septic AbsorpUon Lift Holding ~c/Plwa~e Tank Field Station Tank S~,~U~ Anchorage Tank 1,000 wa >100' >100' N/A N/A >25' Steel Two (2) >100' >100' N/A N/A ~ / LIFT STATION- NONE ON LOT t,.t~,.>5' '~ ';N/A N/A ~': ~,~,o. >5' >10' N/A N/A '~'~"""""": '~'~ ""' "' "' c~,~ None Noted ~,,~,~ ~ BENCH MARK 2" Insulation Over Septic Tank. Northwest Corner on Top of East Deck in Back of House. Engineer's Stamp Inspections performed by: MEA Dates: 1'~ 7/27/01 2ra 7/29/01 Department of Health and Human Services approval Muhicipality of Anchorage · DEVELOPMENT SERVICES DEPARTMENT 4700 Sout~ Bragaw Street Anchorage, AK 99519-6650 - 343J904 On-Site Wastewater Disposal System or Well Inspection Report Page 2 of 3 Permit Number SW010079 PID No. 051.531-32 Z S; Three -- Bedroom House Well FASSLER CIRCLE ~ A1st~[e~ate A B Sl 35.7 21.6 .C4 5O.5 32.5 C5 81.2 61.0 M1 76.2 55,8 Municipality of Anchorage DEVELOPMENT SERVICES DEPARTMENT 4700 South Bragaw Straet Anchorage, AK 99519-6650 - 343-7904 On-Site Wastewater Disposal System or Well Inspection Report Page 3 of 3 \ Permit Number SW010079 PID No. 051-531-32  _~ ~ 98.5u~ tJO tJ 88.5 / __92.$ / Geotextile Fabric Drainfield Rock 82.3 27' 5' I PkOFILE AS-BUILT 1' = 10' ANDERSON ENGINEERING P.O. BOX 240773 - ANCHORAGE, AK 99524 522-7773 522.6779 (FAX) November 29, 2001 Municipality of Anchorage Development Services Department On-Site Water and Wastewater Program P.O. Box 196650 Anchorage, AK 99519-6650 Subject: Lot 1, Fassler Subdivision Separation Distance Waiver Absorption Trench to Lot Line Dear On Site Services Engineer:. The new absorption bed recently constructed on Lot 1, Fassler Subdivision encroaches within 4' of the northern lot line. During construction it was determined this was the best location on the lot for the new system due to the irregularity of the existing ground surface in the area. The lot line was not clearly staked dudng placement of the trench and the edge of the trench was inadvertently placed closer than 10' from the lot line. The property to the north of the trench is currently being developed, but no conflicts with either the well or the septic system result from the placement of the trench near the property line. In addition, the soils encountered in the trench were well-graded gravel with a large quantity of sand which percolate at rates between 1 and 5 minutes per inch. We therefore recommend a lot line waiver be issued allowing placement of the new trench within 4' of the lot line. Sincerely, Michael E. Anderson, P.E. Municipality of Anchorage Building Safety Division/On-Site Water and Wastewater Program 4700 S. Bragaw Street, Anchorage, AK 99519-6650 SOILS LOG -PERCOLATION TEST Performed For:. ~ Legal Description: ' -- ' OG/OL GW With Sand Bottom of Hole 10 11 12 13 14 15 16 17 18 21 SLOPE Was Groundwater Encountered? No If Yes, What Depth? Depth to Water After Monitoring . None Date: 7/29/01 Date Performed: See Site Plan Reading Date Gross Net Depth TO Net Time Time Water Drop 1 27-Jul 10:15 1.5" 2 10:25 10 6' 4.5' 3 10:26 2' 4 10:36 10 7' 5' 5 10:37 2,25' 6 10:47 10 7.25' 5' Perc. Rate: 2 Min./Inch Peru. Hole Diameter:. 6' Test Run Between 5 Ft. and 6 Ft. Comments: Peru. Cavity Presoaked Prior to Test. Test to Verify Same Soils as Test Hole Nos. 1 and 2. Performed By: M_ Anderson. I, ~ Certify That This Test Was Performed In Accordance With All State and Municipal Guidelines In Effect On This Date: 11/29/01 by DOC CO. SULLIVAN'WATER WELLS P.O. BOX 670272, CHUGIAK, ALASKA ~9567 * TELEPHOI~IE 688-27~0 ADDRESS: LEGAl_DESCRIPTION: _F~~'5 4 ~-----'~-., ~ -- ERMIT .UJ. ER: Date of, su TAX IDENTIFICATION NUMBER; ..~-~-S~ ~ "' ~--~ Is well.located at approved permit location? ~J~'es ~1 No Method of Drilling: ~3~rotary ;.J cable tool Depth ef well: ! -~/ · roe ~ "r,L"&'/-'Wall Thickness i 4:~ ~'"~) inches Casing Tyr --t~ Diameter_,. ~ inches, de~th__ / ~ jl I iner'l:ype: ~..) ~ ~ ~' Casing Stickup Above Ground; Static Water Level: t -~'~) Recover Rate:_ ~ ~ . gpm Method of Testing: ~4-f ~ ,, feet feet , feet Well Intak; Opening Type: ~K~'~o~n end LI open. hole LI Screened;. Start feet Stopped. .. feet [.J Perforations Start ~fc~t ..~..topped feet Grout Type: ~,,u'F'~''~4 . .Volume Depth; from ~ __ feet, to ..~ ~"~ 'feet Well Disinfected Upon Completion? Method of Disi~fectlon: _C 0 No BORE HOLE DATA Comments: ATTENTION: It is the responsibility of the property owner to submit a copy of'the well log to the.proper authority. Municipality o! Anchorage: Department of Health & Human Servia'es and/.Er Departmeht of Environmental Conservation. MatSu Borough: · aI OepartmentdfEReceived Time~rN0v, ~,~. 5:52PM Driller's Name ~ ~ ' .. MUNICIPALITY OF ANCHORAGE Development Sen/ices Department On-Site Water & Wastewater Program 4700 Soufh Bragaw Street P.O. Box 196650, Anchorage, AK 99519-6650 (907) 343-7004 ON-SITE WASTEWATER DISPOSAL SYSTEM PERMIT Initial Date Issued: Apr 24, 2001 Expiration Date: Apr 24, 2002 Permit Number: SW010079 Legal Description: iFASSLER LTI : Design Engineer: 0014 Anderson Engineering Owner Name: RUTH E. FASSLER Owner Address: NHN FASSLER CIRCLE CHUGIAK, AK 99567- Parcel ID: 051-531-32 Site Address: Lot Size: 20023 SQ. FT. Total Bedrooms: 3 Permit Bedrooms: 3 This permit is for the construction of: [] Disposal Field [] Septic Tank [] Holding Tank [] Privy [] Private Well [] Water Storage A~I construction must be in accordance with: 1. The attached approved design. 2. Ail requirements specified in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of AJaska Wastewater Disposal Regulations ( 18AAC72 ) and Drinking Water Regulations ( 18AAC80 ). 3. The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 ( 24 hours ). ( Not required for a Water Supply Permit only ). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must be either: A. Open and closed on the same day. B. Covered, sealed, and heated to prevent freezing. ! 5. The following special provisions. ~ ~.THE MAXIMUM DEPTH OF THE PROPOSED ABSORPTION TRENCH SHALL BE NO DEEPER THAN 8 FEET FROM ORIGINAL GRADE AT ANY POINT. Municipality of Anchorage Development Services Department Building Safety Division On-Site Water and Wastewater Program 4700 South Bragaw St. P.O. Box 196650 Anchorage, AK 99519-6650 www.ci.anchorage.ak.us (907) 343-7904 ON-SITE SEWERJVVELL PERMIT APPLICATION FOR A SINGLE FAMILY DWELLING Parcel I.D. Permit Number SW O l DO 7 ~1 Property owner(s) MM&M Contracting Day phone 688.t236 Mailing address (1) P.O. Box 670495 Chu~liak, AK 9956~ Me~'~-address (2) ~f/#V F,9$$LE R ¢IR£L E Zip Code Legal description (Lot, Block & Sub'd.) Lot t, Fassler Subdivlslon Legal description (Section. Township & Range) Lot Size Z~OZ3 Acres/~ Number of Bedrooms Three (3) THIS APPLICATION IS FOR: Sewer Only Sewer and Well Sewer Upgrade THIS PROPERTY CONTAINS: Hot Tub Swimming Pool Therapy Pool [~] Well Only ~]~ Water Storage ~ Jacuzzi ~ Water Softening Unit I certify that the above information is correct. I further certify that this application is being made for a Single Family Dwelling and is in accordance with applicable Municipal Codes. (Signature of property owner or authorized agent) Permit Fees: Date of Payment: J"~ ~ 1~)~ (~)'~ Receipt Number: (n~v. l~o0) Waiver Fees: Date of Payment: Receipt Number: : Apd112,2001 Municipality of Anchorage . . Development Services Department On-Site Water and Wastewater Program 4700 South Bragaw Street Anchorage, AK 99519-6650 Subject; Lot 1, Fassler ~ubdivision Septic System Design and Permit Application Impacts to Adjacent Properties Dear Onsite Services Engineer:... . The owner of Lot 1, Fassler Subdivision Intends to place a new 3-bedr0om home on the lot..We are therefore applying for a permit to construct a septic system on the lot to ,serve the proposed home. The lot is currently served by a community water system. The attached Site Plan .a. nd backup documentation Identi~ 'the lo.cation and configuration of the new septic system and the parameters used in the design.' It also ... shows the location of the water service line and the alternate septic site. Existing - drainage patterns are shown and will not be altered by the development of the lot, Two test holes were placed at the proposed 'locatkJn for the new and alternate',' ". .absorption trenches and revealed well-graded gravel with minor, amounts of silt. No . '. groundwater was noted In the test holes during excavation and none was noted during .. the monitoring period. 'T. he soil percolated at a rate of 1 minute per !nch. Conditions · are excell~e, nt for an ,o, nslte septic system. We are therefore'proposing to place a 3' wide by 32 long by 6 effective depth a.b.s, orption trench to treat the septic effluent. 'The pipe will be placed at 3' below the existing ground surface and the total depth of.the trench will be 9'. A minimum of 3' of cover will be placed o~,er the bed to prevent frost penetration and possible freezing. - . - . The ground surface on the lot slopes as shown on the attached Site Plan with slight grades from south.to north and west to,east. A steep bluff is noted on the western boundary, which slopes down to the septic area.' It will have no impact on .the new,- system. The new trench will be constructed parallel to the contours of the surface In. conformance with Municipal requirements. Grading will be' accomplished to assure surface drainage is away from the new trenches. 'The existing drainage pattern on the lot will not be affected dudng development. If the system Is constructed lin accordance with our design the following statements 1. The system, if constructed as designed, will have no adverse impact on the wells in the area or those to be constructed in the future.' The lot is currently served by Lot 1, Fassle~ Subdivision April 12, 2001 Page Two - Sincerely, a community.water system. . . -.. 2., ;The system, if constructed as deslgnedl will have no adverse Impact on existing 'septic systems in the area or those to be constructed In the future.. 3.:* The system, if'COnstructed as designed, will have nb adverse impact on reserve . .'space. either surface or subsurface, on any lots located in the area. 1 4.... The'system if constructed asdeslgned will have nb adverse impact On drainag~ · .' ' patterns in the area.- The current drainage pattern will be maintained. .. u~su~=i8~8 (Vacant) THIS PROJECT 5 IEAI)0W RIDGE' AREA MAP SCALE 1" = 100': "' O 0 Z m _25% Alternate Slate I O% TH2 ~ Three Bedroom House TH1 32' Lon~ X 3' Wide X 6' Effective Absorl~tion 1,000 (~llon Septic Tank FASSLER CIRCLE NOTE: This lot is served by a community water system. There are no conflicts with wells or . septic systems in the area. · . ~1/~ ~b~l~ ' $-~..... ..... LOT 1, FASSLER SUBDIVISION DESIGN FACTORS: SYSTEM REQUIREMENTS: Three Bedroom Home Peru. Rate: 1 MinJinch Application Rate: 1.2 GPD/SF Deep Trench System 1,000 Gallon Septic Tank 6' Drain Field Rock 3 Bedrooms X 150 GPD 11.2 GPD/SF = 375 SF of Absorption Area 375 SFI12SF/LF = 31.25 LF Trench Length Therefore: Construct an Absorption Trench 32' in Length by 3' Wide With 6' of Drelnfield Rock Beneath the Distribution Lateral. Distribution Lateral to Be Placed 3' Below Existing Ground. Total Depth of Trench to Be 9' from Existing Sudace. Mound Over Trench if Necessary to Provide Minimum Cover of 3'. ': 2'6" *: ': ' i'.:~'' :..'.': - . :%,:: · Backfill NOTE: TYPICAL DEEP TRENCH SECTION (NO SCALE) Grade Area Over Trench to Drain Away. Minimum 6' Separation From Bedrock. Minimum 10' Separation From Lot Line. Minimum 4' Separation From Groundwater. Minimum 10' Separation From Water Service Une. I 5 7 8 18¸ PERFORMED FOR: LEGAL DESCRIPTION: MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH ~ HUMAN SERVICES 825 L STREET, ANCHORAGE, AKQ9502-0605 SOILS LOG - PERCOLATION TEST M & M CONTRACTING LOT 1, FASSLER SUBD TEST HOLE # PT / OL PERC. LEVEL WELL-GRADED GRAVEL-SAND-CLAY MIXTURES WITH COBBLES: GC SLOPE SITE PLAN WAS GROUNDWATER ENCOUNTERED? NO S L IF YES, WHAT DEPTH? 0 DEPTH TO WATER None P AFTER MONITORING: E DATE: 4/12/01 OX J BOTTOM OF HOLE READING DATE GROSS NET DEPTH OF NET TIME TIME WATER DROP Start 3-April 3.30 12' 1 3:&0 10 2" 10" Recharge 12' 2 3.50 10 2' 10- Recharge 12' 3 ~.:00 10 2' 10' PERC RATE: I MIN./INCH PERC. HOLE DIAMETER: 6' TEST RUN BETWEEN A.,~ FT. AND ~.,,~ FT. COMMENTS: TEST HOLE PRESOAKED PRIOR TO TEST, TEST PERFORMED BY: T.L. K~MBROUGH I, MICHAEL E. ANDEPSON. CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES ON THIS DATE: I 2 3 4, 5 6 7 8 9 II 18 PERFORMED FOR: LEGAL DESCRIPTION: MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH & HUMAN SERVICES 825 L STREET, ANCHORAGE, AKgg502-0605 SOILS LOG - PERCOLATION TEST M & M CONTRACTING LOT I, FASSLER SUBD TEST HOLE # PT / OL PERC. LEVEL WELL-GRADED GRAVEL-SAND-CLAY MIXTURES WITH COBBLES: GC SLOPE SITE PLAN J/L TH*o~ WAS GROUNDWATER ENCOUNTERED? BOTTOM OF IF YES, WHAT DEPTH? HOL[ DEPTH OF WATER AFTER MONITORING: DATE: NO S L O None P E 4/12/01 0% I0~_5% 0% READING DATE GROSS NET DEPTH OF NET TIME T~ME WATER DROP Start 3-April /*~30 12" 1 /.:/.0 t0 3' Recharge 12' 2 /*.50 10 3" Recharge 12' 3 SO0 10 3' 9" PERC RATE: I.I MIN./INCH PERC. HOLE DIAMETER: TEST RUN BETWEEN &,~ FT. AND 5.5 I=T. COMMENTS: TEST HOLE PRESOAKED PRIOR TO TEST. TEST PERFORMED BY: T.L. KIMBROUGH I, MICHAEL E. ANDEI~ON, CERTIFY THAT THIS TEST WAS PERFORHED IN ACCORDANCE WITH ALt. STATE AND MUNICIPAL GUIDELINES ON THIS DATE: ~'~'IZ'°o j ON-SITE WASTEWATER DISPOSAL SYSTEM CONSTRUCTION AND MATERIAL SPECIFICATIONS SUBJECT: LOT 1, FASSLER SUBDIVISION GENERAL: The scope of this project includes the procurement and placement of a new 1,000 gallon septic tank at the.location shown on the site plan. Work also includes the construction of a new 32' long X 3' wide X 6' effective depth absorption trench at the location shown. The distribution line in the trench will be placed at 3' below the existing ground surface. Total depth of the trench will be 9' below the existing ground surface. All components of the septic system must be placed a minimum of 10' frem the water service line on the lot. Construction shall be in accordance with the appreved site plan, design drawings, Municipal Permit with any special previsions or conditions, and all applicable State and Municipal Wastewater Disposal Regulations. The Contractor shall be responsible for obtaining all undergreund utility locates and for the layout of the septic system and verification of the location of all lot lines. Unless .specifically agreed otherwise, the contractor shall be responsible for final grading areas subsequently depressed frem soil settling. Property owner shall be responsible for revegetation of affected areas unless specifically agreed otherwise. Contractors installing wastewater disposal systems must be certified by the Municipal Department of Health and Human Services for system installations. Owners installing their own systems must receive pdor appreval from D.H.H.S. before beginning system installation. SEPTIC TANK INSTALLATION 1. A new 1,000. gallon septic tank must be be precured frem an approved source and installed at the location shown. 2. A septic tank is to be constructed by a certified septic tank manufacturer. Construction shall include two 4' cleanouts for pumping access. 3. The septic tank shall be sufficiently bedded to prevent settling or shifting of the tank. 4. All standpipes on the septic tank shall extend a minimum of 12 inches above final grade. 5. Tanks installed without 4' of cover shall have a minimum of 2" of direct burial insulation. A foundation cleanout shall be installed one to four feet from the building foundation. Two cleanouts are required between the tank and the drainfield. Lot 1, Fassler Subdivision April 12, 2001 Page 2 of 3 7. Final grading over the tank shall be such that a positive slope exists away from the septic tank. DRAINFIELD CONSTRUCTION: 1. The drainfield shall be constructed to the dimensions shown on the design. The bottom of the trench shall be within 2" of level. Distribution piping must be placed level with perforations down atop a level bed of drainfield rock. Rock should then be placed over the pipe to provide a minimum of 2" of cover. 3. A silt barrier or geotextile fabric must be placed between the drainfield rock and the natural soil backfill. 4. Monitor tubes must be 4' in diameter and installed at the locations shown on the design. The portion below ground must be perforated. Contractor shall verify the septic tank and drainfield are a minimum 100' away from any pdvate water wells in the area, 150' from a Class "C" Well or 200' from any community well. 6. Direct bury insulation must .be placed over the distribution system if less than 3' of backfill depth is available. Finish grade over the trench must be mounded to prevent settlement or depressions. 7. Grade area surrounding the absorption trenches to drain away. A minimum 2' of accepting soil is required below the drainfield rock for a 5' wide trench. Contractor shall verify this condition prior to placement of the rock. All pockets of unacceptable materials must be removed and replaced. MATERIAL SPECIFICATIONS: 1. Septic tanks must be constructed by a municipally approved septic tank manufacturer. 2. The following pipe materials are approved for use in septic system installations in the Municipality of Anchorage: Cast Iron (perforated and solid), ASTM D3034 or P.V.C. (perforated and solid), ASTM F810 or H.D.P.E. (perforated, but not solid) and ASTM D2662 or A.B.S. (perforated and solid). 3. Insulation shall be at least 2" thick extruded direct burial polystyrene (Dow Chemical Co. Styrofoam HI or equal). 4. Septic tank inlets and outlets shall be fitted with watertight couplings (Caulder, Femco, or equal). Lot 1, Fassler Subdivision April 12, 2001 Page 3 of 3 5. A permeable geotextile fabric (Typar, Mirafi or equal) must be installed between the final drain rock layer and the native soil layer. 6. All drain rock shall be .5" to 2.5" in diameter with less than 3% passing the #200 sieve. INSPECTIONS: Municipal Ordinance requires a minimum of two inspections. These inspections must be conducted under the supervision of a professional engineer registered in the State of Alaska. The first inspection must be conducted after the excavation of trenches, beds or pits and before the installation of any gravel. A septic tank may be set in place, but may not be backfilled. The second inspection must be conducted after the placement of the geotextile fabdc, gravel, distribution piping, standpipes, cleanouts and insulation. No backfill should be in place at the time of inspection. Contractor shall provide a copy of all field survey layout and construction notes for use in preparing the certified as-built of the completed system. MUNICIPALI~ OF ANCHORAGE Development Services Department On-Site Water & Wastewater Program 4700 South Bragaw Street P.O. Box 196650, Anchorage, AK 99519-6650 (907) 343-7904 ON-SITE WATER SUPPLY PERMIT Initial Date Issued: Jun 07, 2001 Expiration Date: Jun 07, 2002 Permit Number: SW010174 Legal Description: FASSLER LT 1 Design Engineer: 0014 Anderson Engineering Owner Name: RUTH E. FASSLER Owner Address: 24813 FASSLER CIRCLE CHUGIAK, Ak 99587- Parcel ID: 051-531-32 Site Address: Lot Size: 20023 SQ. FT. Total Bedrooms: 3 Permit Bedrooms: 3 This permit is for the construction of: [] Disposal Field [] SepticTank [] Holding Tank [] Privy [] Private Well [] Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations ( 18AAC72 ) and Drinking Water Regulations ( 18AAC80 ). 3. The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 ( 24 hours ). ( Not required for a Water Supply Permit only ). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must be either: A. Open and closed on the same day. B. Covered, sealed, and heated to prevent freezing. Date: 6 '" 7-- ~/ Municipality of Anchorage Development Services Department ' Building Safety Division On-Site Water and Wastewater Program 4700 South Bragaw St. ' P.O, Box 196650 Anchorage, AK 99519--6650 www.ci.anchorage.ak.us (907) 343-7904 ON-SITE SEWER/VVELL PERMIT APPLICATION FOR A SINGLE FAMILY DWELLING Parcel I.D. 051-531-32 Permit Number swOtOI7~l Property owner(s) MM&M Contractin.q Mailing address (1) P.O. Box 670495 Chu,qlak, AK 99567 · -b~i~address (2)~:~'~/~ /~$$LER CI/~(LE Legal description (Lot, Block & Sub'd.). Lot t, Fassler Sulxlivision Day phone 688-1236 Code 7 Legal description (Section, Township & Range) Lot Size_~.~2. ~ Acres/Sq. Ft. Number of Bedrooms Three {3) THIS APPUCATION IS FOR: Sewer Only Sewer and Well Sewer Upgrade THIS PROPERTY CONTAINS: Hot Tub Swimming Pool Therapy Pool Well Only Water Storage Jacuzzi Water Softening Unit I cedify that the above information is correct. I further certify that this application is being made for a Single Family Dwelling and is in accordance with applicable Municipal Codes. (Signature of property owner or authorized agent) Date of Payment: ?) o ~(::~ · (~l Waiver Fees: Date of Payment: Receipt Number:. U.n s u~c~[v~ided ( vacant , PROJECT 16.ADOW ' AREA MAP SCALE 1" = 100': "- -4 m m ,-I Three Bedroom House ~.OT I ' FASSLER CIRCLE SITE PLAN" · SCALE 1' = 30' ' M-nicipality of Anchorage Development Services Department Building Safety Division On-Site Water and Was~ewater Program 4700 Bragaw Slrcct ' P.O. Box 19~,50 Anchorage, AK. 99519-6650 www.ci.~chorage, ak.us (9<)7) 343-7904 Waiver Review Worksheet Wl~: WR0t0I)~) PII~; 051~631-32 HA#: HA010629 Permit~: Date Received: 12/07/01 Legal Description: Fassler Lot I Engineer:. I a . d P Anderson Enalneerlna PO Box 240773 Anchoraae. AK 99~:~4 Applicant: MM&M Construe:till1 Waiver Requested: 4 Feet from Lot Line to AbsoroU¢ll Field Criteria: Geology A. Water Table B. Soil Sorption C. Permeability D. WaterTable Gradient E. Horizontal Separation Total; Points: Waiver Is Granted: .~ Waiver is not Granted: Name of Roviewer Rec#: 13338 Amount: $t16.0~) Date Paid: 17J712001 Municipality .of Anchorage Btflldmg Safety Dzvision P.O. Box 10C, C~O · 4700 S. Bragaw Strcct t~nchoragc. ,'alaska 00519.C,C~0 · (007) $-~3-8801 h t t p://www.cl.anchorag¢.ak.us 12/7/2001 Michael E. Anderson, PE Anderson Engineering PO Box 240773 Anchorage, AK 99524 Subject: Waiver Request for Fassler Lot 1 Waiver Request #WR010099 Parcel ID #051-531-32 HAA #HA010629 ~epIrlment o~ Public Works Dear Mr. Anderson: Your request for a waiver of the required 10 feet horizontal separation from the on-site wastewater disposal system to property line has been approved. The approved separation distance is 4.0 feet. This waiver approval applies to the existing on-sitewaste~vaterdisposal system to property line separation only. Any future upgrade to the on-site wastewater disposal system will require all separation distances be met or another approval from this department. If there are any further concerns or questions regarding this waiver, please call our office at 343-7904. Daniel J. R'oth Civil Engineer On-Site Water & Wastewater Program Municipality of Anchorage Development Services Department Building Safety Division On-Site Water and Wastewater Program 4700 Bragaw Street P.O. Box 196650 Anchorage, AK 99519-6650 www.muni.org/onsite (907) 343-7904 CERTIFICATE OF ON-SITE .SYSTEMS APPROVAL. FOR A SINGLE FAMILY DWELLING Parcel I.D. o5~-531-32 1. GENERAL INFORMATION Complete legal description Fassler Lot~. Location (site address) 248z3 Fassler Circle, Chugiak, AK 99";67 Current Property owner(s) GMAC Mortgage . Mailing address Day phone Lending agency Mailing address Day phone Real Estate Agent Elizabeth MacMullen Mailing Address 892 USA Cir., #~oo. Wasilla, AK 996,;4 .... Unlessotherwise. requested, COSA will be held by DSD for pickup. 2, .NUMBER OF:BE'bROOMS: -~ 3. TYPE OF WATER SUPPLY: In'dividual Well' [] Individual Water Storage [] CommunitY Class ~ Well [] Public Water System Day phone 77,;-~8~2 TYPE OF WASTEWATER DISPOSAL: Individual On-site Individual Holding Tank Community On-site Public Sewer The Municipality of Anchorage Development Services Department (DSD) issues Certificates of On-Site Systems Approval (COSA) based only upon the representations given in paragraph 4 by an independent professional civil engineer registered in the State of Alaska. Certificates of On-Site Systems Approval are required for the transfer of title (except between spouses) for properties served by a single-family on-site wastewater disposal and/or water supply system. DSD also issues COSAs upon request to homeowners. Certificates of On-Site Systems Approval are valid for 90 days from the date of issue for properties served by a private or Class C well and may be reissued with new water sample results. (Certificates may be reissued for a period of up to one year with valid water samples.) Certificates are valid for one year for properties served by Class A or B wells or a public water system. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 4. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On-Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm Pannone Engineering Services, LLC Phone 272-8218 Address P.O. Box 3.002:[7, Anchorage, AK q953.o Engineer's Printed Name Steven R. Pannone, P.E. Date . 8/29/3.3. Engineers Comments: in conducting an adequacy test, [ attempt to provide a thorough, conscientious engineefing analysis of the system in accordance with MOA DSD Guidelines & Regulations. The reported results describe the performance of the system under the conditions encountered at the time of the test, and separation distances measured to readily identifiable features. The operational life of all wells and septic systems depend on the local soil condition, ground water levels that may fluctuate during the year, and the water usage of the family being served by the system. These conditions are outside the control of the evaluator of this system. All systems eventually fail and satisfactory test results do not guarantee future performance of the system, nor do they guarantee that there are no hidden defects or encroachments. PES can therefore not provide any warranty for future performance nor give any estimate of how long the system will continue to meet the operational requirements of the MOA DSD. The content of this report is for the sole benefit of the owner listed above. Any reliance upon or use of this report by any other person or party is not authorized nor will it confer any legal fight whatsoever. 5. DSD SIGNATURE !/ Approved for '~ bedrooms. Disapproved. Conditional approval for 4, ~>' ................ · ~/ · · ,4, ~4" ~ '"..~ & ....... . · ........ ;,?, ...I- ~.~% No. CE 8149 ¢~ ~ ..................... bedrooms, with the following stipulations: Attachments: COSA Checklist Septic System Advisory Well Flow Advisory Nitrate Advisory X Arsenic Advisory Maintenance Agreements Supplemental Engineer's Report Other Original Certificate Date: C:[ ,_., / ~ _ / / Municipality of Anchorage Development Services Department Building Safety Division On-Site Water & Wastewater Program 4700 Bragaw Street P.O. Box 196650 Anchorage, AK 99519-6650 www.muni.org/onsite (907) 343-7904 Bo CERTIFICATE OF ON-SITE SYSTEMS APPROVAL CHECKLIST Legal DescriptiOn: WELL DATA Well type _.P Date completed 7/2o/2ooz Total depth x8z ft. Fassler Lot x If A, B, or C provide PWSID # __ Sanitary seal (Y/N) Y Cased to z8~ ft. Parcel ID: Og~-g~-~2 Date of test Static water level Well production 2o WATER SAMPLE RESULTS: Coliform b~ colonies/100 mL Arsenic: J~..)~) ug/I SEPTIC/HOLDING TANK DATA FROM WELL LOG 7/2o/2oo~ g.p.m. Well Log (Y/N)Y Wires properly protected (Y/N) Y Casing height (above ground) 2~ AT INSPECTION 8/26/20:11 · 58 ff. 6.5+ g.p.m. . in. Nitrate (-.P~ mg/L Date of sample: 8/26/2ox= Collected by: Laura Pannone Tank Type/Material Anchorage Tank Steel Number of Compartments Depression over tank (Y/N) N Pumper JR's Pumping Date installed 7/2q/2oo~ Cleanouts (Y/N) Y High water alarm (Y/N) N/A System type Deep Trench Gravel below pipe 6 Depression over field N For 3 bedrooms Water added4.5o gal. New depth~._A8 in. Absorption rate >= 4,~o+ g.p.d. If yes, give date Date installed ?/2q/~oo~ Soil rating (g.p.d./ft2 or ft2/bdrm) x.2 Length :1~ ft. Width ~ Total depth 9.?F ft. Elf. absorption area :184 ft2 Date of adequacy test 8/:Z6/~O~:L Results (Pass/Fail) ~ Fluid depth in absorption field before test ~_~8 in. Elapsed Time: _o min. Final fluid depth ~_~8 in. Any rejuvenation treatment (past 12 mo.) (Y/N & type) N Tank size aooo gal. Foundation cleanout (Y/N) Y Date of pumping ql*,12o~.', ABSORPTION FIELD DATA fro Monitoring tube Y Pass LIFT STATION Date installed "Pump on" level at~ Datum in. E. SEPARATION DISTANCES Size in gallons~~,,,,2 "Pump off" level ~ Cycles tested z/ V ~ "'~. Manhole/Access (Y/N) High water alarm level at Meets alarm & circuit requirements? in. SEPARATION DISTANCES FROM WELL ON LOT TO: Septic tank/lift station on lot zoo+ On adjacent lots zoo+ Absorption field on lot zoo+ On adjacent lots zoo+ Public sewer main N/A Sewer/septic service line =5+ Public sewer manhole/cleanout N/A Holding tank zoo+ Animal containment areas zoo+ Manure/animal excrete storage areas ~oo+ SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO: Building foundation zo+ Property line zo+ Water main N/A Water service line Absorption field 5+ Surface water zoo+ Wells on adjacent lots zoo+ SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO: Property line ~,' Waived Water Service line =5+ Curtain drain None Known COMMENTS Building foundation zo+ Surface water zoo+ Wells on adjacent lots zoo+ Water main N/A Driveway, parking/vehicle storage zo+ Field was pre-soaked with 700 gallons water. ENGINEER'S CERTIFICATION I certify that I have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA COSA guidelines in effect on this date. Engineer's Printed Name Date COSA Fee $ Date of Payment Receipt Number (Rev. 11/05) Steven R. Pannone~ P.E. Waiver Fee $ Date of Payment Receipt Number Mnnicipality of Anchorage Community Development Department Development Services Division On-Site Water and Wastewater Program 4700 Elmore Street P.O. Box 196650 Anchorage, AK 99519-6650 www.muni.org/onsite (907) 343-7904 Nitrate Advisory Certificate of On-Site Systems Approval # 111340 A Certificate of On-Site Systems Approval inspection and test of potable water was recently conducted on the well water supply on Block , Lot 1 of Fassler subdivision. This inspection revealed a nitrate concentration of 6.8 milligrams per liter (mg/L) was reported for the property's well water sample. The Environmental Protection Agency (EPA) has established a maximum contaminant level (MCL) of 10.0 mg/L for public drinking water systems. While private wells are not subject to this regulation, EPA standards are based on existing health information and can therefore be used to gauge the relative quality of water from private wells. Please see the attached "Nitrate Fact Sheet" for important information regarding nitrate. This advisory must be attached to all copies of the subject Certificate of On- Site Systems Approval. SGS Reft# 1114110001 Client Name Pannone Eng. Srv. Printed Date/Time 08/31/2011 16:48 Project Name/# Fassler Lot 1 Collected Date/Time 08/26/2011 15:30 Client Sample ID Fassler Lot 1 Received Date/Time 08/26/2011 15:55 Matrix Drinking Water Technical Director Steohen C. Ede PWSID 0 Sample Remarks: 4500NO3-F - Total Nitrate/Nitrite - MS recovery is outside of QC criteria. Refer to LCS for accuracy requirements. Allowable Prep Analysis Parameter Results LOQ Units Method Container ID Limits Date Date Init Metals by ICP/MS Arsenic ND 5.00 ug/L EP200.8 C (<10) 08/30/11 08/31/11 NRB Waters Department Total Nitrate/Nitrite-N 6.80 0.100 mg/L SM20 4500NO3-F B (<10) 08/26/11 AYC Microbiology Laboratory E. Coli Total Coliform Negative 1 100mL SM209223B A 08/26/11 DLC Negative 1 100mL SM20 9223B A 08/26/11 DLC I hereby oertify ~ha~ ! have surveyed ~e foLIowing described property: A~Chorage R:e~ordi~ D~s~ri~, ~horage, A~ ~ ~. ~he ~rove- m~ lo'~a~ed ~hereom ~e wi~m the property lim~ ~d do mo~overlap om a~j~cemt property, ~ha~ i~rovemem~s om adjacen~ ~prope~ does encroach on ~he premises in question. O~y '~ements f~m ~ec~d pla~ mhown ~h'im date. ~ / ~ . _ . . .~ ' , ~ ~* · Municipalit3' of Anchorage Development Services Department Building Safety Division On-Sile Water and Wastewater Program 4700 South Bragaw St. P.O. Box 196650 AnchoraGe, AK 99519-6650 ~,wvw.ci.anchora g e.ak.us (907) 343-7904 CERTIFICATE OF HEALTH AUTHORITY APPROVAL FOR A SINGLE FAMILY DWELLING Parcel I.D..-07, S3~. 33 · 1. GENERAL INFORMATION · Complete legal description i Lot t~ Fassler Subdivision Expiration Date: Location (site addre, ss or directions) I~onron Street and Fassler Circle Current Property owner(s) I~It~1&~t Construction Day phone 688-1236 Mailing address P.O. Box 670495 Chugiak, AK 99567 Lending agency Day phone Mailing address Real Estate Agent Day phone Mailing Address Unless othem'ise requested, HAA will be held by DSD for pickup. 2. HUMBER OF BEDROOMS: Three {3) 3. TYPE OF WATER SUPPLY: Individual Well Individual Water Storage Community Class' Public Water System Well TYPE OF WASTEWATER DISPOSAL: [] Individual On-site I'-] Individual Holding tank [] Community On-site [] Public Sewer The Municipality of Anchorage Development Services Depadment (DSD) Issues Cedificates of Health Authority Approval (HAA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. Certificates of Health Authority Approval are required for the transfer of title (except between spouses) for properties served by a single family on-site wastewater disposal and/or water supply system. DSD also issues HAAs upon request to homeowners. Cedificates of Health Authority Approval are valid for 90 days from the date of issue for properties served by a private or Class C weII and may be reissued with new water sample results less than 30 days old. (Certificates may be reissued for a period of up to one year with valid water samples.) Cedificates are valid for one year for properties served by Class A or B weIIs or a public water system. :The Municipality of AnchoraGe is not responsible for errors or omissions in the professional engineer's work. 4. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Health Authority Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is(are} safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage flies and from my investigation and inspection, the on-site water supply and/or wastcwater disposal system is(are} in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm' Anderson Engineering Phone 522.7773 Address P,O. Box 240773 Anchora.qe, AK 99524 Engineer's Printed Name Michael E. Anderson,.P.E. 5. DSD SIGNATURE * Approved for Disapproved. ,.~ bedrooms. Conditional approval for bedrooms, with the following stipulations: Additional Comments Attachments: HAA Checklist Septic System Advisory Well Flow Advisory X Maintenance Agreements ' Supplemental Engineer's Repo~ Other Original Certificate Date:/Z / 7 ! O/ Municipality of Anchorage Development Services Department Building Safety Division On-Site Water & Wastewater Program 4700 South Bragaw St. P.O. Box 196650 Ancherage, AK 99519-6650 ~vw,ci.ancbemge,ak.us (m7) 343-7~04 HEALTH AUTHORITY APPROVAL CHECKLIST Legal Des=iption: WELL DATA Well type Private [3ate completed 7/20/2001 Total depth 181 fl. Date of test Static water level Wlal production WATER S/I~PLE RESULTS: . Colifon~ 0 colonies/100 n~ B. SF. Frrlc/HOLDING TANK DATA Tank Type/Material Se~r.~teel Tank size t,000 gal. Lot t, IFassler Subdivision ff A, B, er C provide PWSID # __ Sanitary seal (Y/N) Cased to 181 It. FROM WELL LOG 7/20/200t 150 20 g.p.m. Nilz'ata I~."Jb mgJ. · C~ected by: ?~ Klmbrouf~h Foundation clean,ut (Y/N) Y_ Damof pu~ng' ' :' Number of Comments _2 Depression over lank (Y/N) N_ Pumper New Conatmctlon C. ABSORPTION FIELD DATA Data insta[led 7/29/2001 Soll rating (g.p.d./ltz er ~/bdrm) t2 GpD/SF Pamel ID: 051-531-32 Wail Log (Y/N) Y Wa'es I~operly protected (Y/N) Y Casing height (above ground) >24 AT INSPECTION g.p.m. Other bacteria 0 c~onies/lO0 mi. Date installed 7/27/2001 Cleanouts (Y/N) Y High water alarm (Y/N) System type Deep Trench lt. Width 3 lt. Gravel below pipe 6 Eft. absorption area 384 ~ Monitoring tube Y_. Depression over field N_ Resuffs (Pass/Fail) Length ~2 Total depth 9.5 fl. Date of adequacy tast Fluid depth in abso~lion field before test in. Water added gal. Elapsed Time: min. Fina~ fluid depth in. Absorption rate Any rejuvenation I~eatment (past 12 mo.) (Y/N & type) N For bedrooms New depth in. ff yes, give date g.p.d. UFT STATION Date installed Size in gallons 'Pump on' level at in. 'Pump off level at __ in. Datum Cycles tested E. SEPARATION DISTANCES SEPARATION DISTANCES FROM WELL ON LOT TO: Septic tankAiff station on lot >t00' Absorption field on lot >t00. Public sewer main N/A Sewer/septic service line >25. Propen'y line 4 Water Service line >10' Cud~in drain. None Noted F. COMMENTS "' See LOt LJ~e Waiver. Manhota/Acc,~_ __ _~ (Y/N) High water alarm level at. Meets alarm & cimuit requirements? On adjacent lots >100' On adjacent lots >100' Public sewer mar~ote/cleanout N/A Holding tank N/A Absorption field >5' Surtace water >t00' Water main >10' Driveway, p~ddng/~ehide st~age >10' SEPARATION DISTANCES FROM SEPTIC/HOLDiNG TANK ON LOT TO: Building foundation >5' Property line >5' Water main N/A Water service line >t0' Wells on adjacent lots >100' SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO: Building foundation ~10' Surface water >100. Wells on adjacent lots >t00' in. G. ENGINEER'S CERTIFICATION I certify that I have determined through field ir~ and review of Munic~oal records that the above systems am in conformance with MOA HAA guidelines in effect on this date. Enginee~.'s Printed N~me Michael E Anders~n, P.E." Date 11/30~1 HAAFee $ ~[~ Waiver Fee $ Date of Payment Receipt Number :1~ NOV-~:9-01. ea.:45PM FI~OkI-CTf, E ENVIRONMENTAL SRV 90?5615301 T-596 P.01/01 F-45t CT&E Ref,# 101SI 10001 Client Nome Ande~on Engineerin~ Project Name/# Lot I FAssler Client Sampla ID Lot ! £essler l~latrllt Drln~ing W~ter Or~ero~ By PwSID 0 ~L Uni~ ~,~thod Client Printed Date/Time 11/20/2001 16:05 Collected Daterflme 11/27/2001 15:45 Received Date/Time 11/27/2001. 16'.25 Technlcel Di~ctorj Stepl~en C. Ede. Allowable PTcp Analysis Limiu D~e Date Init 4.?8 0.500 mg/t. EPA 300.0 (<1o) 11/27/01 SCL Received Time Nov.29. 4:47PM