Loading...
HomeMy WebLinkAboutKNIK VIEW ESTATES BLK 3 LT 10 Municipality of Anchorage Development Services Department On-Site Water and Wastewater Program 4700 South Bragaw Street P.O. Box 196650 Anchorage. AK S9519-6650 www.d.anchorage.ak.us (907) 343-7904 ON-SITE WASTEWATER DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT Permit Number: _ Spinell Homes 9210 VanRuard Drive 344-5678 3 10 SW01047~ Anch., AK 99507 Four (4) LEGAL DESCRIPTION Knik View Estates Well: Class A Well I I SEPARATION DISTANCES T~ TO Septic Absorption Lift Tank Field Station ~,,, >200' >200' N/A ~=w,,.>100' >100' N/A ~ >5' >10' N/A >5' >10' N/A None Noted PID Number: 051-043-61 Wastewater System: New Page I of 3 ABSORPTION FIELD Deep Trench 1.2 o~e ~,. 4.5 FI. FI. I ,. 51 ~,. 5 F,. I N/A ~,. 510 re ASTM D3034 PVC Spinell Homes 1/16/02 TANK ~ Septic ri Holding r'l S.T.E.P. Holding ~ublic/Pdvate~aanu~ac~uter: Tank S~Une Anchorage Tank N/A>25' Steel N/AX / ~,. ,~.,~,~,. N/A/~ ~ Garage Slab ri Other. 1,250 Two (2) LIFT STATION - NONE ON LOT BENCH MARK 100.0 Engineer's Stamp Inspections performed by: Tim Kimbrough Dates: 1" 1/16/02 2~ 1/16/02 Depa~ment of Health and Human Se~ices approval Revi~ed and approved by: ~/~/ /~ ~Date: ?-~ ~ Municipality of Anchorage DEVELOPMENT SERVICES DEPARTMENT 4700 South Bragaw Street Anchorage, AK 99519-6650 - 343-7904 On-Site Wastewater Disposal System or Well Inspection Report Page 2 of 3 Permit Number SW010475 PID No. 051-043-61 A B Sl 36.3 15.4 S2 39.1 22.3 C4 32.1 37.2 M1 31.5 35.3 C5 66.2 46.5 M2 65.1 44.8 \ \ House PLAN AS-BUILT SCALE 1" = 40' DEVEOPMENT SERVICES DEPARTMENT 4700 South Bragaw Street Anchorage, AK. 99519-6655 - 343-7904 On-Site Wastewater Disposal System or Well Inspection Report Permit Number. SW010476 PID No. 051-043-61 [-'9 98,P ' ~--68.55 Ge(~t extile rob?it D?oln~'ietd Rock ~ 01.6 51' PROFILE $cole: 1' ,- 10' AS-BUILT jr MUNICIPALITY OF ANCHORAGE Development Sen/ices Department On-Site Water & Wastewater Program 4700 South Bragaw Street P.O. Box 196650. Anchorage, AK 99519-6650 (907) 343-7904 ON-SITE WASTEWATER DISPOSAL SYSTEM PERMIT Initial Date Issued: Dec 03, 2001 Expiration Date: Dec 03, 2002 Permit Number: SW010475 Legal Description: KNIK ViEW ESTATES BLK 3 LT 8 & 10 Design Engineer: 0014 Anderson Engineering Owner Name: Spinell Homes Owner Address: 9510 Vanguard Dr. Anchorage, AK 99507- Parcel ID: 051-043-61 Site Address: Lot Size: 61995 SQ. FT. Total Bedrooms: 4 Permit Bedrooms: 4 This permit is for the construction of: [] Disposal Field [] Septic Tank [] Holding Tank [] Privy [] Private Well [] Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal Code Chapters 15.55 and 15,65 and the State of Alaska Wastewater Disposal Regulations ( 18AAC72 ) and Drinking Water Regulations ( 18AAC80 ). 3. The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 ( 24 hours ). ( Not required for a Water Supply Permit only ). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must be either: A. Open and closed on the same day. B. Covered, sealed, and heated to prevent freezing. Issued By: Date: Municipality of Anchorage Development Services Department Building Safety Division On-Site Water and Wastewater Program 4700 South Bragaw St. P.O. Box 196650 Anchorage, AK 99519-6650 www.ci.anchorage.ak.us (907) 343-7904 ON-SITE SEWEPJVVELL PERMIT APPLICATION FOR A SINGLE FAMILY DWELLING Parcel I.D. Permit Number swOIO4-7~ Property owner(s) Spinell Homes, Inc. Day phone 344-5678 Mailing address (1) 9510 Van.quard Ddve Anchoracle, AK 99507 Mailing address (2) Zip Code ~.~. ~.~-~ __ Legal description (Lot, Block & Sub'd.) Lot 10, Block 3, Knik View Estates Subdivision -'"7 /~,/~ ~_q- /~. _'~1 .......-.~-.- Legal description (Section, Township & Range) Lot Size 40,131 SF THIS APPLICATION IS FOR: Sewer Only Sewer and Well Sewer Upgrade THIS PROPERTY CONTAINS: Hot Tub Swimming Pool Therapy Pool Acres/Sq. Ft. Number of Bedrooms Four [] Well Only [] [] Water Storage [] Jacuzzi Water Softening Unit I certify that the above information is correct. I further certify that this application is being made for a Single Family Dwelling and is in accordance with applicable Municipal Codes. (Signature of properly owner or authorized agent) Permit Fees: Date of Payment: Receipt Number: (Rev. 12/00) Waiver Fees: Date of Payment: ~' Receipt Number: ANDERSON ENGINEERING P.O. BOX 240773 · ANCHORAGE, AK 99524 522-7773 522-6779 (FAX) November 26, 2001 Municipality of Anchorage Development Services Department On-Site Water and Wastewater Program 4700 South Bragaw Street Anchorage, AK 99519-6650 Su~e~: Lot 10, Block 3, Knik View Estates Subdivision Septic System Design and Permit Application Impacts to Adjacent Properties Dear Onsite Services Engineer:. The owner of Lot 10, Block 3, Knik View Estates Subdivision intends to construct a new four-bedroom home on the lot. We are therefore requesting a permit be issued for the construction of a new septic system to serve the proposed home. The attached Site Pla.n. and backup documentation identify the Ioc.ation and.configuration of the new septic system and the parameters .used in the design. Also identified on the plans are the location of the water service hne on the lot and the test hole location. Existing drainage patterns are shown and will not be altered by the development of the lot. A test hole was placed near the location of the proposed absorption trench. This test hole indicates clea.n well-graded gravel with yawing amounts of sand near the location of the new absorption trench. Percolation tests in the matedal resulted in rates of less than 1 minute per inch. The majority of the matedal in the hole will pass the No. 4 Sieve so no sand liner is necessary. No groundwater was found during the placement of the test hole and none was noted during the monitonng period. We are therefore proposing to place a 5' wide shallow absorption trench system with 4' of gravel beneath the distribution pipe. The total depth of the trench will be 7'. The distribution pipe will be placed at 3' below the ground surface to provide sufficient drop from the septic tank to the absorption trench. The total length of the new absorption trench will be 50'. A podion of the trench will encroach into the 100' power line easement. We have an agreement, however, from Matanuska Electdc Association allowing placement of a portion of the trench in the easement. A copy of that agreement is attached for your review. The ground surface on the lot slopes as shown on the attached Site Plan with very little to no slope near the proposed septic system site. The new absorption trench will be constructed on a fairly flat surface in conformance with Municipal requirements and parallel to ground contours where possible. All components of the new septic system will be constructed a minimum of 10' from the water service line to be constructed on the lot. If the system Is constructed In accordance with our design the following statements Lot 10, Block 3, Knlk View Est. Subdivision November 26, 2001 Page Two apply: t. The system, if constructed as designed, will have no adverse impact on the wells in the area or those to be constructed in the future. 2. The system, if constructed as designed, will have no adverse impact on existing septic systems in the area or those to be constructed in the future. 3. The system, if constructed as designed, will have no adverse impact on reserve space, either surface or subsurface, on any lots located in the area. 4. The system, if constructed as designed, will have no adverse impact on drainage patterns in the area. The current drainage pattern will be maintained. Sincerely, Michael E. Anderson, P.E. Attachments ,/ 0 / //4 J JUDD 2/ / Circle 22 / ? 2J $0.00 / / 205.00 / / THIS PROJECT 1" = 100' AREA MAP J~,,01.,90o00 N \ \ : \ \ \ Fou~ Bedroom Hous~ / / / / / ! / SITE PLAN - SCALE 1' =40' LOT 10, BLOCK 3, KNIK VIEW ESTATES SUBDIVISION DESIGN FACTORS: SYSTEM REQUIREMENTS: Four Bedroom Home Perc. Rate: <1 MinJInch Application Rate: 1.2 GPDISF 5' Wide Trench System 1,500 Gallon Septic Tank 4' Drainfield Rock 4 Bedrooms X 150 GPD 11.2 GPD/SF = 500 SF of Absorption Area 500 SFI5 LF (Wldth)*.5 (Red. Factor) = 50 LF Trench Length Therefore: Construct a 50' Long X 5' Wide X 4' Effective Depth Absorption Trench. Flowline Elevation in Trench to be 3' Below Original Ground Surface. Total Depth to be 7' Below Existing Ground. Mound Over Trench to Provide a Minimum of 3' of Cover or Provide 2" of Direct Bury Insulation and 2' of Cover. · ... ~ . ' ~ ..... . ... ~...~ , - .. ' ... . '.' , 2.5 :.. ., ..... · ~" .' · ' " ! ~ Geote×ti[e.Fabric · , ' _', - . :'~ ~ ' . . ~; . · . ... . , .'. · . .... 5, ' '-'d/~,'''0" ~'~ ~''" : ' . - ' ' -' '- · · .. -- , . ~ 'J~' -- _~-~'~ '.. .. · . . -'..[ ,=~a~...~ ~. ~' ' ,~ · ' PVC. (Hole's .Down) · .. ., ' . $' . . '.~. .... ,~ .: . . ., · · ~ :-. _, .. ",~,~,~.~,~. , . . · . · . ~ . -,".. w~ .. ~ '. ' . · · ;' "-. '' o. ~. ~ . . Dralnfiela·Rock .:.' · -. · .,-~' .~.~. /. ~' . '~..' ...,, . . · . -.' ' ' ' ~' ~ '~;.i,'~. ~' "' '"" .... "~ ''~'" :""' ' · .'....' .. ,~. -~o..~...~. ..~ · .. ~ · . · .. .. · . · ,. · .' ',.. ~ , .....~o,-,:.:: ~ ~ ..... .: NOTE: TYPICAL WIDE TRENCH SECTION (NO SCALE) Grade Are,a, Over Trench to Drain Away. Minimum 6 Separation From Bedrock. Minimum 4' Separation From Groundwater. Minimum 10' Separation From Water Service Line. PROJECT #: V0133 PERFORMED FOR: Municipal[b/of Anchorage Development Services Department 4700 South Bragaw Street Anchorage, AK 995196650 SOILS LOG - PERCOLATION TEST SPINNEL HOHES DATE PERFORMED: I1-01-01 LEGAL DESCRIPTION: LOT 101 BLK ). KNIK VIEW ESTATES SUBD. TEST HOLE REDISH I~ROWN SILTY OL 1 SLOPE LOOSE WELL GRADED GRAVELS WITH SANDS- GW 0% SW LENSE : ~ . LOOSE WELL GRADED GRAVELS 6 ~ · " WITH SANDS' GW I0-- 12-- 15-- 16 17-- 18 WAS GROUNDWATER ENCOUNTERED') NO IF YES, WHAT DEPTH? DEPTH OF WATER AFTER MONITORING: DATE: SLIGHTLY COHPACT[D SANDY GRAVELS GP x~erc. Rate <5 Mi.n./zn. SITE PLAN / None 1111'//O1 S 'L 0 P E READING DATE GROSS NET TiME DEPTH OF NET DROP TIME ' (i"'llN) WATER (INCHES) Start 11-01-01 1060 12' 1 10.63 2.S 12" Recharge 10:/.3 12' 2 10:66 2.5 12' Recharge 1066 12' 3 1069 2.'/5 12' PERC RATE: ,. 1 PrIN./INCH PERC. HOLE DIAHETER: 6' TEST RUN BETWEEN 3 S FT. AND 6 S FT. COHMENTS: HOLE PRESOAKED / NO IMPERHABLES ENCOUNTERED TEST PERFOE~ED BY: T.L. KIMBROUGH I, MICHAEL E. ANi)ERSON, CERTIFY THAT THIS TEST WAS PERFORMED IN ACCOF~ANCE WITH ALL STATE AND MUNICIPAL GUIDELINES ON THIS DATE: Il- ~.1~ -iT I ON-SITE WASTEWATER DISPOSAL SYSTEM CONSTRUCTION AND MATERIAL SPECIFICATIONS SUBJECT: LOT 10, BLOCK 3, KNIK VIEW ESTATES SUBDIVISION GENERAL: The scope of this project includes the procurement and placement of a new 1,250 gallon septic tank at the location shown on the Site Plan. Work also includes the construction of a new 50' long X 5' wide X 4' effective depth absorption trench at the location also shown on the Site Plan. The distribution line in the trench will be placed at 3' below the existing ground surface. Total depth of the trench will be 7' below the existing ground surface. The new absorption trench must be placed a minimum of 10' from the water service line on the lot. Construction shall be in accordance with the approved site plan, design drawings, Municipal Permit with any special provisions or conditions, and all applicable State and Municipal Wastewater Disposal Regulations. The Contractor shall be responsible for obtaining all underground utility locates and for the layout of the septic system and verification of the location of all lot lines. 4. Unless specifically agreed otherwise, the contractor shall be responsible for final grading areas subsequently depressed from soil settling. Property owner shall be responsible for revegetation of affected areas unless specifically agreed otherwise. Contractors installing wastewater disposal systems must be certified by the Municipal Department of Health and Human Services for system installations. Owners installing their own systems must receive prior approval from D.H.H.S. before beginning system installation. SEPTIC TANK INSTALLATION 1. A new 1,250-gallon septic tank must be procured from an approved source and installed at the location shown. 2. A septic tank is to be constructed by a certified septic tank manufacturer. Construction shall includet~o 4' cleanouts for pumping access. 3. The septic tank shall be sufficiently bedded to prevent settling or shifting of the tank. 4. All standpipes on the septic tank shall extend a minimum of 12 inches above final grade. 5. Tanks installed without 4' of cover shall have a minimum of 2" of direct burial insulation. A foundation cleanout shall be installed one to four feet from the building foundation. Two cleanouts are required between the tank and the drainfield. Lot 10, Block 3, Knik View Est. Subdivision November 26, 2001 Page 2 of 3 7. Final grading over the tank shall be such that a positive slope exists away from the septic tank. DRAINFIELD CONSTRUCTION: 1. The drainfield shall be constructed to the dimensions shown on the design. The bottom of the trench shall be within 2" of level. Distribution piping must be placed level with perforations down atop a level bed of drainfield rock. Rock should then be placed over the pipe to provide a minimum of 2" of cover, 3. A silt barrier or geotextile fabdc must be placed between the drainfield rock and the natural soil backfill. 4. Monitor tubes must be 4" in diameter and installed at the locations shown on the design. The portion below ground must be perforated. St Contractor shall verify the septic tank and drainfield are a minimum 100' away from any,private water wells in the area, 150' from a Class "C" Well or 200' from any community well. o Direct bury insulation must be placed over the distribution system if less than 3' of backfill depth is available. Finish grade over the trench must be mounded to prevent settlement or depressions. 7. Grade area surrounding the absorption trench to drain away. o A minimum 2' of accepting soil is required below the drainfield rock for a 5' wide trench. Contractor shall vedfy this condition pdor to placement of the rock. All pockets of unacceptable materials must be removed and replaced. MATERIAL SPECIFICATIONS: 1. Septic tanks must be constructed by a municipally approved septic tank manufacturer. 2. The following pipe materials are approved for use in septic system installations in the Municipality of Anchorage: Cast Iron (perforated and solid), ASTM D3034 or P.V.C. (perforated and solid), ASTM F810 or H.D.P,E. (perforated, but not solid) and ASTM D2662 or A.B.S. (perforated and solid). 3. Insulation shall be at least 2" thick extruded direct burial polystyrene (Dow Chemical Co. Styrofoam HI or equal). 4. Septic tank inlets and outlets shall be fitted with watertight couplings (Caulder, Femco, or equal). ' Lot 10, Block 3, Knik View Est. Subdivision November 26, 2001 Page 3 of 3 5. A permeable geotextile fabric (Typar, Mirafi or equal) must be installed between the final drain rock layer and the native soil layer. 6. All drain rock shall be .5" to 2.5" in diameter with less than 3% passing the #200 sieve. INSPECTIONS: Municipal Ordinance requires a minimum of two inspections. These inspections must be conducted under the supervision of a professional engineer registered in the State of Alaska. The first inspection must be conducted after the excavation of trenches, beds or pits and before the installation of any gravel. A septic tank may be set in place, but may not be backfilled. The second inspection must be conducted after the placement of the geotextile fabric, gravel, distribution piping, standpipes, cleanouts and insulation. No backfill should be in place at the time of inspection. Contractor shall provide a copy of all field survey layout and construction notes for use in preparing the certified as-built of the completed system. 6: 14.PM FROM MEA-ROW ' 9077619322 STATEMENT OF NON-OBJECTION FOR ENCROACHMENT WITHIN UTILITY EASEMENT Matanuska Electric Association, Inc. (MEA) has no objection to the location of a sepii~ system leach field within the 100' powerline easement that lies within the following :, property;.' Lot 10, Block 3, KNIK VIEW ESTATES SUBDIVISION, according to Plat No. 86-113; Anchorage Recording District, Alaska Situated in Section 4, Township 15 NoAh, Range 1 West, Seward Meridian. ¢ This non-objection is conditioned by the stipulation that MEA will be held harmless from any and all damages to the encroachment that may result from the existing and futur~ use of said easement. This non-objection is also subject to Plat Note No. 3 on the subdivision plat that stat~s that no leach field or standpipe~ will be allowed within 20' from the centerline of exls~ng · powerline. P. 2 Matanuska Electr~ Association, Inc. General Manager or hj,f~RepresentatNe November 14. 2001 Date MEA ACKNOWLEDGMENT STATE OF ALASKA ) ) ss. THIRD JUDICIAL DISTRICT ) The foregoing agreement was acknowledged before'me this ~14 day of November. 2001. by Robert G Ylvlseker. ' .J>. ANDERSON ENGINEERING P.O. BOX 240773 ANCHORAGE, AK 99524 522-7773 522-6779 (FAX) MEMORANDUM DATE: November 30, 2001 TO: FROM: Dan Roth Mike Anderson, P.E~ SUBJECT: Lot 10, Knik View Estates Subdivision Septic System Construction Permit A dimension has been added indicating the distance between the new house and the proposed absorption trench. Please let me know if you have any questions or additional information is required. Municipality of Anchorage Development Services Department Building Safety Division On-Site Water and Wastewater Program 4700 South Bragaw St. P.O. Box 196650 Anchorage. AK 99519-6650 www.ci.anchorage.ak.us (907) 343-79O4 CERTIFICATE OF HEALTH AUTHORITY APPROVAL FOR A SINGLE FAMILY DWELLING Parcel I.D. 051.043-61 2. NUMBER OF BEDROOMS: Expiration Date: 7- -~, ~/- O .~ GENERAL INFORMATION Complete legal description Location (site address or directions) Rebecca Circle Current Properly owner(s) Spinell Homes, Inc. Mailing address 9210 Vanguard Drive Anchoracle, AK 99507 Lending agency Mailing address Real Estate Agent Mailing Address Unless othen/vise requested, HAA will be held by DSD for pickup. Four Lot 10. Block 3. Knik View Estates Subdivision 3. TYPE OF WATER SUPPLY: Individual Well Individual Water Storage Community Class_A Well Public Water System Day phone 344.5678 Day phone Day phone TYPE OF WASTEWATER DISPOSAL: [] Individual On-site [] [--I Individual Holding tank [] [] Community On-site [] r-I Public Sewer [] The Municipality of Anchorage Development Services Department (DSD) Issues Certificates of Health Authority Approval (HAA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. Certificates of Health Authority Approval are required for the transfer of title (except between spouses) for properties served by a single family on-site wastewater disposal and/or water supply system. DSD also issues HAAs upon request to homeowners. Certificates of Health Authority Approval are valid for 90 days from the date of issue for properties served by a private or Class C well and may be reissued with new water sample results less than 30 days old. (Certificates may be reissued for a period of up to one year with valid water samples.} Certificates are valid for one year for properties served by Class A or B wells or a public water system. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 4. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Health Authority Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is(are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm Anderson Enaineerin(~ Address P.O. Box 240773 Anchoraae. AK 99524 Phone 522-7773 Engineer's Printed Name Michael E. Anderson. P.E. 5. DSD SIGNATURE Approved for J-iL. Disapproved. Conditional approval for bedrooms. Date 7/24/2002 · '..':-Or ,~' ' '.. {~, ~>... ,.',-* .~ bedrooms, with the following stipulations: Additional Comments Attachments: HAA Checklist Septic System Advisory Well Flow Advisory Maintenance Agreements Supplemental Engineer's Report Other Original Certificate Date: '7" ~ q ' 0.2. Municipality of Anchorage __o Development Services Department Building Safety Division '~........,' On-Site Water & Wastewater Program 4700 South Bragaw St. P.O. Box 196650 Anchorage, AK 99519-6650 www.ci.anchorage.ak.us (907) 343-7904 HEALTH AUTHORITY APPROVAL CHECKLIST Legal Description: Lotl0, Block3. Knik View Estates If A, B, or C provide PWSID # Sanitary seal (Y/N) Cased to ft. FROM WELL LOG A. WELL DATA Well type & Date completed Total depth g.p.m. Nitrate mg.fl. Collected by: Number of Compartments 2_ Depression over tank (Y/N) N_ Pumper New Constn~ion Date of test Static water level Well production WATER SAMPLE RESULTS: Coliform colenies/1O0 mi. Date of sample: B. SEPTIC/HOLDING TANK DATA Tank Type/Material Se~c/Steel Tank size 1,250 gal. Foundation clear, ut (Y/N) Y_ Date of pumping C. ABSORFrrlON FIELD DATA ParcellD: 0514)43-6t Welt Log (Y/N) Wires property protected (Y/N) Casing height (above ground) AT INSPECTION Data installed t/16/2002 Length S1 Total depth 8_ ft. Date of adequacy test in. g.p,m. colonies/lO0 mi. Date installed t/16/2002 C~eanouts (Y/N) Y High water alarm (Y/N) N Fluid depth in absorption field before test __ in. Water added gal. Elapsed Time: min. Final fluid depth in. Absorption rate >= Any rejuvenation treatment (past 12 mo.) (Y/N & type) N ff yes, give date Soil rating (g.p.d./f~ or ft2/bdrm) 1.2 GPD/SF System type 5' Wide Shallow Trench fl. W~dth $ fl. Gravel below pipe 4 ft. Eft. absorption area 510 ~ Monito,'ing tube Y_. Deprassien over field N.N_ Resuits (Pass/Fall) For bedrooms New depth in. g.p.d. D. UFT STATION Date installed "Pump on" level at __ in. Datum E, SEPARATION DISTANCES Size in gallons 'Pump ~ level at __ Cyctes tested SEPARATION DISTANCES FROM WELL ON LOT TO: Septic tank/lift station on lot Absorption field on lot N/A Public sewer main N/A Sewer/septic service line in. Manhole/Access (Y/N) High water alarm level at Meets alarm & circuit requirements? On adjacent lots N/A On adjacent lots N/A Public sewer manhole/cleanout N/A Holding tank N/A SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO: Building foundation >5' Property line >5' Water main N/A Water service line >t0' Wells on adjacent lots >200' SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO: Properly line >t0' Building foundation >t0' Water Service line >10' Surface water >t00' Curtain drain None Noted Wells on adjacent lots >200' F. COMMENTS Lot is sened by AWWU water system. G. ENGINEER'S CERTIFICATION I certify that I have determined through field inspections and review of Municipe/ records that the above systems are in conformance with MOA I-fAA guidelines in effect on this date. Engineer's Printed Name Michael E. Anderson, P.E. Date 7r24/02 Absorption field >5' Surface water >t 00. Water main >10' Driveway, parking/vehicle storage >25' HAA Fee $ Date of Payment Receipt Number (Rev. 12~oo) 7 - 02. in.