Loading...
HomeMy WebLinkAboutRIVER VIEW ESTATES BLK 5 LT 16River Vi Block Lot ]6 #050-792-17 Page I of 3 Municipality of Anchorage Development Services Department On-Sita Water and Wastewater Program 4700 South Bragaw Street P.O. Box 196650 Anchorage, AK 99519-6650 www.ct.anchorage.ak.us (907) 343-7904 ON-SITE WASTEWATER DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT Permit Number: SW020146 MM&M Contractin~ P.O. Box 670495 ChuRiak, AK 99567 688-1236 Three (3) LEGAL DESCRIPTION River View Estates 5 3.6 Well: New Private L_Z_;._.IT° L~O F,. 21 F,. Sullivan Water Wells 7 c,~ I F~. 2 SEPARATION DISTANCES  Septic Absorption Lift Holding Tank Field Station Tank w. >100' >3.00' >'100' N/A s~.w.,.>3.00' >100' >100' N/A ~ >5' >3.0' >3.0' N/A ~o~,~ >5' >3.0' >10' N/A None Noted PID Number: 050-792-3.7 Wastewater System: New ABSORPTION FIELD 5' Wide Shallow Trench 3..2 c.~ 4 3..5 ' 2 F,. 54 F,. 5 ~,. 2 I >3.0 385.7 ~' ASTM D3034 PVC MM&M Contracting 7/3.9-24/02 TANK - STEP Anchorage Tank :1.,250 s~,~ Ur, Steel >25' ~' 250 42 Orenco Garage Slab LIFT STATION Anchorage Tank Three (3) 42,.. 44,.. BENCH MARK 100.0 FL Inspections performed by: MEA Dates: Ist 7/3.9/02 2"~ 7/24/02 Department of Health and Human Services approval Reviewed and approved byX/y ~. N87°44'58"E 270.48 Alternate Site TH2 16 $2 PLAN AS-BUILT SCALE 1" = 50' A S1 14.3 S2 19,3 M~ 20.4 B 31.6 34,3 35.1 Municipality of Anchorage Page 3 of 3 DEVEOPMENT SERVICES DEPARTMENT 4700 South Bragaw Street Anchorage, AK. 99519-6655 - 343-7904 On-Site Wastewater Disposal System or Well Inspection Report Permit Number: SW020146 PID No. 050-792-17 12 Orifices In Each Lateral Each 3/16" In Diameter and 2.25' Spacing Geotextlie Fob,'ic l)~-oinFielct Rock 110.4 ~--1' PVC ~-107.1 104.9j NOTE: Both Trenches are Identical PROFILE AS-BUILT Scale: Measurements Shown FRO~ : C~LINTRY' RERLTY ~ NO. : 9076881238 Oct. 14 2g~. E~2.: 13Ptl P5 ~,~:~;~,;.~.,,~.~;,~;;~,:~-f~,~; -.~?..,, .~j-5='.~';~?~t,,,;~.~..~'.. ,. ................ ~ ~.. . . ~ ....... · .~. '~'.~z;'~:;~*~;~.~f~:~::; ~:~g'F.~' ~'?,~,,'. '" .". ' . ' '~ . ' · ' .. "'-. · ' '. ~. . .. ~"' ~ ?g':"';"~ ~1 ~"~"~;~" ~" .... ' .... ' ..... ' ;/~ ~ g.:.~C~ ~ ~,;t~'A'~.~*~:~ .."' ~ ..'. ..... ~ ..... -~ .. --.~ , . ' - ~ ' · =' ' --' t . ',.- ',': ,-~.-.~- ,~1,'..~-.'-~,.' ..... - ~*..~,t. * ..,......~' , .b" .0 E~'/~ ~ .' '*'..." ..... ~:~.~ . ~,~.~ .... : ...... . . ...,:, -- ..... ........ . ..... . . . .. . .. ,.., ~i~St~ckup.~oye.G~ . ~ · . feet · , .......... · .... · ~..~.. ;?~,{'3 t.~:k' ~;~'~>;,~: ..... '. ~', · ;.~ .:...,.. '. : · .:: .... . . ..... . . ~.~......:,~ t..: ... ~?J~'~ ~.~; ',;~::{.~:~.,;?.~'~2;.'~, ,,~,~ ~.~; t-~-; · .' .. '- · .. ~, ..... :.' " '- ...... . ". · ~ · . ' · .' ~": . .'.",..' ~"-':' · ~ '~c-~4;~q~, ~.~ ~,~-~-;.-%--.,.~.~;:~-~-~.~=.., -. · ' ' ' ' ' ' " " '' ' ~;"" '"'" :Me~6fDi~f~t~~;~:,...:- .~.~.~,:~,.;/ ~.;..,~, ~-: ~.fi;. ,. ,. ..... .,........,~?..,.. ,.~..- <,...:.~ ........ ~ ~. Nov~nlx:r I~, 2002 F~# 907-6~1.123g EI~rlcal work perfo'ar,~d (~ rcqucs~ Mlvl,~ ~ng, Inc. P.O. Box 6?0495 CheWink, AX. 9956? To whom it may concc~: The eleclri~l insmllaQon of the lift s~agon ~EB ~ EL~C, LLC cc: ~ C~*acfu~. l~c. Hie P.O. Box 876510, P/art/la, Al~.~ka 99(~? Office (90~ 375.3~95 / Cel1232.868?/ Fax 375-389¢ Eeceive~ Ti~e Nov.20. 10:34AY ~/~ 'd tOl~'°~ ~ldl~:~ ~00~ '0~'^°~ MUNICIPALITY OF ANCHORAGE Deve/oprnent Services Depar~nent On-Site Water & Wastewater Program 4700 South Bragaw SYeet P.O. Box 196650, Anchorage, AK 99519-6650 (907) 343-7904 ON-SITE WASTEWATER DISPOSAL SYSTEM I WATER SUPPLY PERMIT Initial Date Issued: Jun 05, 2002 Expiration Date: Jun 05, 2003 Permit Number: SW020146 Legal Description: RIVER VIEW ESTATES BLK 5 LT 16 Design Engineer: 0014 Anderson Engineering Owner Name: MM&M Contracting Owner Address: PO Box 670495 Chugiak, AK 99567-0000 Parcel ID: 050-792-17 Site Address: 007401 WATERFALL DR Lot Size: 41971 SQ. FT. Total Bedrooms: 3 Permit Bedrooms: 3 This permit is for the construction of: [] Disposal Field [] Septic Tank [] Holding Tank [] Privy [] Private Well [] Water Storage All construction must be in accordance with: 1. The attached approved design. 2. Ail requirements specified in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations ( 18AAC72 ) and Drinking Water Regulations ( 18AAC80 ). 3. The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by caIIing (907) 343-7904 ( 24 hours ). ( Not required for a Water Supply Permit only ). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must be either:. A. Open and closed on the same day. B. Covered, sealed, and heated to prevent freezing. Municipality of Anchorage Development Services Department Building Safety Division On-Site Water and Wastewater Program 4700 South Bragaw St. P.O. Box 196650 Anchorage, AK 99519-6650 www.ci.anchorage.ak.us (907) 343-7904 ON-SITE SEWER/WELL PERMIT APPLICATION FOR A SINGLE FAMILY DWELLING Parcel I.D. 050.792.17 Permit Number SW Property owner(s) MM&M Contractin.q, Inc. Mailing address (1) P.O. Box 670495 Chuqiak, AK 99567 Mailing address (2) Day phone 688.t236 Zip Code Legal description (Lot, Block & Sub'd.) Lot t6, Block 5, Riverview Estates Subdivision Legal description (Section, Township & Range) Lot Size 41,971 SF Acres/Sq. Ft. Number of Bedrooms Three THIS APPLICATION IS FOR: Sewer Only Sewer and Well Sewer Upgrade THIS PROPERTY CONTAINS: Hot Tub Swimming Pool Therapy Pool [] Well Only [] [] Water Storage [] Jacuzzi []~ Water Softening Unit I certify that the above information is correct. I further certify that this application is being made for a Single Family Dwelling and is in accordance with applicable Municipal Codes. (Signature of property owner or authorized agent) Permit Fees: Date of Payment: Receipt Number: (Rev. 12/00) Waiver Fees: Date of Payment: Receipt Number: ANDERSON ENGINEERING P.O. BOX 240773 ANCHORAGE, AK 99524 522-7773 522-6779 (FAX) May 29, 2002 Municipality of Anchorage Development Services Department On-Site Water and Wastewater Program 4700 South Bragaw Street Anchorage, AK 99519-6650 Subject: Lot 16, Block 5, Riverview Estates Subdivision Septic System Design and Permit Application Impacts to Adjacent Properties Permit No. SW980100 Dear Onsite Services Engineer:. A permit was issued for the construction of a well and septic system for Lot 16, Block 5, Riverview Estates Subdivision in May of 1998. The permit subsequently expired and the property changed hands. The current owner of the property intends to construct a three-bedroom home on the lot. We are therefore requesting the permit be reissued for the construction of a new well and septic system to serve the home. The attached Site Plan and backup documentation identify the location and configuration of the new well and septic system and the parameters used in the original design. Also identified on the plans are the location of the well on the lot, test hole locations and the locations of existing wells and septic systems in the area. Since the original permit was issued both the lot to the south and to the northeast have been developed. The locations of the wells and septic systems on these lots have been added to the drawings. The test holes placed near the location of the proposed absorption trenches and alternate site indicate slightly silty gravel with a percolation rate of less than 3 minutes per inch. Groundwater was found during the placement of the test holes and was monitored during the high water period. We are therefore proposing to place 2 - 5' wide by 27' long by 2' effective depth absorption trenches on the property. The total depth of the trench will be 4'. The distribution pipe will be placed at 2' below the ground surface to provide sufficient separation from groundwater. The ground surface on the lot slopes as shown on the attached Site Plan with moderate slopes east to west. The new absorption trenches will be constructed In conformance with Municipal requirements and parallel to ground contou ,rs, where possible. All components of the new septic system will be constructed a m~n~mum of 100' from the well on the lot and those In the area and 10' from the service line from the well to the house. If the system is constructed in accordance with our design the following statements · Lot 16, Block 5, Riverview Estates May 29, 2002 Page Two apply: i. 2. 3. The system, if constructed as designed, will have no adverse impact on the wells in the area or those to be constructed in the future. The system, if constructed as designed, will have no adverse impact on existing septic systems in the area or those to be constructed in the future. The system, if constructed as designed, will have no adverse impact on reserve space, either surface or subsurface, on any lots located in the area. 4. The system, if constructed as designed, will have no adverse impact on drainage patterns in the area. The current drainage pattem will be maintained. Sincerely, Michael E. Anderson, P.E. Attachments LOT 16, BLOCK 5, RIVERVIEW ESTATES SCOPE OF WORK: 1, Place New 1,250 Gallon STEP System. 2. Construct 2- 27' Long X 5' Wlde X 2' Effective Depth Absorption Trenches. 3. 1.25" PVC Delivery Line From Tank. 4. 1" Distribution Line In Trenches ..... 5. 12.3116" Holes @ 2.25' Spaclng PerTrench OT t5 LOT t4 " p~OPOStO omvt~Y ~_~ PROP. LOT I0 ~ LOT 16 · xx PROP. LOT 9 SITE PLAN SCALE 1" = 60' .o I SEPTIC TANK · .Ew ' roe I t # % L~T 7 LOT 16, BLOCK 5, RIVERVIEW ESTATES [~ Bedrooms X 150.,GPD 11.2 GPDISF = 375 SF of Absorption Area 75 SFI5 LF 0Nidth~.7 (Red. Factor) = 52.5 LF Trench Length DESIGN FACTORS: Three Bedroom Home Perc. Rate: 2.7 MinJInch Application Rate: 1.2 GPDISF SYSTEM REQUIREMENTS: 5' Wide Trench System 1,250 Gallon STEP System 2' Drainfield Rock ierefo?: C_onst.ruct a 2-27' Long X 5' Wide X 2' Effective Depth .sorpuon/rencnes. Flowline Elevation in Trench to be 2' elow Original Ground Surface. Total Depth to be 4' Bel,ow Existing round. Mound Over Trench to Provide a Minimum of 3 of Cover or Provide 2" of Direct Bury Insulation and 2' of Cover. 3/16" Diameter Holes 2.25 '~0. S.T.£... 1~ DRAINFIELD DETAIL PRESSURE DISTRIBUTION CALCULATION Elevation at Highest Discharge Point Pressure at Highest Discharge Point Liquid Level in Tank (Elevation) Diameter of Holes in Distribution Line Diameter of Distribution Line Hole Spacing in Distribution Line Length of Transport Line Diameter of Transport Line 125' 5' Head 115' .1875" (3116") 2.25' 65' 1.25" Q = 12.4d~' = 12.4(.1875)(.1875)~/~- = .9748 GPM/Orifice = .9748 * 24 = 23.4 GPM TDH = (130-115) + .0192(23.4)(23.4) = 15 + 10.5 I.Z~7 + .000995(23.4) (65) (1.25) ~' b ~ + 7.4 = 32.9 Therefore 24 Orifices - 12 in Each Lateral @ 2.25' Spacing ill I~:::ll~i~l ~:li· - ~d EFFLUENT PUMP~ '~ [i l/2Hptol I/2Hp ;; SINGLE'PHASE, 60HZ i, _~ llS/230 VOLT ~ ~ PC#2 . . r "~l' ~ ~ig~ ' ~ '..~ '_ LA-I--. - '~-,'~'-.~ - ~'i ,: ,t' : ~ II,I ~ , . ~. :, ,~ }: ,:,! .. -- .~-~ - ~i"?' '~"- "~ . ..t.A-.~. ~?,~..--. O~ENCOSYSTEMS, INC ] !',!L2'T. D!-e-,C-HA.~GE.- GPM [2826~OLONIAf-ROAD ROSEBURG, OR97470 (503)6T3-0165] ON-SITE WASTEWATER DISPOSAL SYSTEM CONSTRUCTION AND MATERIAL SPECIFICATIONS SUBJECT: LOT 16, BLOCK 5, RIVERVlEW ESTATES SUBDIVISION GENERAL: The scope of this project includes the procurement and placement of a new 1,250-gallon combination septic tank and lift station and pressure distribution system. Work also includes the construction of 2 - 27' long x 5' wide x 2' effective depth absorption trenches at the location shown on the attached Site Plan. The new trench distribution piping shall be constructed 2' below existing ground level for a total trench depth of 4'. Direct bury insulation may be required to provide the minimum coverage required over the new trench. In lieu of insulation 3' of cover may be placed atop geotextile fabric over the new trenches. Construction shall be in accordance with the approved site plan, design drawings, Municipal Permit with any special provisions or conditions, and all applicable State and Municipal Wastewater Disposal Regulations. The Contractor shall be responsible for obtaining all underground utility locates and for the layout of the septic system and verification of the location of all lot lines. Unless specifically agreed otherwise, the contractor shall be responsible for final grading areas subsequently depressed from soil settling. Property owner shall be responsible for revegetation of affected areas unless specifically agreed otherwise. Contractors installing wastewater disposal systems must be certified by the Municipal Department of Health and Human Services for system installations, Owners installing their own systems must receive prior approval from D.H.H.S. before beginning system installation. SEPTIC TANK/LIFT STATION INSTALLATION The 1,250-gallon septic tank/lift station must be constructed by certified tank manufacturer. Construction shall include an 18" manhole to provide access to the lift station. 2. The septic tank shall be sufficiently bedded to prevent settling or shifting of the tank. 3. All standpipes on the septic tank shall extend a minimum of 12 inches above final grade, 4. Tanks installed without 4' of cover shall have a minimum of 2" of direct burial insulation. A foundation cleanout shall be installed one to four feet from the building foundation. Two cleanouts are required between the tank and the drain field. Lot 16, Block 5, Riverview Estates May 28, 2001 Page 2 of 3 6. Final grading over the tank shall be such that a positive slope exists away from the septic tank. DRAIN FIELD CONSTRUCTION: 1. The drain field shall be constructed to the dimensions shown on the design, The bottom of the trenches shall be within 2" of level. 2. Distribution piping must be placed level with perforations down atop a level bed of drain field rock. Rock should then be placed over the pipe to provide a minimum of 2" of cover. 3. A silt barrier or geotextile fabdc must be placed between the drain field rock and the natural soil backfill. 4, Monitor tubes must be 4" in diameter and installed at the locations shown on the design. The portion below ground must be perforated. Contractor shall vedfy the septic tank and drain field are a minimum 100' away from any pdvate water wells in the area, 150' from a Class "C" Well or 200' from any community well. Direct bury insulation must be placed over the distribution system if less than 3' of backfill depth is available. Finish grade over the trench must be mounded to prevent settlement or depressions. 7. Grade area surrounding the absorption trenches to drain away. A minimum 2' of accepting soil is required below the drain field rock for a 5' wide trench. Contractor shall verify this condition prior to placement of the rock. All pockets of unacceptable materials must be removed and replaced. MATERIAL SPECIFICATIONS: The lift station must be constructed by a municipally approved septic tank manufacturer. An Orenco 20 OSI 05 HHF-5 pump is recommended. 2. The following pipe materials are approved for use in septic system installations in the Municipality of Anchorage: Cast Iron (perforated and solid), ASTM D3034 or P.V.C. (perforated and solid). ASTM F810 or H.D.P.E. (perforated, but not solid) and ASTM D2662 or A.B.S. (perforated and solid). 3. Insulation shall be at least 2" thick extruded direct burial polystyrene (Dow Chemical Co. Styrofoam HI or equal). 4. Septic tank inlets and outlets shall be fitted with watertight couplings (Caulder, Femco, or equal). Lot 16, Block 5, Riverview Estates May 28, 2001 Page 3 of 3 5. A permeable geotextile fabdc (Typar, Mirafi or equal) must be installed between the final drain rock layer and the native soil layer. 6. All drain rock shall be .5" to 2.5" in diameter with less than 3% passing the #200 sieve. INSPECTIONS: Municipal Ordinance requires a minimum of two inspections. These inspections must be conducted under the supervision of a professional engineer registered in the State of Alaska. The first inspection must be conducted after the excavation of trenches, beds or pits and before the installation of any gravel. A septic tank may be set in place, but may not be bacldilled. The second inspection must be conducted after the placement of the geotextile fabdc, gravel, distribution piping, standpipes, cleanouts and insulation. No backfill should be in place at the time of inspection. Contractor shall provide a copy of all field survey layout and construction notes for use in preparing the certified as-built of the completed system. Rick Mystrom, Mayor Department of Health and Human Services 825 "L" Street P.O. Box196650 Anchorage. Alaska 99519-6650 http: :www c~ anct~orage.ak.us May ?, 1999 Brian N & Kathryn K Grandorff 19546 3rd Street Eagle River, Alaska 99577 8421 Subject: Lot 16 Block 5 River View Estates Subdivision Permit # SW980100 P1D # 050-792-17 The subject permit, issued May 7, 1998 by this office for a single family well and/or on- site wastewater system, has expired as of May 7, 1999. A new permit must be obtained from this office for a well and/or on-site wastewater system NOT installed by the expiration date. If you have drilled the well, a well log must be sent to this office for documentation of the installation and to close the permit. If a licensed Professional Engineer has inspected the installation of the on-site wastewater system, the original as-built inspection report must be sent to this o~ice for review, approval and documentation. All inspection reports must be submitted within 30 days of construction completion. When applying for a new permit, the fees are: $320.00 for an on-site wastewater permit; $120.00 for a well permit and $440.00 for a combined on-site wastewater and well permit. If you have any questions, please call this office at 343-4744. S~ncerely~' Jamqs Cross, PE Program Manager On-site Services enc: Copy of Permit PAGE 1 OF 1 MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH ~5.ND HUM3kN SERVICES P.O. BOX 196650, 825 "L" STREET, ROOM 502 ANCHORAGE, A~LASKA 99519-6650 ON-SITE WELL AND WASTEWATER DISPOSAL SYSTEM PERMIT PERMIT NUMBER:SW980100 DESIGN ENGINEER:S & S ENGINEERING OWNER NAME:GR3kNDORFF BRIAN N & KATHRYN K OWNER ADDRESS:2221 MULDOON ROAD SPACE 577 3kNCHORAGE, ALASKA 99504 DATE ISSUED: 5/07/98 EXPIRATION DATE: 5/07/99 PARCEL ID:05079217 LEGAL DESCRIPTION: RIVER VIEW ESTATES BLK 5 LT 16 LOT SIZE: 41971 (SQ. FT.) NUMBER OF BEDROOMS: 4 THIS PERMIT: 4 THIS PERMIT IS FOR THE CONSTRUCTION OF: DISPOSAL FIELD /SEPTIC TANK / WELL SYSTEM ALL CONSTRUCTION MUST BE IN ACCORD~kNCE WITH: THE ATTACHED APPROVED DESIGN. ALL REQUIREMENTS SPECIFIED IN ~%NCHORAGE MUNICIPAL CODE CHAPTERS 15.55 kND 15.65 AAID THE STATE OF ALASKA WASTEWATER DISPOSAL REGULATIONS (18AAC72) kND DRINKING WATER REGULATIONS (18AAC80) . THE ENGINEER MUST NOTIFY DHHS AT LEAST 2 HOURS PRIOR TO EACH INSPECTION. PROVIDE NOTIFICATION BY CALLING 343-4744 ( 24 HOURS ) (NOT REQUIRED FOR WELL ONLY PERMIT) FROM OCTOBER 15 TO APRIL 15 A SUBSURFACE SOIL ABSORPTION SYSTEM UNDER CONSTRUCTION DURING FREEZING WEATHER MUST BE EITHER: A. OPENED A/gD CLOSED ON THE SAME DAY B. COVERED, SEALED ~kND HEATED TO PREVENT FREEZING THE FOLLOWING SPECIAL PROVISIONS. SPECIAL PROVISIONS DATE: ROBERT C. COWAN, P.E. April 17, 1998 CIVIL ENGINEERS (907) 694-2979 FAX (907) 694-1211 HEALTH AUTHORITY APPROVALS SEWER&WATER MAIN EXTENSIONS SEWER&WATER INSPECTION ENGINEERING STUDIES A.ND REPORTS WELL INSPECTION & FLOW TEST SITE PLANS ROAO OESIGN SOIL TEST PERCOLATION TEST STRUCTURAL & MECHANICAL INSPECTIONS ON SITE WASTEWATER DISPOSAL SYSTEM DESIGN MUNiCiPALITY OF ANCHORAGE Department of Health and Human Services P.O. Box 196650 Anchorage, AK. 99519 REFERENCE: Lot 16, Block 5, Riverview Subdivision Request you issue a permit to iustall a septic system to serve the proposed four bedroom house on the referenced property. Txvo test holes were excavated and a percolation test was perfo~ned. The approximate locations of the test holes are located on the attached site plan. At the time of excavation, groundwater was encountered in the test hole #1 at 4 fi. After seven day groundwater monitoring, the monitoring tube was checked and gn'oundwater was found a 3 ft. In test hole #2, at the time of excavation, the groundwater level was at 9 ft. After seven day groundwater monitoring, the water level was unchanged. We do not anticipate any adverse effects on neighboring wells, septic systems or drainage patterns by the installation of the proposed septic system. There are no points of contamination within the proposed well radius which can be seen on the attached site plan. If you require additional information, please contact us. Sincerely, Robe~l C. Cowan, P.E. RCC/jlm Enclosure 17034 NORTH EAGLE RIVER LOOP · SUITE 204 · EAGLE RIVER, ALASKA 99577 1"=60' SCALE / SITE PLAN DESIGN ~£LLs ~I~IN 100' OF Z~ -- ~0TM ~m 0~o ~m~m mom ~ _.~-- rZm O~mm / 4 N.T.S. DESIGN PROFILE SCALE o, , o, ~o.~ ~uO ~ - I I I ~ ,~ , ,~ ~ ' i ' " I ~1 I I ~1I ~ " " " ~s~'~ ~i .,.3~ , ,o , ~ h .~ ," n~ ~, PERFORMED FOR: LEGAL DESCRIPTION: 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19- 2O Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG -- PERCOLATION TEST DATE PERFORMED: Township, Range, Section: I I WAS GROUND WATER ENCOUNTE"ED? IF YES, AT WHAT DEPTH? Oeplh to Waler After., Moniloring? Date: Gross Net Depth to Net Reading Date Time Time Water Drop PERCOLATION RATE __ (m~nutesCmch) PERC HOLE DIAMETER TEST RUN BETWEEN __ FT AND __ FT COMMENTS $ & $ EblG~NEERING 17034 Eagle l,~iver Lot~p-RoadTNc,. =04 ' ~:" PERFORMED B,~agle [,iver, &t~,, 99577 /ff~(~/2 &~ ~'- CER]IFY THA% THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFEC] ON THIS DATE' DATE: ~ /I O~ ~[ ~" 72 008 (Rev, 4/85) PERFORMED FOR: LEGAL DESCRIPTION: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 2O COMMENTS Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG -- PERCOLATION TEST DATE PERFORME::(~.'. Township, Range, Section: SLOPE SITE' PLAN WAS GROUND WATER ENCOUNTERED? s L IF YES, AT WHAT j DEPTH? ~ O P E f,L~ ..¢' Depth to Waler A~terq//.~ / Monitoring? Dote: Gross Net ~ N) Depth tO Net Reading Date Time Time t'4, t Water Drop 6 ~ ] ~ ~/~".. ~/~" PERCOLATION RATE /~ ,'"~ (m,nutes/,nch) PERC HOLE DIAMETER TEST RUN BE'I'WEEN FT AND FT S & $ i';'.N~INE. ERING / / . ..... -"-'~ I lA.-...-. CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: L/ / l ¢~) (1 ~ 72~008 (Rev. 4/85J ROBERT C. COWAN, P.E. HEALTH AUTHORITY APPROVALS SEWER & WATER MAIN EXTENSIONS SEWER & WATER INSPECTION ENGINEERING STUDIES AND REPORTS WELL INSPECTION & FLOW TEST SITE PLANS ROAD DESIGN SOILTEST PERCOLATION TEST STRUCTURAL & MECHANICAL INSPECTIONS ONSITE W,~ST EWATE R OISPOSAL SYSTEM DESIGN ON-SITE WASTEWATER DISPOSAL SYSTEM CONSTRUCTION PRACTICES and MATERIAL SPECIFICATIONS CIVIL ENGINEERS (907) 694-2979 FAX (907) 694-1211 REFERENCE: Lot 16, Block 5, Riverview Subdivision April 17, 1998 GENERAL: The scope of this project includes the installation of a 1500 gallon S.T.E.P.system, and a five foot wide drainfield to serve the proposed four bedroom house located on the referenced property. Construction shall be in accordance with the approved site plan and design drawings, Municipal permit with any special provisions or conditions, and all applicable State and Municipal Wastewater Disposal Regulations. The contractor shall be responsible for obtaining any necessary underground utility locates. Unless specifically agreed otherwise, the property owner shall be responsible for final grading areas subsequently depressed fi'om soil settling. On all leachfield mound systems, the property owner shall be responsible for ensuring a satisfactory vegetation growth over the mound area. Contractors installing wastewater disposal systems must be certiffed by the Municipal Health Department for system installations. Owners installing their own systems must also receive prior approval from the Municipal Health Department. SEPTIC TANK INSTALLATION: A septic tank is to be constructed by a certiffed septic tank manufacturer. Construction shall include two 4" cleanouts for pmnping access. The septic tank shall be sufficiently bedded to prevent settling or shifting of the tank. All standpipes on the septic tank shall extend a miuimum of 12 inches above final grade. 4. Septic tanks installed with less than 4 ft. of cover shall be insulated. 17034 NORTH EAGLE RIVER LOOP · SUITE 204 · EAGLE RIVER, ALASKA 99577 Page Two Lot 16, Block 5, Riverview Subdivision April 17, 1998 A foundation cleanout shall be installed one to four feet fi'om the building foundation. In the line between the tank and the leachfield there shall be two adjacent cleanouts (unless an effluent pumping system exists within the septic tank). These cleanouts shall be located on undisturbed soil not more than 10 ft. from the tank. The first cleanout, in line, shall be to clean toward the leachfield. The second cleanout shall be to clean towm'd the septic tank. Final grading over the septic tank shall be such that a positive slope exists axvay from the septic tank. ABSORPTION TRENCH/DRAINFIELD INSTALLATION: Excavate the proposed trench to the dimensions shown on the design. The bottom of the excavation shall be within 2 inches of level. If the sidewalls of the excavation become smeared, they must be raked or scratched (ruffed-up) before gravel (sewer rock) placement. Once the gravel is installed, the distribution pipe is to be installed level with the perforations faced downward. Gravel is then to be placed over the distribution pipe to provide a minimum of 6 inches of cover over the pipe. A silt barrier must be installed between the final gravel layer and the native soil backfill. Ensure the silt bmTier covers the entire gravel surface before placing backfill. Monitor tubes shall be of four (4) inch diameter, installed approximately in the locations shown on the design, and extend a minimum of 12 inches above final grade. The portion of the monitoring tube extending through the gravel shall be perforated fi'om the bottom of the trench to the invert of the distribution pipe. This is equivalent to the effective depth of the gravel as noted on the design. Backfill over the final gravel layer must not be less than twenty-four (24) inches. Insulation must be installed when the backfill depth is less than thirty-six (36) inches. The finish grade over the trench must be mounded to prevent the formation of a depression after settling. MINIMUM MATERIAL SPECIFICATIONS: Any septic tank proposed for installation must be constructed by a Municipal approved septic tank manufacturer. The following pipe materials are approved for use in septic system installations in the Municipality of Anchorage: Page Three Lot 16, Block 5, Riverview Subdivision April 17, 1998 Type of Pipe Perforated Solid Cast Iron Yes ASTM D3034 (PVC)' Yes ASTM F810 (HDPE) Yes ASTM D2662 (ABS) Yes Yes Yes No Yes Use of a type of pipe other than listed above must be approved by the inspecting engineer. Insulation shall be at least 2" thick extruded direct burial polystyrene (Dow Chemical Company Styrofoam HI or equal). Septic tank inlets and outlets shall be fitted with watertight couplings (Caulder, Fernco, or equal). A pe~rneable nontoxic silt barrier (Typar 3401, Mirafi 140N, or eqnal) must be installed between the final leachfield gravel layer and the native soil backfill. All leachfield gravel (sewer rock) shall be 0.5"-2.5" screened gravel with less than 3% passing the #200 sieve. When sand is being used as a filter material, its gradation specifications must conform to CUlrent M.O.A. or D.E.C. requirements, which ever requirement applies. INSPECTIONS: Typically there will be a minimum of thi'ee (3) inspections required during the installation of the wastewater disposal system. These inspections will occur as follows: The first inspection must be conducted after the excavation of ditches, pits, trenches, or beds and before the installation of any gravel. A septic tank may be set in place, but may not be backfilled before this inspection. The second inspection must be conducted after the placement of the silt barrier, gravel, distribution lines, standpipes, cleanouts, and insulation, but before the placement of any other backfill. 3. The final inspection is to occur upon final grading of the property. Page Four Lot 16, Block 5, Riverview Subdivision April 17, 1998 Often there will be more than these 3 inspections required. Especially with the installation of multiple trenches, sand filters, pressurized distribution systems, etc. Thus, the inspecting engineer is to be contacted at least 24 hours prior to the start of construction. If necessary, a pre-construction meeting will take place on-site. The inspecting engineer will not coordinate, direct or control in any way the contractors activities. The owner shall contract with the contractor to perform the work outlined in these specifications and plans and in accordance with the attached M.O.A. pernfit. There will be no contractual arrangement existing between the contractor and S & S Engineering. S & S Engineering shall be the owner's representative and will inspect the work as stated above to document the contractors activities. Final acceptance of the contractors work rests with the owner and the M.O.A. S & S Engineering shall have no liability to the owner or to others for acts or omissions of the contractor or any other persons perforating work on this project or the failure of the contractor to carry out the work in accordance with these construction documents. S & S Engineering's inspecting engineer will not be responsible for the construction means, methods, techniques, sequence, procedm'es or the safety precautions incident to this project. CONTRACTOR//NSTALLER Municipality of Anchorage Development Services Department Building Safety Division On-Site Water and Wastewater Program 4700 South Bragaw St. P.O. Box 196650 Anchorage, AK 99519-6650 www.ci.anchorage.ak.us (907) 343-790-1 CERTIFICATE OF HEALTH AUTHORITY APPROVAL FOR A SINGLE FAMILY DWELLING Parcel I.D. 050-792-17 1. GENERAL INFORMATION Complete legal description HAA# Expiration Date: Lot 16, Block 5. River Vie,,,; Estates Subdivision Location (site address or directions) 7401 Watedall Drive Current Property owner(s) ~,tfi1&M Ccntractino Day phone 688-t236 Mailing address Lending agency P.O. Box 670495 Chuciak, AK 99567 Day phone Mailing address Real Estate Agent Day phone Mailing Address Unless otherwise requested, HAA will be held by DSD for plckup. 2. NUMBER OF BEDROOMS: Three(3) 3. TYPE OF WATER SUPPLY: Individual Well Individual Water Storage Community Class Public Water System Well TYPE OF WASTEWATER DISPOSAL: [] Individual On-site [] [] Individual Holding tank [] [] Community On-site [] [] Public Sewer [] The Municipality of Anchorage Development Se,vices Department (DSD) Issues Certificates of Health Authority Approval (HAA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. Certificates of H,~alth Authority Approval are required for the transfer of title (except between spouses) for properties served by a single family on-site wastewater disposal and;or water supply system. DSD a!so issues HAAs upon request to homeowners. Certificates of Health Authority Approval are valid for 90 days from the date of issue for properties seined by a private or Class C well and may be reissued with new water sample results less than 30 days old. (Certificates may be reissued for a period of up to one year with valid water samples.) Certificates are valid for one year for properties served by Class A or B wells or a public waIer syslem. The Municipality of Anchcrage is not responsible for errors or omissions in the professional engineer's wcrk. 4. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation dale shown below, I verify that my investigation, based on procedures oullined in the Health Authodly Approval Guidelines for this application, shows that the on-sile water supply and/or wastewater disposal system is(are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I fudher verify Ihat based on the information obIained from the Municipality of Anchorage files and from my invesfigafion and inspeclion, the on-site water supply and/or wastewater disposal system is(are) in compliance with a~l applicable Municipal and Slato codes, ordinances, and regulations in effect at the time of installation. Name of Firm Anderson Enqineerinq Address P.O. Box 240773 Anchoraae, AK 99524 Engineer's Printed Name I~,lichael E. Anderson, P.E. Phone 522-7773 Dale 11/17/02 5. DSD SIGNATURE ~ Approved for _'~ Disapproved. Conditional approval for bedrooms. bedrooms, with the following stipulations: Additional Comments Attachments: HAA Checklist Septic System Advisory Wall Flew Advisory X Maintenance Agreements Supplemental Engineer's Report Other Original Certificate Date: / i - ~ l- 0 ..~-._ Municipality of Anchorage Development Services Department Building Safety Division On-Site Water & Wastewater Program 4700 South Bragaw St. P.O. Box 196650 Anchorage, AK 99519-6650 www.ci.anchorage.ak.us (9O7) 343~79O4 HEALTH AUTHORITY APPROVAL CHECKLIST Legal Description: Lot 16, Block 5, River View Estates A. WELL DATA Well type Pri~ate Date completed 6F~/2002 Total depth 120 ft. if A, B, o~ C provide PWSID # Sanitary sea~ (Y~N) ~_ Cased to .~I ft. FROM WELL LOG Date o¢ test Static wal~' tevel Well production WATER SAMPLE RESULTS: 0 ff. 7 gp.m. Bo Ce Parcel ID: 050-792-17 Well Log (Y/N) Y W~res properly protected (Y/N) Y Casing height (above ground) >24 AT INSPECTION tl/9r2oo2 o ft. 5.5,,1 g.p.m. in. Coliform 0 colonies/19o mi. Date of sample: 11J9/2002 SEPTIC/HOLDING TANK DATA Tank Type/Material Sl'EP/Stesl Tank size ~.250 gal. Foundation cleanout (y/N) y_ Date of puh~ping ABSORPTION FIELD DATA Date installed 7/24/2~2 Length 54 Total depth 5.~ ft. Dale of adequacy test N~ate .6 mg./L Coaested by: MEA Other bacleda {} colonies/lO0 mi, Fluid depth in absorption field before test in. Water added . gal. Elapsed Time: min. Final fluid depth, in. Absorption rate >= Any rejuvenalkm treatment (past 12 mo.) (YIN & type) N If yes, give date Number of Compartments 3_ Depression Over tank (Y/N) N Pumper New Constm~on Date installed 7/19/2{X)2 Cteanouts (Y/N) v High water alarm (Y/N) Y ' Soilrating (g.p.dJft~orft;/bdrm)12GPD/S., F System type 5' Wide Trench ft. W~dth $ ft. Graval below pipe 2 Eft. absorption area .3~5.7~f~ Monitoring tube Y_ Depression over field _N Results (Pass/Fail) For. bedrooms New depth in. g.p.d. D. LIFT STATION Date installed 7/19/2002 'Pump on' level al 42 in. Datum Bottom of Tank SEPARATION DISTANCES Size in gallons 250 'Pump off" level at 42 in. Cycles tesled SEPARATION DISTANCES FROM WELL ON LOT TO: Septic tank/lift station on lot >100' Absorption field on lot >100. Public sewer main N/A Sewer/septic service line >25* Property line >t0' Water Service line >10' Curtain drain None Noted F. COMMENTS ManhoteJAccess (Y/N) Y' High water alarm level at 44 Meets alan"n & circuit requirements? Y On adjacent lots >!00. On adjacent lots >t00' Public sewer rnanhole/cleanout N/A Holding lank in. SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO: Building foundation >5' Property line >5* Waler main N/A Water service line >10' Wells on adjacent lots >t00. SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO: Building foundation >t0' Surface water >100' Wells on adjacent lots >t00' G. ENGINEER'S CERTIFICATION Absorption field >5' Surface water >t00. Water main >t0. Driveway, pa~Jng/vehicte sto~age >25' I certify that I have determined through field inspeclfons and review of Municipal records that the above systems are in conformance with MOA HAA gu~eli~es in effect on this date. Engineer's Printed Name Michael E. Anderson, P.E. Date 111t5/02 HAA Fee S Date of Payment (Rev. ~) ..':. Wa~ F~ $ Date ~ Paymenl R~ipt Num~ Oct. 14 ~ ~?l~:'Pt'l P4 Rec.eived T!me.'Oct. 14,- 11-15-.0Z 10:11 FROI,~CT&E ENVIROHR~NTAL SRV '~t~'. CT&E Environmental ,Services Inc. 9075615301 T-750 P.03/03 F-243 CT&F_. Ref.# Client Name Prole~ Name/~ Client Sample ID Matrix PWSID 0 Sample Remarks: 1027768003 .A~dcr~on ,~ng~eering Various Lot 16, Block 5, Rivet View D~'i.~i~g Water All Datesffl'lmes are Alasl~ Standard Time Printed Date/Time 11/15/2002 10:23 Collected Date/Time I lit 1/2002 12:30 Rerelved DateFl'lme 11111/2002 16:00 Technical ~ Step~C. £de Result~ PQL Units Mc~od ABowehle Prep Anal/sis Limits D~tt~ Date Init Wa~:o~a Depa~'tmemt: Nitrate*N 0.600 U 0.600 mrS- EPA 30o.0 11/12/02 ~.crob:Lolos3~ Labo:ato:~' Total Coliform col/100mL SM 18 92.?.2B 11111/02 KAP Received Time Nov.15. IO:I7AM