HomeMy WebLinkAboutEAGLE CREST #1 TR A LT 64Eagl Crest TPact A Lot 64 #050-304-27 MUNICIPALITY OF ANCHORAGE Department of Health and Human Services On-Site Services Program 825 L Street, R~orn 502 P.O. Box 196650, Anchorage, AK 99519-6650 (907) 3434744 ON-SITE WASTEWATER DISPOSAL SYSTEM PERMIT Upgrade Date Issued: Jul 12, 2000 Expiration Date: Jul 12, 2001 Permit Number: SW000228 Legal Description: EAGLE CREST #1 TR ALT 64 Design Engineer: 0003 S & S Engineering Owner Name: Clyde Armistead Owner Address: 19432 1st St. Eagle River, AK 99577-8429 Parcel ID: 050-304-27 Site Address: 019432 FIRST ST Lot Size: 17820 SQ. FT. Total Bedrooms: 4 Permit Bedrooms: 4 This permit is for the construction of: [] Disposal Field [] Septic Tank [] Holding Tank [] Privy [] Private Well [] Water Storage All construction must be in accordance with: 1. The attached approved design. 2. Ail requirements specified In Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations ( 18AAC72 ) and Drinking Water Regulations ( 18AAC80 ). 3. The engineer must notify DHHS at least 2 hours prior to each inspection. Provide notification by calling (907) 343-4744 ( 24 hours ). ( Not required for a Water Supply Permit only ). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must be either: A. Open and closed on the same day. B. Covered, sealed, and heated to prevent freezing. Received By: Issued By: Date: Date:~ R~ck ~,qystrom. Mayor Municipali of Anchorage Department of Health and Human Services 825 'L" Street P.O, Box 196650 Anchorage. Alaska 99519-6650 hltp:l/www ci.anchorage.ak.us July 13, 2000 Bob Cowan S & S Engineering 17034 Eagle River Loop Rd., Suite 204 Eagle River, AK 99577 Subject.' Waiver Request for Eagle Crest # 1, Lot 64, Tract A Waiver Request #WR000044 Parcel ID #050-304-27 SW000228 Dear Mr. Cowan: Your request for a waiver of the required 10 feet horizontal separation from the on-site wastewater disposal system to property line has been approved. The approved separation distance is 0.0 feet. This waiver approval applies to the existing on-site wastewaterdisposal system to property line separation only. Any furore upgrade to the on-site wastewater disposal system will require all separation distances be met or another approval from this department. If there are any further concerns or questions regarding this waiver, please call our office at 343-4744. Sincerely, Daniel J. Roth Civil Engineer On-Site Water Quality Program MUN~CIPAUTY OF ANCHORAGE Department of Health & Human Eawice$ On-Site Services Waiver Review Worksheet WR#: WR000044 PID~: 050-304-27 HA~. Date Received: Juno 28~ 2000 Legal Description: Eagle Crest #1~ Lot 64~ Tract A Engineer:. S & S Engineering 17034 Eagle River Loop Road~ Suite 204~ Eagle River~ AK 99577 Applicant: Clyde Armlatesd Waiver Requested: 0 foot lot-line waiver Pennit~: 5t~D22,~ Criteria: 1. Geology Poinls: A. Water Table B. Soil Sorption C. Permeability D. Water Table Gradient E. Horizon[al Separation 2. Special Conditions: 3. Other. Tol~l: Waiver is Granted: List Conditions or Reasons for above: Waiver is not Granted: Rec~: 06173 Amount: $115.00 Name of Reviewer Date Paid: 06128/00 June 27, 2000 ROBERT C. COWAN. P.E. CML ENGINEERS (907) 694-2979 FAX (907) 694-1211 MUNICn~ALITY OF ANCHORAGE Department of Health and Human Services P.O. Box 196650 Anchorage, AK. 99519 REFERENCE: Lot 64, Tract A, Eagle Crest Subdivision It is requested that you issue a permlt to upgrade a septic system to serve the existing four bedroom dwelling on the referenced property. A lot line waiver to zero feet is also requested. Bollards will be Installed to prevent vehicles from driving over the leachfield. One test hole was excavated and a percolation test was performed on 6/13/00. The approximate location of the test hole is located on the attached site plan. Ground water was monitored and after seven days the hole was dry as shown on the attached soils logs. We do not anticipate any adverse effects on neighboring wells, septic systems, reserve areas or drainage patterns by the installation of the proposed septic system. The construction of this system will not prevent any future development on any of the adjacent properties. If you require additional information, please contact us. Sincerely, Robe~ C. Cowan, P.E. RCCCo Enclosure 17034 NORTH EAGLE RIVER LOOP * SUITE 204 * EAGLE RIVER, ALA.~ KA 99577 B.J.J. R.C.C. 6-6-00 1 OF 1 rring DESIGN CRITERIA: REVISED: 6-26-00 ~RU~URES, E~EMEN~. OR ~NCROACHMEN~ 4 BDRM = 600 GPD suo~N ON Tills SITE P~N ARE ~ SHOWN ON / PRIOR Tq ANY ~CAVATION 9.5' EFFECTIVE -- ,~ ___J~ _.~/ ~/ / 2.0' WIDE ~ ~ _ SEPTIC ~SEMENT FOR USE ~/ 26.5' LONG ~~ OF LOT 65 TO BE VACATED ~/ ~,.,, ', ~X~ X, .o~1 ~ ~ t ~m ~a " ~- ~ '""~"""- -' LOT 3 / ~' I FLOOR .~ ......... .... / + 1- ..... LOT 76 LOT ~? XA_ LOT GARAGE WrrH UPPER FLOOR Municlpalily Gl ARchorage DEPARTMENT OF HEAL'III & HUMAN SERVICES 825 "L" Sireel0 Anchorage. Alaska 99502-0650 SOILS LOG -- PERCOLATION TEST 5 6 7 8 10 20- DATE PERFORM Township. Range. Seclion: ~...~ ~) SLOPE SITE PLAN WAS GROUND WATER ENCOUNTERED?~.L DEPIII? pO E 0epth Io Waler Alter PERCOLATIONRAIE __ (mmuleUmChII'ERCIIOLEDIAMEIEll ~'~ 1E$1 RUN BEIWEEN /~ I:1 AND ~ FI ROBERT C. COWAN. P.E. CML ENGINEERS (907) 694-2979 FAX (907) 694-1211 ON-SITE WASTEWATER DISPOSAL SYSTEM CONSTRUCTION PRACTICES and MATERIAL SPECIFICATIONS REFERENCE: Lot 64, Tract A, Eagle Crest S/D June 26, 2000 GENERAL: The scope of this project includes the abandonment of the existing septic tank, installation of a new 1300 gallon Premier polyethylene septic tank, and installation of a new trench to serve the existing four bedroom residence located on the referenced property. Construction shall be in accordance with the approved site plan and design drawings, Municipal permit with any special provisions or conditions, and all applicable State and Municipal Wastewater Disposal Regulations. The conWactor shall be responsible for obtaining any necessary underground utility locates. Unless specifically agreed otherwise, the property owner shall be responsible for final grading areas subsequently depressed from soil settling. Contractors installing wastewater disposal systems must be certified by the Municipal Health Department for system installations. Owners installing their own systems must also receive prior approval fi'om the Municipal Health Depa~h.ent. SEPTIC TANK INSTALLATION: A septic tank is to be constructed by a certified septic tank manufacturer. Construction shall include two 4" cleunouts for pumping access. 17034 NORTH EAGLE RIVER lOOP · SUITE 204 * EAGLE FUVER, ALASKA gg577 Page 2 Lot 64, Tract A, Eagle Crest June 26, 2000 2. The septic tank shall be sufficiently bedded to prevent settling or shifting of the tank. All standpipes on the septic tank shall extend a minimum of 12 inches above final grade. Septic tanks installed with less than 4 fi. of cover shall be insulated. A foundation eleanout shall be installed one to four feet from the building foundation. In the line between the tank and the leachfield there shall be two adjacent cleanouts (unless an effluent pumping system exists within the septic tank). These cleanouts shall be located on undistuffoed soil not more than 10 ft. from the tank. The first cleanout, in line, shall be to clean toward the leachfield. The second cleanout shall be to clean toward the septic tank. Final grading over the septic tank shall be such that a positive slope exists away from the septic tank. ABSORPTION TRENCH/DRAINFIELD INSTALLATION: Excavate the proposed trench to the dimensions shown on the design. The bottom of the excavation shall be within 2 inches of level. If the sidewalls of the excavation become smeared, they must be raked or scratched (rafted-up) before gravel (sewer rock) placement. Once the gravel is installed, the distribution pipe is to be installed level with the perforations faced downward. Gravel is then to be placed over the distribution pipe to provide a minimum of 2 inches of cover over the pipe. A silt barrier must be installed between the final gravel layer and the native soil backfill. Ensure the silt barrier covers the entire gravel surface before placing backfill. Monitor tubes shall be of four (4) inch diameter, installed approximately in the locations shown on the design, and extend a minimum of 12 inches above final grade. The portion of the monitoring tube extending through the gravel shall be perforated from the bottom ofthe trench to the invert of the distribution pipe. This is equivalent to the effective depth of the gravel as noted on the design. Page 3 Lot64, Tract A, b~le Crast 8~O June 26,2000 Backfill over the final gravel layer must not be less than twenty-four (24) inches. Insulation must be installed when the backfill depth is less than thirty-six (36) inches. The finish grade over the t~nch must be mound~l to prevent the formation of a depression after settling. MINIMUM MATERIAL SPECIFICATIONS: Any septic tank proposed for installation must be constructed by a Municipal approved septic tank manufacturer. The following pipe materials are approved for use in septic system installations in the Municipality of Anchorage: T_vpe of Pip~ Perforated Solid Cast Iron Yes Yes ASTM D3034 (PVC) Yes Yes ASTM F810 (HDPE) Yes No ASTM D2662 (/kBS) Yes Yes Use of a type of pipe other than listed above must be approved by the inspecting engineer. Insulation shall be at least 2" thick extruded direct burial polystyrene (Dow Chemical Company Styrofoam HI or equal). Septic tank inlets and outlets shall be titled with watertight couplings (Caulder, Femco, or equal). A periiieable nontoxic silt barrier (Typar 3401, Mirafi 140N, or equal) must be installed between the final leaehfleld gravel layer and the native soil backfill. All leachfield gravel (sewer rock) shall be 0.5"-2.5" screened gravel with less than 3% passing the #200 sieve. When sand is being used as a filter material, its gradation specifications must conform to current M.O.A. or D.E.C. requirements, which ever requirement applies. Page 4 Lot64, Tr~ctA, Eagle Cre.t $/D June25,2000 INSPECTIONS: Typically there will be a minimum of three (3) inspections required during the installation of the wastewater disposal system. These inspections will occur as follows: The first inspection must be conducted after the excavation of ditches, pits, trenches, or beds and before the installation of any gravel. A septic tank may be set in place, but may not be backfilled before this inspection. The second inspection must be conducted after the placement of the silt barrier, gravel, distribution lines, standpipes, cleanouts, and insulation, but before the placement of any other backfill. 3. The final inspection is to occur upon final grading of the property. Often there will be more than these 3 inspections required. Especially with the installation of multiple trenches, sand filters, pressurized distribution systems, etc. Thus, the inspecting engineer is to be contacted at least 24 hours prior to the start of construction. If necessary, a pm-construction meeting will take place on-site. The inspecting engineer will not coordinate, direct or control in any way the contractors activities. The owner shall contract with the contractor to perform the work outlined in these specifications and plans and in accordance with the attached M.O.A. permit. There will be no contractual arrangement existing between the contractor and S & S Engineering. S & S Engineering shall be the owner's representative and will inspect the work as stated above to document the conwactors activities. Final acceptance of the contractors work rests with the owner and the M.O.A. S & S Engineering shall have no liability ~ the owner or to others for acts or omissions of the contractor or any other persons performing work on this project or the failure of the contractor to carry out the work in accordance with these construction documents. S & S Engineering's inspecting engineer will not be responsible for the coustmcfion means, methods, techniques, sequence, procedures or the safety precautions incident to this project. CONTRACTOR / INSTALLER ~ - % MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH & ENVIRONMENTAL PRO'I:ECTION ENVIRONMENTAL ENGINEERING DIVISION 825 L Street- Anchorage, Alaska 99501 Telephone 264-4720 ON-SITE SEWAGE DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT NAME ~ ~ M*nuf~r ~ ~ ~ / NO. Of compartments ~OZ~ ~ DISTANCE TO: Well ~ ] /~Dwelling PERMIT NO. O Z Manufacturer II Foundation Nearest ~ne PE~MIT~ Length Width ~pth -- PERMIT NO. ~ ~ Ty~ of crib Crib diame Crib depth Total eff~ti~ absorption area m Well Building f~ndation Nearest lot line ~ DISTANCE TO: ~ iClass ~ [ ~ ~ .Oepth~/~ Driller Distance Io lot line PERMI~ NO. ~ DISTANCE TO: Building foundation Se~t line Septic tank Absorption area(s) ~0 ~ 0 SOILTESTRAT~G,~- ~ / ~ INSTAL~, ~ / · ~ REMARKS .~ ,..,:,..}1, ~?..." / ~ ..,.:// T ?.,% Rev. 3178) F'ERMIT NO. Of.I--.c; I TE i.'lUt-4 I C I I~'tL I T"r' (:IF RI",ICH~RGE DEF'RRTMENT OF HEALTH AND ENVIRONHENTRL ~-,.OTECTION 825 ~L 264-4720 SELLER PEArl I T APPLICANT CLYDE.G. RRHISTERD LOCATION Ti4N RiH S7 PO BOX 564-8 CHU~IRK 99567 LEGAL LOT 64 TRACT R EAGLE CREST TyPE OF SOIL RBSORPTION SYSTEM IS: TRENCH LOT SIZE 694-99 :L7820 SQUARE FEET MRXIMUH Nur,IBER OF BEDROOMS = 3 SOIL RATING <SO FT?BR)= 123 THE REQUIRED SIZ'E OF THE SOIL ABSORPTION SYSTEM IS: DEF'TH= I 4 LEt-~GTH=' 2C-~ GRAVEL DEPTH= THE LENGTH DIHENSION IS THE LENGTH (IN FEET> OF THE TRENCH OR DRAINFIELD. THE DEPTH OF R TRENCH OR PIT IS THE DISTANCE BETHEEN THE SURFACE OF THE GROUND AND THE BOTTOH OF THE EXCAVATION (IN FEET>. THERE IS NO SET HIDTN FOR TRENCHES. THE GRAVEL DEPTH IS THE MINIMUH DEPTH OF GRAVEL BETWEEN THE OUTFRLL PIPE AND THE BOTTOH OF THE EXCAVATION <IN FEET)?'~' REi;::LI I RED .C;EPT I C TRIslt.-. S I .7__E= ::1_~0 C-~ GALLON.C; PERHIT APPLICANT HAS THE RESPONSIBILITY TO INFORH THIS DEPARTMENT DURING THE INSTALLATION INSPECTIONS OF ANY HELLS ADJACENT TO THIS PROPERTY AND THE NUMBER OF RESIDENCES THAT THE HELL WILL SERVE.. TWO < 2 > I I~.C;PECT I ON--c; ARE R EI_3. U I RED BACKFILLING OF ANY SYSTEM HITHOUT FINAL INSPECTION AND APPROVAL BY THIS DEPARTMENT WILL BE SUBJECT TO PROSECUTION. MINIMUM DISTANCE BETHEEN A HELL AND ANY ON-SITE SEWAGE DISPOSAL SYSTEH IS 100 FEET FOR R PRIVATE HELL OF; 150 TO 200 FEET FROM R PUBLIC HELL DEPENDIHG UPON THE TYPE OF PUBLIC HELL. MINIMUH DISTANCE FROM R PRIVATE HELL TO ~ PRIVATE SEWER LINE IS 25 FEET AND TO R COMHUNITY SEHER LINE IS 75 FEET. OTHER REQUIREMENTS HAY APPLY. SPECIFICATIONS AND CONSTRUCTION DIAGRAMS ARE AVAILABLE TO INSURE PROPER INSTALLATION. PERI"II T EXP I RE-C; DECEI'IE:ER .?~:I..- I CERTIFY THAT i: I AH FAHILIRR WITH THE REQUIREMENTS FOR OW-SITE SEWERS AND WELLS AS SET FORTH BY' THE MUNICIF'RLITY OF ANCHORAGE. ~': I WILL INSTALL THE SYSTEI'I IN ACCORDANCE WITH'THE CODES. 3:, I UNDERSTAND THAT THE ON-SITE 5EHER SYSTEM MAY REQUIRE ENLARGEMENT IF .TH~j~. .RESIDENCE IS REMODELED TO INCLUDE MORE THAN 3 BEDROOMS. ~0~,'~ ~~~ 0 APPLICANT CLYDE G, RRHISTERD J" ~ERH IT t*ll_Jt,2 Z C · PI--tL. ]: T~r" OI~ t-~qOHO~t-~ll~ OEPIqRTHENT OF H~FR. TH fiND ~t,IV[RONHENTRL' PROTECrZON ~2~ 'L' ~TREET~. ~NCHORR~ RY. 99501 ' P. oPt. ICFtNT Ct.gDE G. RRHISTERP PO L~TION T~4N R~ S7 LOT 64 .T~CT A ~GLE CREST THE .LENOTH DIHENSION I~ THE LENGTH THE O~TH OF R TR~ICH OR P~T · GROUND RNb ~E 80TTOH ~ THE .E~:RVhT%~ THERE I5 NO ~Er-~IDTH FO~ T~HE~. · t"~llt.~llJ 'r RISC',, --c;EPT [ C TFINK L:, I ZE= 1.000 FERMIT RPPI.[CRNT H~ THE RE'~PON'~[OILITY TO IttFORII'TH[~ OEP'~I~TI.IENT DURING THE J IN'~TRI.I.i~TJON £N~PECFION~ OF RNY 14ELI. S RDJIqCENT TO THI$"PROPERT¥ RN(~ THE i tJIJI'ISER OF RESIDFJ'IC~S THFtT THE L'I~c,L HILL. SERVe. ---- Ti.JO '~ 2 ) I 1'4SPECT I s3N__'Z. FIRE RE,~U I RED --t" 8~CI.'FILL[NG Gc ~HY $'/SEH I'~ITHOUT FINRL IN'SPECTIOH RN(~ f~PPROVPK. 8V 'THIS DEPR2THENT HILL BE ~IJBJECT TO PROSECUTIOn[ --PIININUN DISTI3NCE I~E. TI,IEEN fl HELL RND ANY ON-~[TE ~EI4R~ D/SPOD~ ~T~ I5 I · G~ FEET FOR R PRI~TE I,I~L OR t:~ TO 20~ FEET FROH R PU~lC H~L ~'ID[IIG I · ' UPON TH~ TV~ OF PU~IC I,[L l TO Ft ~HHUNITM ~WER LINE IS 75 FEET. ; OTHER REQUIREHEHTS HRY I]PPLY. SPECIFICRT[O/~ HND ~I'~TRUCTION DIR~ ~RE I ~VAILRBLE ~ IHSURE ~OPER [I¢~fRL~TION. i [ ' CERTIF'/ THRT 1: [ 8H FthHILIRR FILTH THE REGUIREHEHT~3 FOR ON-~[TE SEI.IER$ AND IAL~ FORTH ~ ~E :HUNICIP~[~ ~ ,R~:ItORR[ ' t 2: I I,IILL I~T}%L THE ~f~ IN ~:CORDR~'I,IITfl ~ COD~. MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH AND ENVIRONMENTAL PROTECTION 825 I-- Street, Anchm'lge. Alaska 99501 264-4720 SOILS LOG - PERCOLATION TEST ~.~._.$OI LS LOG [] PERCOLATION TEST PERFORMED FOR:4:::L LEGAL DESCRIPTION: 1 2 3' 7 SLOPE DATE PE..ORMED: ~ -- 7-.t.-- ~ 10 "11 12 13 14- 15. 16. 17- 18-. 19- 20- .:'COMMENTS · .' PERFORMED BY: 72-008 (6/79) WAS G.OUNO WATER E.COUNTERED~ IF YES, AT WHAT DEPTH? Gross Net. Depth to Net Reading , Date Time Tinge Water Drop N/l ,' I N /~ (minutes/inch) PERCOLATION RATE TEST RUN BETWEEN F~O FTf · ' ' /x~/lxx / DATE' ~RB l~oX ~ _ ___CERTiFIE ' PH.