Loading...
HomeMy WebLinkAboutZANTHA VISTA BLK B LT 3antha VI*sta Block B Lot 3 #015-472-13 �ry Municipality of Anchorage Page 1 of 3 Development Services Department OnSile Water and Wastewater Program 4700 South Bragaw Street P.O. Box 196650 Anchorage, AK 99519-6650 www.d anchorage.ek.us (907) 9437904 ON-SITE WASTEWATER DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT Permit Number. SWO40255 PID Number. 015.472-13 Nwn• Alan C. Trawver Wastewater System: Upgrade Ao.«• 7900 Upper O'Malley Road Anch., AK 99516 ABSORPTION FIELD 346.2404 ours 4 5' Wide Trench LEGAL DESCRIPTION SW Rare 1.2 iaa DwM Man arq.w v.os GawFe 13.5 FI. ff c La Dsph b P" Mahan Ihm ory W pals Crn dWMi M•rwvl pp• B 3 Zantha Vista 9.5 FI. 4 FL TowWp R -W lsq Fill ra•e anw ogrW vsW Griwl Leroft 0.1 FI. 52 FI. Well: Existing Gr•va •,an 5 Nu a Mn.. 1 P.Iro o.lvr••rl bw FI. FL CWwlc•oon (Rma•,A6. CL iaa Dw� C.•a Mr aWW_PW ew F" aW F1. FL 520 Fe ASTM 3034 PVC Orxw Da• 0~ 6W. Wow Lela FL Acres a Systems 7120-2212004 valo wtosa. GMM A GmIiw TANK GPM FI. FI SEPARATION DISTANCES Septic Tank To Sepbc Lin Holding icA r"w From TankStation Tank SewerLlne Anchorage Tank 1,250 W9. >100' >100' NIA >25' Steel Two >100' I >100' WA LIFT STATION — NONE ON LOT La Ln• >5' >5' WA c.l FaviEerm >5' >5' WA c~Dr.l None a. In Bench Mark Ft " Catalan eto Audarl On She Existing Absorption Trench Tied In Concrete Front Porch Stoop. with Diverter Valve. 100.0 FL Engineer's Stamp Inspections by: MEA Dates: 1" 712112004 C � *##0 performed a9ln ` 2n0 712212004 .' L. Department of Health and Human Services approval _ i/. cj MICHAEL E ANDERSON: Revpt�iewed by: 0 Mrn J) ♦ �S No CE -4381 . ��� and approved .. N -,J n Q, Date: a pN �W �. 44444�SSX Municipality of Anchorage Page 2 of 3 DEVEOPMENT SERVICES DEPARTMENT 4700 South Bragaw Street Anchorage, AK. 99519-6655 - 343-7904 On -Site Wastewater Disposal System or Well Inspection Report Permit Number. SWO40255 PID No. 015-472-13 r M O N O O O to MiC LE. IWOER No. CE4n Upper O'Malley Road PLAN AS -BUILT SCALE 1" - 30' r; LO M fV O O O (n LOT 3, BLOCK B, ZANTHA VISTA SUBDIVISION 150.22 5 W IDiver1w Valve CS S2 B st M, I A m IFour Bedroom THw O c Home O O b I' h C6 A I B C S1 16.1 S2 24.2 39.2 140.9 CS 46.6 72.5 M1 39.7 36.3 C6 51.3 40.5 tD I Ezrsung Well I 150.20 ._ N89 55'33"E PLAN AS -BUILT SCALE 1" - 30' r; LO M fV O O O (n LOT 3, BLOCK B, ZANTHA VISTA SUBDIVISION • Municipality of Anchorage Page 3 of 3 DEVEOPMENT SERVICES DEPARTMENT 4700 South Bragaw Street Anchorage, AK. 99519-6655 - 343-7904 On-Site Wastewater Disposal System or Well Inspection Report Permit Number. SW040255 PID No. 015-472-13 104.7 A U N N UL) 2' insul. 1,250 Ilion Septic Tank 98. 8.15 U a r u 106.0 pe t xtlle FaLbHc _ 97.75 Drainfield Rock 7.7 93.7 52' (Trench Length) 87.2 '&�aaaayaa � i 49th • r r............ ........... .. MICINEL L NJOERSON PROFILE AS-BUILT Scale: 1•70' �L."N"• :.� 1 2 3 4 5 6 17 MUNICIPALITY OF ANCHORAGE DEVELOPMENT SERVICES DEPARTMENT 4700 SOUTH BRAGAW STREET ANCHORAGE, ALASKA 99519-6650 SOILS LOG - PERCOLATION TEST PERFORMED FOR: Alan Trawver DATE PERFORMED: 7/20/2004 LEGAL DESCRIPTION: Lot 3, Block B. Zantha Vista Subdivision �T� TEST HOLE # 1 SLOPE SITE PLAN II I I I I I II OG/OLPROJECT # Silty Sand W/Some Gravel SM a' i . ° •• 49th WAS GROUNDWATER ENCOUNTERED? IF YES, WHAT DEPTH? DEPTH OF WATER AFTER MONITORING: DATE: °' ... s.... r ................ . ° ' •. 00....y....... .. • .• •1'C.�s MIC+MEL E. NIDERSON a•,.•• #,-,p No. CE4381 ° BOH -19.5' 0 0 NO None 7/2312004 S L 0 P E Upper O'Malley Road 2% READING DATE GROSS TIME NET TIME DEPTH OF WATER NET DROP Start 7/20 5:33 12' 1 5:43 10 9.25' 2.75' Recharge 5:44 11.75' 2 5:54 10 9" 2.75' Recharge 1 1 5:55 1 1 12' 3 6:05 10 9.25- 2.75- PERC RATE: 3_6 MIN./INCH PERC. HOLE DIAMETER: 6• TEST RUN BETWEEN 7.0 FT. AND 8.0 T. COMMENTS: Test Hale Pre Soaked Prior to Test. TEST PERFORMED BY: MEA I, MICHAFL E. ANDFRSON, CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES ON THIS DATE: 7/23/2004 MUNICIPALITY OF ANCHORAGE Development Services Department On -Site Water 6 Wastewater Program 4700 South Bragaw Street P.O. Box 196650, Anchorage, AK 99519.6650 (907) 343-7904 ON-SITE WASTEWATER DISPOSAL SYSTEM PERMIT Initial ','/alloy AlDOIJ Date Issued: Jul 12, 2004 Expiration Date: Jul 12, 2005 Permit Number: SWO40255 Parcel ID: 015-472-13 Legal Description: `ZANTHA VISTA BLK B LT 3' Design Engineer: 0014 Anderson Engineering Site Address: 007900 UPPER O'MALLEY RD Owner Name: ALAN C. TRAWVER Lot Size: 26250 SQ. FT. Owner Address: 7900 UPPER O'MALLEY RD Total Bedrooms: 4 Permit Bedrooms: 4 ANCHORAGE. AK 99516-1121 This permit is for the construction of. ❑ Disposal Field ❑ Septic Tank ❑ Holding Tank ❑ Privy ❑ Private Well ❑ Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specked in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72 ) and Drinking Water Regulations (18AAC80 ). 3, The engineer must notify DSD at least 2 hours prior to each Inspection. Provide notification by calling (907) 343-7904 ( 24 hours ). ( Not required for a Water Supply Permit only ). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must be either: A. Open and closed on the same day. B. Covered, sealed, and heated to prevent freezing. 5. The following special provisions. A NEW TEST HOLE WITH GROUNDWATER MONITORING AND PERC TEST NEEDS PERFORMED DURING CONTRUCTION FOR A RADIUS OF NO MORE THAN 30 FEET AROUND LOCATION OF PROPOSED SUBSURFACE DISPOSAL AREA Received By: Date: Issued By: an Date: 71#710Y ANDERSON ENGINEERING P.O. BOX 240773 ANCHORAGE, AK 99524 522-7773 522-6779 (F DATE: 7/20/2004 TO: Joe Goodall WITH: MOA/On-Site Water and Wastewater FROM: Mike Anderson SUBJECT: Lot 3, Block B, Zantha Vista Subdivision Septic System Design Revision Permit No. SWO40255 We completed a test hole and percolation test on the subject lot yesterday. The percolation rate was the same as that used in the original design for the revised system (3 min./inch). We are revising the design of the upgrade to a 50' long x 5' wide x 4' effective depth trench. The location will be the same as that shown on the site plan previously submitted. Please revise the permit to allow the revised configuration of the absorption trench. All documentation for the new test hole, percolation test and water monitoring will be submitted with the certified as -built. Municipality of Anchorage Development Services Department Building Safety Division On -Site Water and Wastewater Program 4700 South Bragaw SL P.O. Box 196650 Anchorage, AK 99519-6650 www.ci.anchorage.ak.us (907) 343-7904 ON-SITE SEWER/WELL PERMIT APPLICATION FOR A SINGLE FAMILY DWELLING Parcel I.D. 015472.13 Permit Number SW Property owner(s) Alan C. Trawver Day phone 3462404 Mailing address (1)79000ooerO'IMatkrPOW AndorKMAKN516 Mailing address (2) Zip Code Legal description (Lot, Block & Sub'd.) Lot 3. Mock B, Zanda Vista SeEavision Legal description (Section, Township & Range) Lot Size_ Zra6DA Sq.FI THIS APPLICATION IS FOR: Number of Bedrooms Four (4) Currently Three Bedrooms Sewer Only ❑ Well Only ❑ Sewer and Well ❑ Water Storage ❑ Sewer Upgrade ID THIS PROPERTY CONTAINS: Hot Tub ❑ Jacuzzi ❑ Swimming Pool ❑ Water Softening Unit ❑ Therapy Pool ❑ I certify that the above information is correct. I further certify that this application is being made for a Single Family Dwelling and is in accordance with applicable Municipal Codes. (Signature of property owner or authorized agent) Permit Fees: g qt L) Waiver Fees: Date of Payment -/ - 1, - 0y Date of Payment Receipt Number: k )-To i�f f Receipt Number. (Rev.12MM ANDERSON ENGINEERING P.O. BOX 240773 ANCHORAGE, AK 99524 522-7773 522.6779 FAX July 3, 2004 Municipality of Anchorage Development Services Department On -Site Water and Wastewater Program 4700 South Bragaw Street Anchorage, AK 99519-6650 Subject: Lot 3, Block B, Zantha Vista Subdivision Septic System Design and Permit Application Impacts to Adjacent Properties Dear Onsite Services Engineer: The owner of Lot 3, Block B, Zantha Vista Subdivision intends to upgrade his existing septic system. The existing system, constructed in 1976 is still functioning adequately, but the owner is concerned about future problems. We are therefore requesting a permit be issued for the construction of a new septic system to serve the home. The Site Plan and backup documentation identify the location and configuration of the proposed and existing septic system. No conflicts between the new septic system and other systems or wells in the area have been noted. Existing drainage arrows and the current drainage pattern are also identified on the Site Plan. The drainage pattern will be maintained after development of the new system is complete. A Test hole placed near the location of the absorption trench in 1976 indicated sandy silt and silty sandy gravel. The accepting soils were tested and found to have a percolation rate of less than 5 minutes per inch. No groundwater was found during excavation and none was noted during the monitoring period. We will place a new test hole during the construction of the new absorption trench to verify soil conditions and the lack of bedrock and groundwater. Our design includes the placement of a new 1,250 -gallon septic tank along with a new 32' long by 3' wide by 8' effective depth absorption trench to collect and treat the sewage generated in the house. The bottom of the trench will be 13' below the surface. The distribution pipe will be 5' below the surface. A flow diverter valve will be installed and the existing absorption trench tied in to the new system for possible future use. A minimum of 3' of cover will be placed atop the trenches and a minimum of 4' of cover will be placed atop the new septic tank. The ground surface on the lot slopes at grades from 2% to 5% from east to west in the Lot 3, Block B, Zantha Vista Subdivision July 3, 2004 Page Two area of the absorption trench. The new absorption trench will be constructed parallel with the slope of the ground surface as much as possible in conformance with Municipal requirements. The new septic system will be constructed 100' from all wells and surface water. It will also be constructed a minimum of 10' from any water service in the area. If the system is constructed in accordance with our design the following statements apply: 1. The system, if constructed as designed, will have no adverse impact on the wells in the area or those to be constructed in the future. 2. The system, if constructed as designed, will have no adverse impact on existing septic systems in the area or those to be constructed in the future. 3. The system, if constructed as designed, will have no adverse impact on reserve space, either surface or subsurface, on any lots located in the area. 4. The system, if constructed as designed, will have no adverse impact on drainage patterns in the area. The current drainage pattern will be maintained. Sincerely, rY W1011 i Michael E. Anderson, P.E. Attachments AEE E. ANDERSON N0. CE -48' J Upper O'Malley Road 5n5.0 ,)22 'e7 r � 2 m i SO20 .0 0 g B N55 104 52 ng 42 105M Ewe 40 o 2 • N � (2L301) W G N19 9 E 25955 Z 2 O tiP co 1 a 5 Y (7L201) 1 2975s N55)S 37-E 7002 _W S", 295 Bz U51( 10" EY• 1 6 • 4 1 „. ��.: .. AREA MAP g°tiNo. MI � 2 SCALE 1• = 100' hti ..•.% ZANTHA VISTA SUBDIVISION LOT 3, BLOCK B Upper O'Malley Road 150.22 IB' TH W� I s o Eals2 enk.b Four Bedroom I W i go Home (Currentl c N 0 0 0> 00 Three Bedroo s) I o0 vn c I m 150.20 .vW may N89 55'33"E i 4` • NO. CEl r SITE PLAN SCALE 1. _ 40' LOT 3, BLOCK B, ZANTHA VISTA SUBDIVISION DESIGN FACTORS: SYSTEM REQUIREMENTS: Four Bedroom House Deep Trench System Perc. Rate: 2.5 Min./inch 1,250 Gallon Septic Tank Application Rate: 1.2 GPO/SF 8' Drainfiekt Rock 4 Bedrooms X 150 GPD/1.2 GPD/SF (Application Rate) = 500 SF Absorption Area 500SF/16 SF/LF - 31.25 LF Trench Length THEREFORE: Construct a 32' Long x 3' Wide x 8' Effective Depth Absorption Trench. Flow Line Elevation in Trenches to be 5'Below Original Ground Surface. Total Depth to be 13' Below Existing Ground. Place Diverter Splitter Valve to lie in Existing Trench. Provide 3' of Cover Over Trench and 4' Over Septic Tank or Provide 2" Insulation and 2' of Cover. Maintain 100' Separation Between Existing Well On Lot and Septic Tank and Absorption Trench. Natural Backfill 4'6" Geotextile Fabric 6" 4" Perforated PVC (Holes Down) aci 14:40%1 Drainfield Rock NOTE: Grade Area Over Trench to Drain Away. Minimum 6' Separation From Bedrock. Minimum 4' Separation From Groundwater. Minimum 100' Separation From Wells in the Area. Minimum 100' Separation From Surface Water or Streams. . Minimum 10' Separation From Water Service Line. ON-SITE WASTEWATER DISPOSAL SYSTEM CONSTRUCTION AND MATERIAL SPECIFICATIONS SUBJECT: LOT 3, BLOCK B, ZANTHA VISTA SUBDIVISION GENERAL: The scope of this project includes the removal and abandonment of the existing septic tank on the lot and the procurement and placement of a new 1,250 -gallon septic tank at the location shown on the Site Plan. Work also includes the construction of a new 32' long X 3' wide X 8' effective depth absorption trench at the location also shown on the Site Plan. The distribution line in the trench will be placed at 5' below the existing ground surface. Total depth of the trench will be 13' below the existing ground surface. A flow diverter valve must be placed to provide a connection to the existing trench for possible future use. The new absorption trench must be placed a minimum of 100' from the well on this and adjacent lots. A minimum of 100' must separate any surface water in the area and the septic tank and absorption trench. The trench must be a minimum of 10' from the lot line. Care must be taken to preserve as many of the existing trees and vegetative buffer as possible. 2. Construction shall be in accordance with the approved site plan, design drawings, Municipal Permit with any special provisions or conditions, and all applicable State and Municipal Wastewater Disposal Regulations. 3. The Contractor shall be responsible for obtaining all underground utility locates and for the layout of the septic system and verification of the location of all lot lines. The Contractor must also verify the location of wells in the area and assure that the separation distances are met. 4. Unless specifically agreed otherwise, the contractor shall be responsible for final grading areas subsequently depressed from soil settling. Property owner shall be responsible for revegetation of affected areas unless specifically agreed otherwise. 5. Contractors installing wastewater disposal systems must be certified by the Municipal Department of Health and Human Services for system installations. Owners installing their own systems must receive prior approval from D.H.H.S. before beginning system installation. SEPTIC TANK INSTALLATION A new 1,250 -gallon septic tank must be procured from an approved source and installed at the location shown. Lot 3, Block B, Zantha Vista Subdivision July 3, 2004 Page 2 of 3 2. A septic tank is to be constructed by a certified septic tank manufacturer. Construction shall include two 4" cleanouts for pumping access. 3. The septic tank shall be sufficiently bedded to prevent settling or shifting of the tank. 4. All standpipes on the septic tank shall extend a minimum of 12 inches above final grade. 5. Tanks installed without 4' of cover shall have a minimum of 2" of direct burial insulation. 6. A foundation cleanout shalt be installed one to four feet from the building foundation. Two cleanouts are required between the tank and the drainfield. 7. Final grading over the tank shall be such that a positive slope exists away from the septic tank. DRAINFIELD CONSTRUCTION: 1. The drainfield shall be constructed to the dimensions shown on the design. The bottom of the trench shall be within 2" of level. 2. Distribution piping must be placed level with perforations down atop a level bed of drainfield rock. Rock should then be placed over the pipe to provide a minimum of 2" of cover. 3. A silt barrier or geotextile fabric must be placed between the drainfield rock and the natural soil backfill. 4. Monitor tubes must be 4" in diameter and installed at the locations shown on the design. The portion below ground must be perforated. 5. Contractor shall verify the septic tank and drainfield are a minimum 100' away from any private water wells in the area, 150' from a Class "C" Well or 200' from any community well. 6. Direct bury insulation must be placed over the distribution system if less than 3' of backfill depth is available. Finish grade over the trench must be mounded to prevent settlement or depressions. 7. Grade area surrounding the absorption trench to drain away. 8. A minimum 2' of accepting soil is required below the drainfield rock for a 5' wide trench. Contractor shall verify this condition prior to placement of the rock. All pockets of unacceptable materials must be removed and replaced. Lot 3, Block B, Zantha Vista Subdivision July 3, 2004 Page 3 of 3 MATERIAL SPECIFICATIONS: Septic tanks must be constructed by a municipally approved septic tank manufacturer. 2. The following pipe materials are approved for use in septic system installations in the Municipality of Anchorage: Cast Iron (perforated and solid), ASTM D3034 or P.V.C. (perforated and solid), ASTM F810 or H.D.P.E. (perforated, but not solid) and ASTM D2662 or A.B.S. (perforated and solid). 3. Insulation shall be at least 2" thick extruded direct burial polystyrene (Dow Chemical Co. Styrofoam HI or equal). 4. Septic tank inlets and outlets shall be fitted with watertight couplings (Caulder, Femco, or equal). 5. A permeable geotextile fabric (Typar. Mirafi or equal) must be installed between the final drain rock layer and the native soil layer. 6. All drain rock shall be .5" to 2.5" in diameter with less than 3% passing the #200 sieve. INSPECTIONS: Municipal Ordinance requires a minimum of two inspections. These inspections must be conducted under the supervision of a professional engineer registered in the State of Alaska. The first inspection must be conducted after the excavation of trenches, beds or pits and before the installation of any gravel. A septic tank may be set in place, but may not be backfilled. The second inspection must be conducted after the placement of the geotextile fabric, gravel, distribution piping, standpipes, cleanouts and insulation. No backfill should be in place at the time of inspection. Contractor shall provide a copy of all field survey layout and construction notes for use in preparing the certified as -built of the completed system. ® ,� Municipality of Anchorage AL Department of Health and Human Services 825'1.' Street P.O. Box 196650 Anchorage, Alaska 99519-6650 Rick Mystrom hnpJMww.cl.anchorage.ak.us Mayor Permit Number. #SW Date of Issue: Parcel Identification Number. Date Started: 4-24-01 Date Completed- 4-27-01 Is well located at approved permit location? ® Yes ❑ No Legal Description: Zan Vista B/k B Lot 3 Property Owner Name & Address: Alan C. Trawver 7900 Upper O'Malley Anchorage. Ak 99516 Borehole Data: Depth (ft} Method of Drilling ® air rotary ❑ cable tool Soil Typc, Thickness & Watcr Strata From To Casing type: steel stick-up 0 2 Wall Thickness: .025 inches Existing well 2 95 Diameter: 6 inches Depth: 63 feet Bedrock 95 246 Liner Type: Diameter: inches Depth: feet Casing stickup above ground: 2 feet Static water level (from ground level): 47 feet Pumping level: 246 feet after 4 hours pumping 1_5 gpm Recovery Rate: 1_5 gpm Method of Testing: airlift Well Intake Opening Type: ® Open End ® Open Bole ❑ Screened Start feet Stopped feet ® Perforations Start 58 feet Stopped 64 feet Grout Type: Bentonite # 8 Volume: 1 he Depth: Start0 feet Stopped ± feet Pump: Intake Depth feet Pump size hp Brand Name Well Disinfected Upon Completion? ® Yes ❑ No Method of Disinfection: Clorine Tablets Comments: Reperforated original perforations from 58- 59 new to 64. Most of the water appears to be coming from bedrock. Well Driller: Alpine Drilling & Enterprises P O Box 110496 Anchorage AK 99511 Attention: The well driller shall provide a well log to the property owner within 30 days of completion and the property ^%v nr /leo ivnll r1r:11, 41,011 nrnVVIP O uAl 1M }n fh. ni t nr[toolfh R, U.1mon Cnrvlr. Iwfhin An clove nfnmm�66An WELL LOCAT WATER WELL LOG FOSS DRILLING 1336 Ingra Street Anchorage, Alaska 99501 SIZE OF CASINGDEPTH OF HOLEFT. CASEI) TOi�jFT. STATIC WATER LEVEL_FT. YIELD IyoZ GALoPER.MIN. WITH_�_� FEET OF DRAWDOWN. I -Y- _ A� ) i + L_. L DATE COMPLETED s�j& PUMP TO BE SET AT—SE. _z:6 `r'�tOS GREG d ANCHORAGE AREA BM,jGW H16 � Department of Environmental Quality 3330 C Street Anchorage, Alaska 99503 - INSPECTION REPORT CSN -SITE SEWAGE DISPOSAL SYSTEM NAME LOCATION SEPTIC TANK: MAILING ADDRESS LEGAL DESCRIPTION PHONE rJ Z - DISTANCE {r, 1"`-'{/ OF FROM WELL MANUFACTURER _ L7A�!'�<' ) ,- NUMBER _MATERIAL �I�L�,I�� COMPARTMENTS INSIDE LENGTH_—_ INSIDE WIDTH LIQUID DEPTH _ -___LIQUID CAPACITY_ f1�)0 GALLONS. ~ p/� ---- SFF.J'1T: 'PtAoagg /� �./ % 7 NUMBER OF RkT3—�. DIAMETER —_OR WIDTH, , LENGTH S DEPTH _ �• � /,rhr, . LINING MATERIAL __�—may-_ CRIB SIZE: DIAMETER {{__DEPTH-__ DISTANCE FROM: WELL 14-? f r BUILDING FOUNDATION._Jor; NEAREST LOT LINE -2 w ABSORPTION - TOTAL CAREA (WALL AREA) SQ. FT. ADDITIONAL ABSORPTION WELL: TYPE //(!/_/ �CONSTRUCTION_— O 2- DEPTH --_DISTANCE FROM BUILDING FOUNDATION LOT LSEPTICEST NEAREST INE SEWER I INE TANKJUQ1 . SYSTEMSEEPAG!ll%W) ! / CESSPOOL [, OTHER SOURCES — APPROVED ___ DISAPPROVED --_ REMARKS _,-�i�7�hz ,��%�- ��)iQ>�' �'+��-- DISTANCES: ��<-� LJ�es/ DIAGRAM OF SYSTEM INSTALLED BY: O(IG Ck PIPE MATERIAL: LOT SLOPE:/JC�l - F- ' REMARKS: qtr ) Form No. EQ -031 N-° II W._tl Y-�I :Ji: n.�-?•� a N`'N 1_.__ :N�. 71... ° � ° A,.,A Lr= 1=1 W"'4 A_: Y"'h ..__7 K Y,:4®:3 Y':�: � .. C-UPFIRT-MEN'T OF HEALTH AND ENVIRONMENTAL F'ROTEEI: TI.E]"td plc') r >� � Fi ,,a . t ,,:�,:1.F_u E. TLIF,�:�r? F: ANCHORAGE, IIF ��4Ar 2."6-2221I k_ '"t -UE: Lc EE EA IEE FT Y:.,,: N:i:_:: m II ^ 1 :IE: N'- _:... PERMIT NO. K 81 APPLICANT THOMAS HUNTER ,.'._� 2308 ROOSEVELT .:.:,i Yr-¢;...;�r';L. LOCATION I..1F-'F'E.R n:1•'rA,LLF:li' I...E.GIAL:. L3 BB ;c r'it•NTHA ISTA:.: : S L.I:'rr SIZE ,... F'i•.....::. [u_IL-1rF' FE:r--: F T'YP'E: OF ;;OI:L. ABSORBTION :`',STEM IS: TRENCH MAXIMUM NUMBER OF BEDfe:Itt.:MS :'iOI:L.. RATING C SQ FT?BR> = 151 THE: h:L•:GILI.F;RED SIZE OF THE SOIL ABSORPTION N SYSTEM I.;: .::N.. IS W._. N:c:: Y'..,II A:b --1- tl....1 ---- - N... n.:� W=�" p_N'•.^° W:1_. W= _ F" ...I'" II—N :=_- f', THE LENGTH DIMENSION 15 THE:: LENGTH u:IN FEET) OF THE T"♦<:Ga,CH OR DRA:ENF':I:Ei:L..D. THE EiEPTT"N OF A TRENCH OR PIT- 15 THE: DISTANCE BETWEEN THE :E,URF'FII::E OF THE: (:dRE,11.1t'ND AND THE BOTTOM OF THE EXCAVATION (IN FEET). THERE IS NO SET WIDTH FI_t1' TRENCHES. THE GRAVEL DEPTH 15 THE: MINIMUM DEPTH OF GRAVEL BETWEEN THE OUTFALL PIPE:: AND THE BOTTOM OF THE EXCAVATION 0N FEET). L;Fu:KF-IL.L...ING OF ANY :SYSTEM WITHOUT FItNAL. INSPECTION AND APPF:OVPTL. BY THIS DEPARTMENT WILL BE SUBJECT TO PROSECUTION. MINIMUM DISTANCE BETWEEN A WELL. AND ANY ON—SITE SE.LdAGE. DISPOSAL SYSTEM IS: 100 FEET- FOR A PRIVATE: WEL..L.. OR 200 FEET FOR A PUBLIC WEI_I_.. WELL COGS ARE REQUIRED AND MUST BE: RETURNED TO T'HFE. DEPARTMENT ('.I:I:TI-IIN 30 DAYS OF THE WE;L...L.., COMPLETION. SPECIFICATIONS AND CONSTRUCTION DIAGRAMS ARE AVAILABLE TO IN`;1.-1fsE F:F:Cif:ER INSTALLATION, ".Y''R N —N.... N'.cu.:AY A: HPYkr T CERTIFY THAI 1: 1 FIM FAMILIAR WITH THE REQUIREMENTS FOR ON—SITE SEWERS AND WELLS AS SET FORTH BY THE MUNICIPALITY OF Fit+CHORnOE:, 1 WILL INSTALL THE SYSTEM IN ACCORDANCE WITH THE CODES. . ,:-, _:E.4�.LEi(=: _.r_,TE11 h1A, F:Ea>tl._IIF?E: F..:NL_f=1F:(iil'_L''1FYd-I' .T.F 'rLllic: >. UNDERSTAND TbltlT" '1"rIF.F Otd—::;:f."CE RESIDENCE: IS RE.'MODEL..jj,j;jj;:jjDE MORE THAN 3 BE:C�F:`.00MS�. APPL..ICAN"I" T'A: Iss1_IEE, E1Y._ arswif --------- ..EFrrE..... ...... _�, _- .. ... _7eg 249 EAST SIST AVENUE P.O. BOX 8007 ANCHORAGE. ALASKA 99503 l"FI.EPHONE 907-279-0483 TELEX 090-35410 May 28, 1976 Mr. Carl Luchsinger Box 94 SRA Anchorage, Alaska R & M No. 656242 RE: Test Hole and Soil Log Report for Sanitary System Lot 3 Block B Zawtha Vista Subdivision Dear Mr. Luchsinger: We are submitting herewith the boring logs, percolation results and our comments regarding soil conditions encountered at the subject site. This investigation was performed in accordance with your request of May 17, 1976, and those procedures outlined in a letter dated July 15, 1976, by Mr. Rolf Strickland of the Municipality of Anchorage, Department of Environmental Quality. A single test hole was put down within the Lot 3 area for the purpose of defining gneeral subsurface soil condition and conduction percolation tests for the proposed sanitary system. Excavation was accomplished with a tractor mounted auger type drilling rig and the test hole was extended to a total depth of 19 feet below ground surface. The final log prepared for the test hole has been included in Drawing A-01. Ground water was not encountered in the test hole. We appreciate being given this opportunity to be of service to you. Should you have any question with reqard to the above, please do not hesitate to contact us. Very truly yours, R & M CONSULTANTS, INC. James W. Rooney Vice President JWR/PJ/pe xc: Municipality of Anchorage AN FAIIIIJANKS COI�VSUI�.CANTti, INC;. JUNEAU 249 EAST SIST AVENUE P.O. BOX 8007 ANCHORAGE. ALASKA 99503 l"FI.EPHONE 907-279-0483 TELEX 090-35410 May 28, 1976 Mr. Carl Luchsinger Box 94 SRA Anchorage, Alaska R & M No. 656242 RE: Test Hole and Soil Log Report for Sanitary System Lot 3 Block B Zawtha Vista Subdivision Dear Mr. Luchsinger: We are submitting herewith the boring logs, percolation results and our comments regarding soil conditions encountered at the subject site. This investigation was performed in accordance with your request of May 17, 1976, and those procedures outlined in a letter dated July 15, 1976, by Mr. Rolf Strickland of the Municipality of Anchorage, Department of Environmental Quality. A single test hole was put down within the Lot 3 area for the purpose of defining gneeral subsurface soil condition and conduction percolation tests for the proposed sanitary system. Excavation was accomplished with a tractor mounted auger type drilling rig and the test hole was extended to a total depth of 19 feet below ground surface. The final log prepared for the test hole has been included in Drawing A-01. Ground water was not encountered in the test hole. We appreciate being given this opportunity to be of service to you. Should you have any question with reqard to the above, please do not hesitate to contact us. Very truly yours, R & M CONSULTANTS, INC. James W. Rooney Vice President JWR/PJ/pe xc: Municipality of Anchorage 0 I L SNOW LINE DRIVE Log Represents Location of Test Hole Zawtha Vista Subdivision CKD: pT DATE: C-1-7 SCALE1.1"=3' _.iIIz ��2,. 1� rl ': �1 %%Oe I R &M CONBULTANTH. INC. TH 1 0.0' ORGANICS (PT) �— ----- -----0.5' SANDY SILT (ML) — — — — — — — —.---7.5' SILTY SANDY GRAVEL (Q'4) --------------13.5' SAND W/SOME SILT SILTY SANDY GRAVEL (GM) �-----------15.0' SAND W/TRACE SILT AND GRAVEL (SP) -- ---16.5 SANDY GRAVEL W/TRACE SILT (GM GW) (160) 19.0'M No Water Table .I Log of Test Hole Carl Luchsinger ?nchorage, Alaska F, B. GRID PRO•.I. NO. DWG. NO. PERCOLATION TEST CARL LUCHSINGER R & M NO. 656242 ELAPSED DROP TIME TIME INCHES 2:30 0 0 2:31 1 3 2:.32 1 2 1/2 2:33 1 2 2:34 1 1 3/4 2:35 1 11/2 2:40 5 3 1/2 2:45 5 2 2:50 5 1. 1/2 2:55 5 1 1/4 5 —1- 3:05 5 3:.10 5 3:15 5 3/4 3:20 5 3/4 3:25 5 0/23:30 5 60 Minutes, 24 1/2 Total Drop Lot 3 Block B Zawtha Vista Subdivision l Jop�A 1) M6 Lln, dusl� jaol&P _---------� INSPECTION APPOINTMENTS DATE RECEIVED TIME - TIME /' i ��k, TIME DATE �C�n DATE 4 7 -fid �i�uYu — DATE INSPE/CAOR INSPECTOR -- INSPECTOR jAU?4181144614 GF CpUunR - MUNICIPALITY OF ANCHORAGE DEPT* F�VIRONMENI',SL fl:JIECTION Of- R_ALTII & DEPARTMENT OF HEALTH &ENVIRONMENTAL PROTECTION' - 825 L Street - Anchorage, Alaska 99501 Three ❑ Six --------- ENVIRONMENTAL SANITATION DIVISION Telephone 264-4720 I� v 19_ E _ REQUEST FOR APPROVAL OF INDIVIDUAL WATER AND SEWER FACILITIES DIRECTIONS: Complete all parts on page 1. Incomplete requests will not be processed. Please allow ten (10) days for processing. 1. PROPERTY OWNER /R -- PHONE MAI LING F`�Dr$�.�SS - j /C ( C/ l p A P� PHO'NI C[/ / �7 PR"LZV �S N�f dif7 renFj�f'r1rp above) ,I t, 4A &A v m� ?6O jar T'fJ C, 'IK� ! Idyl "(^ V �` PHONE 2. BUYER Y�e�wu,wJ r _ MAILING ADDRESS --. 3. LENDI/NGG INS/TIT�UTTION 1;.^(/.�► �1 -{/�� / PHONE j Le MAILING ADDRESS k�s 13- 4. REALTORIAGEjJT PHONE — AILING ADDR F,SS, ��Na ;nG k(zD/�"'I��`^e' / 5. LEGAL DESCR1-0- 3 -6 ( 6 ' f -- (4 ✓"r" S 1 STREET LOCATION - -A - (Z) --_ 6. TYPE OF RESIDENCE NUMBER OF,BECROOMS ❑ One ❑ Four ❑ Other__ SINGLE FAMILY - ❑ Two ❑ Five - ❑ MULTIPLE FAMILY Three ❑ Six --------- 7, WATER SUPPLY X INDIVIDUAL' -- �' ATTACH WELL LOG. A well log is required for all wells drilled ❑ COMMUNITY since June 1975. For wells drilled prior to that date, give well ❑ PUBLIC UTILITY depth (attach log if available.) — 8. SEWAGE DISPOSAL SYSTEM 5uMlv4qR /97G INSTALLED. INDIVIDUAL/ON-SITE" YEAR ON-SITE SYSTEM WAS ❑ PUBLICUTILITY J`_n�. NOTE: THE INSPECTION FEE MUST ACCOMPANY EACH REQUEST BEFORE PROCESSING CAN BE INITIATED. 72-010 (Rev. 6/79) _ _ ti I THIS SIDE FOR OFFICIAL USE ONLY 1. TYPE OF RESIDENCE ❑ SINGLEFAMILY ❑ MULTIPLE FAMILY NUMBER OF BEDROOMS ❑ ONE ❑ THREE ❑ FIVE ❑ OTHER ❑ TWO ❑ FOUR ❑ SIX 2. WATER SUPPLY ❑ INDIVIDUAL ❑ COMMUNITY ❑ PUBLIC UTILITY Connection Verified PERMIT NUMBER DEPTH OF WELL DATE DRI LLED LOG RECEIVED 3. SEWAGE DISPOSAL SYSTEM ❑INDIVIDUAL/ON-SITE ❑PUBLIC UTILITY Connection Verified PERMIT NUMBER DATEINSTALLED INSTALLER ❑Septic Tank or El Holding Tank Size: If Tank is homemade give dimensions: SOILS RATING TYPE OF TANK MANUFACTURER TOTAL ABSORPTION AREA MATERIAL 4. DISTANCES WELL T0: Septic/Holding Tank Absorption Area Sewer Line Nearest Lot Line Absorption Area to nearest Lot Line 5. COMMENTS 11�- APPROVED FOR BEDROOMS ❑ CONDITIONAL APPROVAL (letter.must accompany certificate) ❑ DISAPPROVED DATE BY 72-010 (Rev. 6/79)