On -Site Wastewater Disposal System Permit
Permit Number: OSP221114
Work Type: Septic Upgrade
Tax Code Number: 05115112000
Site Legal Address: T15N R1 W SEC 8 LT 117 G:1257
Site Mailing Address: 21223 JAYHAWK DR, Chugiak
Owner: EBY ERIC K & KIRSTEN E
Design Engineer: GARNESS ENGINEERING GROUP LTD
This permit is for the construction of:
Q Disposal Field Q Septic Tank ❑ Holding Tank ❑ Privy
Effective Date:
Expiration Date
�i
r�
n s
I)epartnient
5/19/2022
5/19/2023
Lot Size in Sq Ft: 108900
Total Bedrooms: ,8' y
❑ Private Well ❑ Water Storage
All construction shall be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska
Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80)
3. The wastewater code requires inspections during the installation. The engineer shall notify the Development
Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather
shall be either:
a. Opened and Closed on the same day, or
b. Covered, sealed, and heated to prevent freezing
co 1 �x e,n c� bcoi� Are VNC G se C_Cls�> 1 S �* �--C' e -o' -b +
OTfY-°O'Sl+
Received By: Date:
Issued By: fes' ` �2�r'�-Q1� Date: l 01? 4
MUNICIPALITY OF
I IPALIT ANCHORAGE
Development Services Department
Phone: 907-343-7904
On -Site Water & Wastewater Section Fax: 907-343-7997
ON-SITE SEPTIC/WELL PERMIT APPLICATION
Parcel I.D. 051-151-12
Property owner(s) ERIC EBY Day phone 907-529-4385
Mailing address 21223 JAYHAWK DRIVE *CHUGIAK, AK 99567
Site address
Legal description (Sub'd., Block & Lot) T15N R1 W SECTION 8 LOT 117
Legal description (Township, Range '&-Section)
Lot Size Sq. Ft. Number of Bedrooms 8-" L(
APPLICATION IS FOR:
(® all that apply)
Absorption Field Q
Septic Tank
I]
Holding Tank
❑
Privy
❑
Private Well
❑
Water Storage
❑
APPLICATION IS AN:
Initial ❑
Upgrade x❑
Renewal ❑
THIS APPLICATION INCLUDES A WAIVER REQUEST FOR:
TYPE OF DWELLING:
Single Family (SF)
(w/wo AD U)
Duplex (D)
Multiple Dwellings
(SF and/or D)
Distance:
I certify that the above information is correct. I further certify that this is in accordance with
applicable Municipal Codes.
) ZJhr n z s S
(Signature of property owner or a
P C -/—i
agent)
Permit/Rush Fees: _0595 Waiver Fees:
Date of Payment: 5' —% (1 _ Z Date of Payment:
Receipt Number: ()Z2P) 7G Receipt Number:
Permit No. OSP Waiver No.
GMevelopment Services\Building Safety\On Site Water and Wastewater\FormsUient Forms\Permit Application.doc
/D0
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP221114, Rebecca Carroll, 05/19/22
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP221114, Rebecca Carroll, 05/19/22
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP221114, Rebecca Carroll, 05/19/22
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP221114, Rebecca Carroll, 05/19/22
MUNICIPALITY OF ANCHORAGE
Development Services Department Phone: 907-343-7904
On -Site Water & Wastewater Section Fax: 907-343-7997
Certificate of On -Site Systems Approval
Parcel I.D. 051-151-12
Legal description T1 5N R1 W Sec 8, lot117
Site address 21223 Jayhawk Dr Chugiak AK
Current property owner(s) Eric Eby
Expiration Date:
3-14-2023
The On-site system(s) is/are approved for bedrooms
X Conditional approval for 4 bedrooms, with the following stipulations:
Comments or advisories: Field to be extended in spring of 2023
By: Original Certificate Date:_t Z
This Certificate of On -Site Systems Approval (COSA) is intended to demonstrate the subject
system(s) is/are in substantial compliance with municipal code. The Municipality of
Anchorage, Development Services Department (DSD) issues COSAs based upon
representations provided by an independent professional engineer. The Municipality of
Anchorage is not responsible for errors or omissions in the professional engineer's work.
ATTACHMENTS:
COSA Checklist X Well Flow Advisory
Absorption Field Advisory Nitrate Advisory
Tank Age Advisory Arsenic Advisory
Other
COSA Approval June 2022
UH- MWALITY OF A CH0RAG
Development Services Department Phone: 907-343-7904
On-Site Water & Wastewater Section Fax: 907-343-7997
Certificate of On -Site Systems Approval Application
1. GENERAL INFORMATION
Parcel I.D. 051-151-12
Complete legal description T1 5N, R1 W, SECTION 8; LOT 117
Location (site address) 21223 JAYHAWK DRIVE *CHUGIAK, AK 99567
Current property owners) ERIC & KRISTEN EBY Day phone 907-529-4385
2. ON-SITE SYSTEMS SIZED FOR 4 BEDROOMS
3. TYPE OF WATER SUPPLY: X Private Well ❑ Private Well serving 2 dwelling units
❑ Private Well serving 3+ dwelling units ❑ Community Well or Public
❑ Water Storage
4. TYPE OF WASTEWATER DISPOSAL: X Private Septic ❑ Private Septic serving 2 dwelling units
❑ Holding Tank ❑ Community Septic or Public Sewer
5. SEPTIC TANK: ❑ Steel 0 Plastic ❑ Concrete ❑ Fiberglass
Age NEW - See advisory if steel older than 20 years
6. ABSORPTION FIELD: ❑ AWWTS ❑ Bed ❑ Deep Trench ❑■ Wide Trench ❑ Seepage Pit
Waiver request for: Distance:
Expedited review requested: ❑
By applying for this entitlement, this property is subject to inspection by municipal On-site staff
to verify the accuracy of the information provided.
COSA Fee $ d--90 + 019La 76
Date of Payment
COSA #
Waiver Fee $
Date of Payment
Waiver #
COSA AppUca6on_June 2022
Legal Description: T15N, R1 W, SECTION 8; LOT 117
Parcel ID: 051-151-12
If more than 1 well and/or septic system on lot, provide separate checklist. Structure served by this system 1
A. WELL DATA
❑ Well log is filed with Onsite (or attached)
Date drilled 1974 M Total depth *76.0+ ft
Cased to LINK. ft
❑ Sanitary seal is functioning correctly
Well production at time of test 3.2 + qpm
Water storage tank volume **400 gallons
Well disinfected for coliform test? ❑ Yes IN No
❑ Coliform bacteria is Negative
❑ Wires are properly protected Nitrate 2.07 mg/L ❑ Nitrate less than MRL (ND)
Casing height (above ground) 18+ in. Arsenic ug/L ❑ Arsenic less than MRL (ND)
Date of flow test for COSA 11/18/2022 Collected by GARNESS ENGINEERING
Static water level at beginning of test 73.2 ft. Date 11/18/2022 44
Comments *PER GEG FLOW TEST. **2 - 200 GALLON GREER PLASTIC STORAGE TANKS ***PUMP 561 GALLONS
OVER 167 MINUTES. STORAGE TANK LEVELS UNCHANGED (50" & 49.5"). LEVEL IN CASING DROPPED 2.8 FEET
B. TANK DATA
Measured operating fluid level in septic tank NEW
Date of pumping NEW
❑ Required maintenance completed, if AWWTS
Comments:
D. ABSORPTION FIELD DATA
Which system tested (date installed) 11/18-28/22
❑ ALL standpipes present per record drawing
Total measured depth from grade 3.8 ft (max)
Measured depth to pipe invert from grade 2.8 ft (min)
❑ N/A — pressurized field.
❑ Per record drawings, field is insulated.
❑ Monitor tubes go to bottom of effective.
If not, state depth into effective
❑ Presoaked required if
(Required if house vacant or field not used for more
than 30 days prior to date of test)
Gallons introduced _gallons date
Any rejuvenation treatment (past 12 months)
If yes, enter date
C. LIFT STATION
❑ Required maintenance completed
Age of lift station NEW years
Lift station material PLASTIC
Comments:
Adequacy test date NEW
Results ❑ Pass
Fluid depth prior to test NEW in
Water added NEW gal
New fluid depth NEW in
Elapsed time NEW min
Final fluid depth NEW in
Absorption rate *450+ gpd
FIELD STATUS — POST RECOVERY
Effective depth (per record drawings) 6 in
Effective depth used NEW in
Effective depth remaining 6 in
Comments/Deficiencies: *TRENCHES WILL BE EXTENDED BY 15' EACH IN SPRING OF 2023 TO BE SIZED FOR
4 -BEDROOMS.
COSA Checklist June 2022
E. SEPARATION DISTANCES
From Private Well on Lot to: (Please enter distances if less than required or if community well on lot)
Septic Tank/Lift Station on Lot > 100'
0 Yes
if No
Community Sewer Manhole/Cleanout > 100'
QYes
if No
ft
E Yes
if No ft
Neighboring Tank > 100' 0 Yes
if No
ft
Private Sewer/Septic Line > 25' Q Yes
if No ft
Absorption Field on Lot > 100' 0 Yes
if No
ft
Holding Tank > 100' [E Yes
if No ft
Neighboring Absorption Fields > 100'
if No
ft
Animal Containment > 50' ■❑Yes
if No ft
❑i Yes
if No
ft
ft
If tank or field is under driveway comment below
Manure/Animal Excreta Storage > 100'
Community Sewer Main > 75' nn Yes
if No
ft
[�] Yes
if No ft
❑ N/A — Served by Community Well (not on lot) or Public Water
From Septic/Holding Tank and Absorption Field(s) on Lot to: (Please enter distances if less than required)
Building Foundations > 10'
0 Yes
if No
ft
Surface Water > 100'
© Yes if No ft
Tank to Property Line > 5'
❑o Yes
if No
ft
Wells on Adjacent Lots:
Field to Property Line > 10'
❑N Yes
if No
ft
Private Wells > 100'
❑E Yes if No ft
Water Main > 10'
Yes
if No
ft
Community Wells > 200'
Q Yes if No ft
Water Service Line > 10'
Yes
if No
ft
If tank or field is under driveway comment below
F. ENGINEER'S COMMENTS
PLEASE ISSUE CONDITIONAL COSA . NEW TRENCHES WILL BE EXTENDED
IN SPRING OF 2023. TO BE SIZED FOR 4 -BEDROOMS.
G. CERTIFICATION & STATEMENT OF INSPECTION BY ENGINEER
As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based
on procedures outlined in the Certificate of On -Site Systems Approval Guidelines, indicates that the on-site water
supply and/or wastewater disposal system appears to comply with applicable Municipal and State codes,
ordinances, and regulations in effect at the time of installation, unless noted otherwise.
Name of Firm Gamess Engineering Group, LTD. (GEG) Phone
Engineer's Printed Name Jeffrey A. Garness Date _
In conducting this evaluation, GEG provided an engineering evaluation of the well and/or septic system in
accordance with the guidelines and regulations established by the Municipality of Anchorage and industry
practices. The reported results describe the condition of the system/s on the date/s of the evaluation.
Separation distances were measured to readily identifiable features. Hidden defects or encroachments may
exist that were not identified during the evaluation. The operational life of all wells and septic systems depend
upon a variety of variables, including (but not limited to) soil conditions, groundwater levels (that may fluctuate
during the year), quality of construction (materials and workmanship), and the water usage of the family utilizing
the system/s. These conditions can vary, and are outside the control of GEG. Satisfactory test results do not
3uarantee future performance of the system/s; therefore, GEG makes no warranty (express or implied) regarding
the future performance of the well or septic system. GEG makes no representation whether an alternative well
or septic system can be installed on the property in the event either of the current systems fail to perform
adequately in the future. The content of this report is for the sole benefit of the personiparty that retained GEG
to perform the evaluation. Reliance upon the information provided in this report by any other person or party
(including subsequent property purchasers) is not authorized, nor will it confer any legal right whatsoever.
COSA Checklist June 2022
907-337-6179
o OF.gCU 4
,o.�F-.-•........ X40
Jef eV, r , A. Ga s ..
049_ —7953
4s n•... ...-
" 0
LICENSE1�professi000
#AECC884 �QQp 00
r-
00
N
6
Z
U
L-
CL
V
J
J
vi
O)
3
N
cu
_
O'
LL
N
N
e -I
C7
M
O
Ln
1
I
M
M
�
W
Nc
CO
m
Iia
N
LL
O
f.7
(A
Q
0)
(A
Q
m
L- nHo- nlf8=
l:
O --_—
S ZZ
9,89 -
0)
2
i im
I
\
ONU
su
ONUS\O\ / (p
n
-Qfio--OF(U �-�-OMo
3/VNa OIN30S 3
Mt107
Z3'0££ M..0£,60 o00N
I a)
�+ moa)
N Cr a)
m O
o a ca aa
Lo)
C/) 4--
c) m
c)m
3coD
C6 C,) U) Q� N
N
61.
^ 1 SPG
P
a°' y
0
/ col -
0 0
0
O—r----------
CHU--- &fOJ- 9HU-
PS'0££ M„ 00,20 o00N
0
o
Z-6 L m C
O y «
O(D W a c m o w
Z Ui
U- cn m� L9 N 0, o
C OLLO } 2: Cf') ami >1 n Q
O7 J O U w 0 0 3
-6aUTO U) ,a`i
Cl) e e U Q N 4-1
c N `0 fo Z
u) ��>uj N0n�cc L
a) c/7
O W �QiQU% O
Za
Co co QQ Q 0 O a. n G
(a
as c !� c �
or -
00 -"00.S QN
-! o 0 N L. (� O N 00
c O 0 Q Cwo N
m y N> L co N Ul
0 3
40 0)
> CL 7 U a) OV� O f6
(U O N O C E O S
J-+ O ow J a) T C L L VI E
n C N O) E 0 N C 5 L O
CY,tis O) !6 0 G� d 0 ./� L < V
Cn fa a tf -p to O a-+ a) >•
"' m 1i m n Z C as > on
C a) Q a (n F' .0@ C Z p 0
C t2
`o C
25
N rn o)0 <ncva G cH u O U < C E
Ln M a)C-C .0 w U 't•. L cu J LU
4J v- vi
ma 3 oa En �' 00 vcu
vi 1,' L2
2 p Baa) 0a)�a) :ti V L Q > cn�v
Y CL °Xc °)Emmami i i ^ > 'S
U a) �a)c Qw �Ev a v i> v
a) < lD
L c0 "mcn2°Oo a � c� N =COo+'
Q 0) T a) O
Op N C T L C O C 'V O L ` l�I Ln >- ai Ln p p
v m v a) E
o v 1 m m ate- a`) 4 -
Ln 3
u
Z C O u) p -p O C) n
CL a) h Q o i ,n C)
a) m a1) I- 0 .5 N m Q _J _ :3 LL io m S'
�-
.0 :E Q O
O O O
O O
CL y 2 m
to Co � w ° m G • �%
N c N 2 N
a)
m tf
cli
Q o O
�2 �; �v)o
�NNCL O:
43)
LU
(v O 0) 0 m Off' O p Lt -
v
NCL
E =
O L 0 E -
®<W �V i) C7 CV ri v •®�
I
f
a
W
w
CO
/o
'-------/------------
Iia
N
LL
O
£91Z "od 09£ 'MG
Ym
lL!
/ 1N31103V3All-11n,0£
00
W
^/Lo
1�
x
PS'0££ M„ 00,20 o00N
0
o
Z-6 L m C
O y «
O(D W a c m o w
Z Ui
U- cn m� L9 N 0, o
C OLLO } 2: Cf') ami >1 n Q
O7 J O U w 0 0 3
-6aUTO U) ,a`i
Cl) e e U Q N 4-1
c N `0 fo Z
u) ��>uj N0n�cc L
a) c/7
O W �QiQU% O
Za
Co co QQ Q 0 O a. n G
(a
as c !� c �
or -
00 -"00.S QN
-! o 0 N L. (� O N 00
c O 0 Q Cwo N
m y N> L co N Ul
0 3
40 0)
> CL 7 U a) OV� O f6
(U O N O C E O S
J-+ O ow J a) T C L L VI E
n C N O) E 0 N C 5 L O
CY,tis O) !6 0 G� d 0 ./� L < V
Cn fa a tf -p to O a-+ a) >•
"' m 1i m n Z C as > on
C a) Q a (n F' .0@ C Z p 0
C t2
`o C
25
N rn o)0 <ncva G cH u O U < C E
Ln M a)C-C .0 w U 't•. L cu J LU
4J v- vi
ma 3 oa En �' 00 vcu
vi 1,' L2
2 p Baa) 0a)�a) :ti V L Q > cn�v
Y CL °Xc °)Emmami i i ^ > 'S
U a) �a)c Qw �Ev a v i> v
a) < lD
L c0 "mcn2°Oo a � c� N =COo+'
Q 0) T a) O
Op N C T L C O C 'V O L ` l�I Ln >- ai Ln p p
v m v a) E
o v 1 m m ate- a`) 4 -
Ln 3
u
Z C O u) p -p O C) n
CL a) h Q o i ,n C)
a) m a1) I- 0 .5 N m Q _J _ :3 LL io m S'
�-
.0 :E Q O
O O O
O O
CL y 2 m
to Co � w ° m G • �%
N c N 2 N
a)
m tf
cli
Q o O
�2 �; �v)o
�NNCL O:
43)
LU
(v O 0) 0 m Off' O p Lt -
v
NCL
E =
O L 0 E -
®<W �V i) C7 CV ri v •®�
� GARNESS ENGINEERING GROUP, Ltd
Jr
ENGINEERING -- SALES =CONSULTING
December 13, 2022
Municipality of Anchorage
Development Service Department
On -Site Water & Wastewater Program
4700 Elmore Road
Anchorage, AK 99507
Ref: Revisions to Septic System Upgrade Design and Conditional COSA for T15N R1W
Section 8 Lot 117
Attention Deb Wockenfuss:
A septic permit was issued on 5/19/2022 for a 3 -bedroom house (OSP221114). A 3 -bedroom
sized drainfield was installed on 11/18-28/2022. The house actually has 4 -bedrooms, so
additional square footage must be added to the newly installed drainfields. Attached is a revised
design drawing which shows the location of the newly installed STEP tank and drainfields; and
also shows the location of the additional trench length that will be added to the drainfields in the
spring of 2023. The new STEP tank is adequately sized for a 4-bedrrom residence. We have
shown the approximate limits of the test hole on the revised design. The east end of the drainfields
will be slightly outside the 30 -foot radius of the test hole. Approximately 90% of the drainfields are
within the 30 -foot radius of the test hole excavation limits. We request the permit be revised for
4 -bedrooms.
The house sale is set to close on December 15th. We request a conditional COSA be issued or
the property on the condition that additional square footage be added to the newly installed
drainfields in the spring of 2023. We do not anticipate any adverse effects with operating a 4 -
bedroom residence on the newly installed septic for approximately a 6 -month period.
We are unaware of any adverse impacts this installation would have on adjacent wells or septic
systems. If you have any questions, please contact us at 337-6179. Thank you for your
assistance. ,
Sincerely,
E., M. S.
%4k 3/Z7_...
3701 East Tudor Road, Suite 101 * Anchorage, Alaska 99507-1259
Phone: (907) 337-6179 * Fax: (907) 338-3246 * Website: www.garnessengineering.com
Ecklund, Timothy J
From: Sonja Blewett <Sonja@garnessengineering.com>
Sent: Wednesday, December 14, 2022 10:27 AM
To: Ecklund, Timothy J; Wockenfuss, Deborah M.
Subject: RE: 21223 Jayhawk drive
Hello, following up on status of this one? Do you think this one will be issued today? Thanks
Sonja
From: Sonja Blewett
Sent: Tuesday, December 13, 2022 1:33 PM
To: 'Ecklund, Timothy J' <timothy.ecklund@anchorageak.gov>; 'Wockenfuss, Deborah M.'
<deborah.wockenfuss@anchorageak.gov>
Subject: FW: 21223 Jayhawk drive
Hi Tim, here is email below from ARM Septic on scope of work and it being under $2,000. Thanks!
Sonja
From: ARM Septic Services LLC <ARMServicesAK@outlool<.com>
Sent: Tuesday, December 13, 2022 1:31 PM
To: Sonja Blewett <Sonia@garnessengineering.com>
Subject: Re: 21223 Jayhawk drive
Yes it's going to be under 2000
Sent from my iPhone
On Dec 13, 2022, at 1:30 PM, Sonja Blewett <sonia@garnessengineering.com> wrote:
Thank you. Just to confirm, Its under $2,000?
Sonja
From: ARM Septic Services, LLC <armservicesak@outlook.com>
Sent: Tuesday, December 13, 2022 1:29 PM
To: Sonja Blewett <Sonia@garnessengineering.com>
Subject: 21223 Jayhawk drive
To whom it may concern:
ARM Septic Services, LLC is returning in the spring/early summer(2023) to 21223 Jayhawk drive to
extend the leech fields 15 linear feet per field, per the engineers direction, to meet the requirements of
a 4 bedroom septic system.
1
Scale 1" = 50'
a
C
2
Legend:
Frontier Surveys, LLC Project No: 22-187
Ordered By: ARM Septic Services
LOT 92-8
— _ N890 59.17wW 329.82 Lo
`l AN M
i I• I N �\ CCVV
r 130.3
716.5 � 6
I
1 �p�
\ �
M 2 CAR\A CD
ay . GARAGE
1
I
i
X53
\ I
�
W
'z
Lu
k mol
timl
a !
Fj M I
q
I
—J------------
50' R-O_W. RESERVE
_.
$ BK. 230 PG. 40
c
CC] Culvert
n
LE, Elec. Pedestal
14) Septic
EDGE OF PAVEMENT
N89° 59'27"W 329.99
I
Sign ® Wood Deck —x-- Fence
Tel. Pedestal Telephone Pole --Overhead Utility
l;;I Septic Clean Out `y) Water Well is Sign
Date: 04/11/2022
Plat: 83-503 1 Grid: 1257
166.7
123.3
104.2
Lot 117
Sec 8 T15N R9 W
Seward Meridian
108,900 Sq. Ft. +/-
21223 Jayhawk Drive
2 Story Woad Frame House
with 2 Detached Garages
ri JAYHA WK DRIVE
NOTE:
BEARINGS & DISTANCES FROM BLM
SURVEY APPROVED MA Y 31, 1917 DO NOT
MATHEMATICALLY CLOSE BEARINGS &
DISTANCE SHOWN ON THIS PLAT WERE
DERIVED FROM PLAT # 83-503.
General Notes:
1. This document is created for the purpose of a single property transaction and is subject to Federal Copyright Laws. a 25 50 100
2- Excepting for gross negligence, the liability for this survey shall not exceed the cost of preparing this survey -
3. All meas urementslsetbacks are to the vi sualla pparent building footprint- Scale In Feet
4. All dimensions to property lines are pluslminus 0-1ft-
.1001-
*r::49-TH
... ...
�'. Pierre M . Sir ler.
`j • . No. L.S: - 9812 . • i
■� ��QF� • .
04111/202Z. • •���
O�fs5 bPi AV
PROFESSIONAL SEAL
This survey complies with the ASPLS Mortgage Loration Standards. The survey represents visible improvements and
conditions at the time of the survey. This document does not constitute a boundary survey and is subject to any
inaccuracies that a subsequent boundary survey may reveal- It is the responsibility of the Owner to determine the
existence of any easements, covenants, or restriction which do no appear on the record plat. Under no circumstances
should this document be used for construction or for establishing a beundary or fence fine.
As -Built Survey of:
Lot 117, Sec 8, T15N, R1W, Seward Meridian
I, Pierre Stragier, hereby certify that this Mortgage Inspection Survey was performed by me, or
under my direct supervision on April 8th, 2022.
Frontier Surveys, LLC I FRONTIER
650 W. 58th Ave. Suite E Anchorage, Alaska 99518 Lft SiLwveys-
907.460.1686 - info@frontiersurveys.com
www.frontiersurveys.com
GRE
'"'ER ANCHORAGE! AREA BOr'"'UGH
Department of Environmental (;~uality
3330 C Street
Anchorage, Alaska 99503
INSPECTION REPORI' ON-SITE JEWAGF ,DISPOSA!. SYSTEM
SEPTIC TANK:
DISTANCE
FROM WELL
INSIDE LENGTH
MANUFACTURER
INSIDE WIDTH__
X
NUMBER OF
MAT E R iA L&~4CI~I'6 ~l ,,,~.~_ CO M pA RT M ENTS I --
LIQUID DEPTH__ _LIQUID CAPACITY /0~)(~ GALLONS,
SEEPAGE PIT: ~b~o '70' ~ ~¥{o ~A'~-"~ O~:'~,
NUMBER OF PITS ]--. DIAMETER --~.¢~! OR WIDTH !~'~,, LENGTH~-, DEPTH
LINING MATERIAL ~.bY¢xg-e.~ CRIB SIZE: DIAMETER.~'
DEPTH _ DISTANCE FROM:
BUILDING FOUNDATION NEAREST LOT LINE ..
ADDITIONAL ABSORPTION
WELL J2 ' _.
TOTAL. EFFECTIVE
ABSORPTION AREA (WALL. AREA) ~"~ _S(~. FT,
WELL.: ~'-~)
BUILDING NEAREST NEAREST
FOUNDATION ~ LOT LINE SEWER LINE
CESSPOOl OTHER SGURCES ~
APPROVED _ DISAPPROVED REMARKS~
DEPTH_
SEPTIC
-rANK
DISTANCE FROM:
SEEPAGE /
SYSTEM 17-'(~
DISTANCES:.
INSTA LED BY:.
PIPE MATERIAL:-
REMARKS:
Form No. EQ~031
DIAGRAM OF SYSTEM
GRI=_.,'ATER ANCHORAGE AREA BOROUGH
DEPARTMENT OF ENVIRONMENTAL QUALITY
3330 "O"STREET ANCHORAGE, ALASKA 99503
TELEPHONE 27.1-4561
SEWAGE DISPOSAl. SYSTEM -- APPLICATION AND PERMIT
PERMIT NO..
INSTALLATION LOCATION
IN STALLAT[ON OF: SEPTIC TANK // S BEPAGE PIT ~// , DRAIN FIELD.
FINANCED THROUGH TO BE ]NSTALLEO BY t-.~ /~ '
COMPLEflON DATE ANTICIPATED
,, OTHER.
NOTE~ THIS PERMIT 15 NOT VALID WITHOUT SOIL TEST
FINAL INSPECTION: 24 HOUR NOTICE REQUIRED. BACKFILLING OF ANY SYSTEM WITHOUT FINAL INSPECTION BY THE
DEPARTMENT OF ENVIRONMENTAL QUALITY AUTHORITY WILL BE SUBJECT TO PROSECUTION.
FOUNDATION TO SEEPAGE Pit ~ / , DRAIN FIELD
SEPTIC 'rank TO SEEPAGE PIT WALL /~-~ /
SEPTIC TANK SEEPAGE PIT ~'~ /
. _ , DRAIN Field
WeLITO SEPTIC Tank ~~ '/ , SeePAge PIT_ /~
SEEPAGE
ALSO CONSIDER AREA WELLS.
AREA SIZE
WATER MAIN TO SEPTIC TANK SEEPAGE PIT
BACKFILL
TYPE
I CERTIFY THAT I AM FAMILIAR WITH THE REQUIREMENTS OF GREATER ANCHORAGE AREA BOROUGH ORDINANCE NO, 28-68 AND TNAT THE ABOVE
DESCRIBED SYSTEM IS IN ACCORDANCE WITH SAID CODE, ~./~[, ~ ~
• Municipality of Anchorage
On -Site Water and Wastewater Program
(907)343-7904
Certificate of On -Site Systems Approval l e,, T5, S v�
Parcel 1. D. 051- (5- 12, Expiration Date: -7-11-14
1. GENERAL INFORMATION
Complete legal description Lot 117, Section 8, T1 5N, R1 W, S.M.
Location (site address) 21223 Jayhawk Drive, Chugiak, Alaska 99567
Current Property owner(s) Bruce & Theresa Bartley Day phone (907) 688-3657
Mailing address 21223 Jayhawk Drive, Chugiak, Alaska 99567
Real Estate Agent Ed Erickson @ Keller Williams Day phone (907) 227-5275
2. TYPE OF DWELLING:
Fx] Single Family (w/wo ADU)
❑ Duplex
❑ Multiple Dwellings (Single Family and/or Duplex)
WaiverNariance request
Received by: :! - ' - -- Date:
COSA to be released to L 4ginear, unle s=otherwise requested by the engineer.
COSA Fee $_
Date of Payment
Receipt Number
COSA#
Waiver Fee $
Date of Payment
Receipt Number
Waiver #
3
3. NUMBER OF BEDROOMS:
4. TYPE OF WATER SUPPLY:
TYPE OF WASTEWATER DISPOSAL:
Individual Well
0
Individual
El
Individual Water Storage
❑
Holding Tank
❑
Community Class Well
❑
Community
❑
Public Water System
❑
Public Sewer
❑
WaiverNariance request
Received by: :! - ' - -- Date:
COSA to be released to L 4ginear, unle s=otherwise requested by the engineer.
COSA Fee $_
Date of Payment
Receipt Number
COSA#
Waiver Fee $
Date of Payment
Receipt Number
Waiver #
5. STATEMENT OF INSPECTION BY ENGINEER
As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation,
based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application,
shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate
for the number of bedrooms and type of structure indicated herein. I further verify that based on the information
obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water
supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes,
ordinances, and regulations in effect at the time of installation.
Name of Firm Pinard Engineering Phone (907) 357-3647
Address PO Box 871347, Wasilla, Alaska 99687
Engineer's Printed Name Paul E. Pinard, P.E.
6. DSDSIG ATURE
System #1 Approved for bedrooms
System #2 Approved for bedrooms
Disapproved
Conditional approval for
Date 4/10/14
bedrooms, with the following stipulations:
By: Original Certificate Date:_) —
The M icip ofnc� a Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only
upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality
of Anchorage is not responsible for errors or omissions in the professional engineer's work.
7. ATTACHMENTS:
COSA Checklist X Nitrate Advisory
Septic System Advisory Arsenic Advisory
Well Flow Advisory Other
COSA blue sheet S - � 0
If more than 1 septic system is on the lot:
COSA Checklist # _of _
Structure served by this system
Certificate of On -Site Systems Approval Checklist
Legal Description: Lot 117, Section 8, T1 5N, R1 W, S. M.
A. WELL DATA
Well type Pvt If A, B, or C provide PWSID #
Date completed 1974 ? Sanitary seal (Y/N) Y
Total depth 150 ft. Cased to ft.
FROM WELL LOG
Date of test
Static water level ft.
Well production g.p.m.
WATER SAMPLE RESULTS:
Coliform 0 colonies/100 mL Nitrate 0.918 mg/L
Arsenic ND ug/L Date of sample: 2/21/13
B. SEPTIC/HOLDING TANK DATA
Tank Type/Material Septic/Conrete Block
Tank size 1000 gal. Number of Compartments
Parcel
Well Log (YIN) N
Wires properly protected (Y/N) Y
Casing height (above ground) 18+ in.
AT INSPECTION
2/23 & 2/24/13
58.2 ft.
g.p.m.
0.33
Collected by: Pinard Engineering
Date installed August 1974
Cleanouts(Y/N) Y
Foundation cleanout (YIN) Y Depression over tank (Y/N) N High water alarm (Y/N) N
Date of pumping 5/3/13 Pumper JRs Pumping
C. ABSORPTION FIELD DATA
Date installed 8/74 Soil ratio Pit & Drain Line
g (g.p.d.lftz or ftZ/bdrm) System type
Length Pit - 15 ft Width Pit -12 ft. Gravel below pipe 4 ft.
Total depth 7.3 ft. Eff. absorption area 300 fh Monitoring tube Y Depression over field N
Date of adequacy test 2/23-24/13 Results (Pass/Fail) Pass For 3 bedrooms
Fluid depth in absorption field before test 25 in. Water added 470 gal. New depth 26 in.
Elapsed Time: 1410 min. Final fluid depth 26 in. Absorption rate >= 450+ g.p.d.
Any rejuvenation treatment (past 12 mo.) (Y/N & type) None Known If yes, give date
D. LIFT STATION
Date installed NA
"Pump on" level at
Datum
Size in gallons _
"Pump off' level at
Cycles tested _
E. SEPARATION DISTANCES
WELL ON LOT TO:
Septic tank/lift station on lot
100'+
Absorption field on lot
1001+
Public sewer main
NA
Sewer /septic service line
25' +
Animal containment areas
50' +
Manhole/Access (Y/N) _
in. High water alarm level at
Meets alarm & circuit requirements?
On adjacent lots 100' +
On adjacent lots 100' +
Public sewer manhole/cleanout NA
Holding tank NA
Manure/animal excrete storage areas 100' +
SEPTIC/HOLDING TANK ON LOT TO:
Building foundation 51+ Property line 5'+
Water main 10'+ Water service line 10' +
Wells on adjacent lots 100' +
ABSORPTION FIELD ON LOT TO:
Property line 10'+ Building foundation 10'+
Water Service line 10'+ Surface water 100'+
Curtain drain None Known Wells on adjacent lots 100' +
Absorption field 5' +
Surface water 100' +
Water main 10'+
Driveway, parking/vehicle storage 10' +
F. COMMENTS
Since ST was homebuilt, MOA staff requested a leakage test. One was conduced while the
in.
owner was out of town. There was no drop in the liquid level in 18.5 hours.
G. ENGINEER'S CERTIFICATION
L"
! certify that / have determined through field inspections and 2 ' 4
review of Municipal records that the above systems are in @ a 3
conformance with MOA COSA guidelines in effect on this date. X r . —
tia�ot0400e eae 6ypp„r
d Pi
l E. Pinard, Engineer's Printed Name Pau , P.E. v�' �'�u I
A O 0
Date 5/30/13
�•J. ^.. ems. ra��”-O GJetJ �P�u�: .
COSA brown sheet 10-10-12.doc
Municipality of Anchorage R
r
Development Services Department
Building Safety Division s
On -Site Water and Wastewater Program
4700 Elmore Street
P.O. Box 196650 Anchorage, AK 99519-6650
www.ci.anchorage.ak.us
(907)343-7904
Water Well Advisory
Certificate of On -Site Systems Approval (COSA) # 132132
During a recent COSA on-site inspection and test of the potable water
supply well on Block , Lot 117 of T15N R1W Section 8 subdivision,
the well's productivity was determined to be 0.33 gallons per minute. The
minimum well productivity required by this Department (AMC 15.55) for a
3 -bedroom residence is 0.31 gallons per minute. Although the subject well
currently exceeds this minimum requirement, all parties concerned are
advised that the production capacity of the well may fluctuate. Restriction
of non-critical water uses such as washing cars and watering lawns and
gardens may be required.
This advisory must be attached to all copies of the subject Certificate of On -
Site Systems Approval.
LOCATION: Lot 117, Section 8, T15N, R1W, S.M.
DRILLER: M & W Drilling
DATE WELL COMPLETED: Circa 1974
WELL DEPTH: 150'
STATIC WATER LEVEL (top of casing): 9.2'
PINARD ENGINEERING
P.O. Box 871347
Wasilla, AK 99687
(907) 357-ENGR (3647)
WELL FLOW TEST
JOB NUMBER: 13-033
DATE OF TEST: 2123 - 24113
FIELD STAFF: PJ Pinard
1�1
Time
Elapsed
Time
(Minutes)
Static
Water
Level
Flow
Rate
m
Cumulative
Gallons
Pumped
Remarks
4:35 PM
-
58.2'
4.0
-
Start Test - Meter
560620
4:50
15
84.9'
4.0
60
560680
5:05
30
102.3'
4.0
120
560740
5:20
45
118.0'
3.3
180
560800
5:35
60
138.1'
2.7
230
560850
5:50
75
138.2'
-
270
Stop Flow -
560890
2/24/13
3:05
15
62.0'
3.3
-
Resume Flow -
560900
3:20
30
85.9'
3.3
320
560950
3:35
45
100.4'
3.3
370
561000
3:50
60
117.3'
3.3
420
561050
4:05
75
130.5'
-
470
Stop Test -
561100
EEJ
I-1—
RECOVERY
5:15 70 111.5' All well protection features are adequate.
Average Flow Rate: 0.33 gpm
Comments: DURING THIS TEST, THIS WATER SUPPLY WELL WAS CAPABLE OF h... �?
PRODUCING 4.0 GPM FOR LIMITED PERIODS. THIS TEST DOES NOT Reviewed by: Paul Pinard'�rl
NOT CONSTITUTE A WARRANTY OR GUARANTEE THAT THE WATER
SUPPLY SYSTEM WILL CONTINUE TO FUNCTION AND PRODUCE AT THIS RATE. Date: 2128113
PINARD ENGINEERING
P.O. Box 871347
C
Wasilla, AK 99687
(907) 357-ENGR (3647)
ADEQUACY TEST
LOCATION: Lot 117, Section 8, T15N, R1W, S.M.
APPLICANT: Bruce & Theresa Bartley
21223 Jayhawk Drive
Chugiak, Alaska 99567
SEPTIC TANK TYPE/SIZE: Homemade (concrete & steel)/1000 Gallons, per MOA Records
ABSORPTION SYSTEM: Seepage Pit & Shallow Drain Line, per MOA Records
DAILY FLOW:
3 BEDROOMS x 150 GAL/BR = 450 Gallons
TEST DATA
JOB NUMBER: 13-033
DATE OF TEST: 2/23 - 24/13
FIELD STAFF: PJ Pinard
NUMBER OF BEDROOMS: 3
SCUM: 0.0' SLUDGE: Minimal
NEEDS TO BE PUMPED: Yes No XX
CURRENTLY IN USE: Yes XX No
Time
Flow
Rate
Volume
Cumulative
Volume
Septic Tank
Septic
Tank
Soil Absorption System
Comments
pM
(GPM)
(GALS)
(GALS)
Liquid Level
A Level
Monitor
Tube 1 *
A SAS
Level
Monitor
Tube 2*
A SAS
Level
4:35
4.0
-
-
5.2'
-
2.1'
-
Start Flow -Meter 560620
4:50
4.0
60
60
5.3'
0.1'
2.2'
0.1'
560680
5:05
4.0
60
120
5.3'
0.0'
2.2'
0.0'
560740
5:20
3.0
60
180
5.3'
0.0'
2.2'
0.0'
560800
5:50
-
90
270
5.3'
0.0'
2.2'
0.0'
Stop Flow 560890
2/24
3:05
3.3
-
270
5.2'
-
2.1'
-
Resume Flow - 560900
3:35
3.3
100
370
5.3'
0.1'
2.2'
0.1'
561000
4:05
-
100
470
5.3'
0.0'
2.2'
0.0'
Stop Test- 561100
RECOVERY
Date
*ALL MEASUREMENTS IN FT.
TEST: PASSED XXX FAILED
COMMENTS: This system was found to be operating satisfactorily. There was 2.1' of measurable liquid in the
SAS MT prior to beginning the test. With the addition of470 gallons to the system (the design daily flow), the
level rose only 0.1, leaving almost half of the ED of the SAS still available. A recovery measurement
showed satisfactory absorption.
Reviewed by: Paul Pinard
Date: 2128113