ON-SITE WASTEWATER DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT
PID Number: .051 "043d52
Wastewater System: New
ABSORPTION FIELD
5' Wide Trench
I of 3
Number of Bedrooms:
Four (4)
Soil Rating: Total Depth ~'om original grade:
LEGAL DESCRIPTION 1.2 Gp~ 7.5 ri.
BlOck: Lot: Sutxlivlsion: eepth to pipe bottom from o~ginal grade: G~vel depth beneath pipe:
5 12 Knik View Estates 3.5 Fl. 4 ~,.
To'.vnship: Range; Secllon: Flit added above original grade: Gravel Length:
.5 ,,. 50 Fi.
Grayel width: Number ~f Ithe~ I Distance belw~en lines:
Well: Community Water 5 R. '1 I Ft.
Classification (Private. A. B. C): Total Depth: Case~ to: Total abeo~tior~ area: Pipe Material:
Class A Ft. ~,. 500 ,e ASTM D3034 PVC
Driller: Date Drilled: Stallc Wale,' Level: Ir~allec Dale Installed:
it. MM&M Contracting 9/3-6/02
v.,.:GP~ i~,..s~.tt~,. Ic~'~'~Gr~d:. FI. TANK
SEPARATION DISTANCES' ~ Septic [] Holding C] S.T.E.P. [~] Other:
T~ To Septic Absorption lift Holding
~o~
Tank Field Station Tank
~ell >200' >200' N/A N/A
Su~,r >100' >100' N/A N/A
~ol~.~ >5' >10' N/A N/A
~o~d~,~ >5' >10' N/A N/A
c~ None Noted
Remarks:
SewerLine Anchorage Tank 1,250
>25' Steel Two (2)
LIFT STATION 2 NONE ON LOT
I
BENCH MARK
Patio Door Stoop Back of House.
100.0 Ft
Inspections performed by: Tim Kimbrough
Dates: 1~t 9/3/02
2"d 9/6/02
Department of Health and Human Services approval
Reviewed and approved by'~~ Date: /Z./b
(l~ev. 10/99)
Engineer's Stamp
-- ~:-"
; 49th
~J~\ No. o~-~s,
Municipality of Anchorage
Development Services Department Page 2 of 3
Building Safety Division
On-Site Water and Wastewater Program
On-Site Wastewater Disposal System and/or Well Inspection Report
Permit No. SW020332 PID No. 051-043-52
C4
S2
S1
Foul'
C5 Bedroom
Home
S1 39.6 53.3
S2 45.5 58,0 ~.~
C4 58.6 76.9
M1 56.5 74.8
C5 62.7 58,2
SITE PLAN
SCALE 1" = 40'
Municipality of Anchorage
Development Services Department
Building Safety Division
On-Site Water and Wastewater Program
On-Site Wastewater Disposal System or Well Inspection Report
Permit Number: SW020332
Page 3 of 3
PID No. 051-043-52
95.71'
/
Geotexti[e F~bric
95.51'
/
/
9~.35'" /~
L88,35'
Dr cdn~cie[d Rock
78.5'
50'
PROFILE
Scale: 1" = 10'
AS BUILT
FROM : COUNTRY RERLTY PHONE NO. : 9876881238 Oct. 24 2882 09:06RM P2
,/
Received Time 0ct.24. 8'.30AM
Anchorage Recording P~cinc~, Alaska. and that'.the
raeiats.situated thereon:are ,within lhe prol~'tE, lines arid ~lo:~.ot
overlap or encroach.on the p~O ,l~e. rty ly'm,.g~adj~' _c~t t~.' re'to.,.'tl~at
nO .improvements or~ ,property. lying adja'c~r;t' there~' encroach
on t, he pternise~ i~. q. ll. estlon and.,iBat, ther~.:ar~ RO roaclway~,
transmission lines, or other, visib,le .ea,sem~nts .on said,.proper~
except as indicated h~n, ,. {: . .
Dated at ~E~,gle River,, Alaska
· ... ROBERT C. JOHNSON ";*
$~Ai.E: Regi~_temd Land:Surveyor No. 880-L$
1" = ~ ~," Box 77..04:~,.Eagle. River; Alaska'9~77
/
/ , '/' ./
~-~ ~,~'~ .;~, / / I he, by ce~ that I have su.~eyed ~e fo~ow~g de~Hbed
Municipality of Anchorage
Development Services Department
Building Safety Division
On-Site Water and Wastewater Program
4700 South Bragaw St.
P.O. Box 196650 Anchorage, AK 99519-6650
www.ci.anchorage.ak.us
(907) 343-7904
ON-SITE SEWER/VVELL PERMIT APPLICATION
FOR A SINGLE FAMILY DWELLING
O
Parcel i.D.
Permit Number SW(~O~ 0,~
Property owner(s) MM&M Contracting, Inc.
Mailing address (1) P.O. Box 670495 Chu.qiak, AK 99567
Mailing address (2)
Day phone 688-1236
Zip Code
Legal description (Lot, Block & Sub'd.)
Legal description (Section, Township & Range)
Lot Size
THIS APPLICATION IS FOR:
Sewer Only
Sewer and Well
Sewer Upgrade
THIS PROPERTY CONTAINS:
Hot Tub
Swimm!ng Pool
Therapy Pool
Lot 12, Block 5, Knik View Estates Subdivision
Number of Bedrooms Four (4)
[] Welt Only []
[] Water Storage []
Acre~
[] Jacuzzi []
[] Water Softening Unit []
I certify that the above information is correct. I further certify that this application is being made for a
Single Family Dwelling and is in accordance with applicable Municipal Codes.
(Signature of property owner or authorized agent)
Permit Fees: H~'~)F
Date of Payment: 5' I~ ¢ (~:~
Receipt Number: 2- q5
(Rev. 12/00)
Waiver Fees:
Date of Payment:
Receipt Number:
August 15, 2002
Municipality of Anchorage
Development Services Department
On-Site Water and Wastewater Program
4700 South Bragaw Street
Anchorage, AK 99519-6650
Subject:
Lot 12, Block 5, Knik View Estates Subdivision
Septic System Design and Permit Application
Impacts to Adjacent Properties
Dear Onsite Services Engineer:
The owner of Lot 12, Block 5, Knik View Estates Subdivision intends to construct a four-
bedroom home on the lot. We are therefore requesting a permit be issued for the
construction of a new septic system to serve the proposed home. The attached Site
Plan and backup documentation identify the location and configuration of the new and
alternate septic system and the parameters used in the design. Also identified on the
plans is the test hole location and the locations of the existing systems on adjacent lots.
The subdivision is served by a Class A water system and the approximate locations of
the water service lines are shown. Drainage arrows are also shown and current
drainage patterns will be maintained after construction.
The test holes placed near the location of the proposed and alternate absorption
trenches indicated well to poorly graded sand with gravel and varying amounts of silt
and a percolation rate of between 1 and 2 minutes per inch. No groundwater was
found during the excavation and none was noted during the ensuing monitoring period.
We are therefore proposing to construct a 5' wide absorption trench system with 4' of
drainfield rock beneath the distribution pipe. That pipe will be placed at 3.5' below the
surface with a total depth of 7.5'. The total length of the trench will be 50'.
The ground surface on the lot slopes as shown on the attached Site Plan with fairly
shallow to no slope in the area of the new absorption trench. The new septic tank and
absorption trenches will be constructed in a fairly shallow surface slope area behind the
proposed house in conformance with Municipal requirements and parallel to ground
contours where possible. All components of the new trench will be constructed a
minimum of 200' from the well serving the community water system. The system will
also be constructed a minimum of 100' from any surface water in the area and 10' from
the water service line.
If the system is constructed in accordance with our design the following statements
apply:
Ldt 12, Block 5, Knik View Estates
August 15, 2002
Page Two
The system, if constructed as designed, will have no adverse impact on the wells
in the area or those to be constructed in the future.
The system, if constructed as designed, will have no adverse impact on existing
septic systems in the area or those to be constructed in the future.
The system, if constructed as designed, will have no adverse impact on reserve
space, either surface or subsurface, on any lots located in the area.
The system, if constructed as designed, will have no adverse impact on drainage
patterns in the area. The current drainage pattern will be maintained.
Sincerely,
Michael E. Anderson, P.E.
Attachments
14
15
17
15
19
AREA SYSTEM PLAN
SCALE 1" = 100'
S89150'36"E 204.67 18~5 S89150'36'E 4~3.91
/
/
/
LOT 12, BLOCK 5,
KNIK VIEW ESTATES
'SITE PLAN
SCALE 1" = 30'
LOT 12, BLOCK 5, KNIK VIEW ESTATES
SUBDIVISION
DESIGN FACTORS:
SYSTEM REQUIREMENTS:
4 Bedroom House
Perc. Rate: LT 1 Min./Inch
Application Rate: 1.2 GPD/SF
5' Wide Trench System
1,250 Gallon Septic Tank
4' Drainfield Rock
4 Bedrooms X 150 GPD/I.2 GPD/SF (Application Rate) = 500 SF of Absorption Area
500 SF/5 LF (Width)* .5(Red. Factor) = 50 LF Trench Length
Therefore: Construct a 5' Wide Absorption Trench With a Total Length of 50'. Flowline
Elevation in Trench to be 9' Below Original Ground Surface. Total Depth to be 3.5' Below
Existing Ground. Total Depth to be 7.5'. Maintain 10' Separation From Water Service Line.
NOTE:
6II
Natural
Backfill
-5'0"
Geotextile
Fabric
4" Perforated
PVC (ASTM 3034)
Drainfield
Rock
TYPICAL WIDE TRENCH SECTION
(NO SCALE)
Grade Area Over Trench to Drain Away.
Minimum 6' Separation From Bedrock.
Minimum 4' Separation From Groundwater.
Minimum 100' From Wells in the Area.
Minimum 10' Separation From Water Service Line.
PROJECT #:
PERFORMED FOR:
MUNICIPALITY OF ANCHORAGE
DEPARTMENT OF HEALTH 8~ HUMAN SERVLCES
825 L STREET, ANCHORAGE, AK 99502-0605
SOILS LOG - PERCOLATION TEST
M0238
PAUL MYERS / MM~M CONSTRUCTION
DATE PERFORMED:
812102
LEGAL DESCRIPTION: LOT 12. BLOCK S. KNIK VIEW SUBDIVISION
I0~ '4- .
16 I
18
COMMENTS:
TEST HOLE # TH #1 SLOPE
OB / O0 .
o%
SLIGHTLY DENSE
WELL GRADED
SANDY-GRAVELS: OW
WAS GROUNDWATER
ENCOUNTERED? NO
IF YES, WHAT DEPTH?
DEPTH OF WATER
S
L
DENSE SILTY
SANDS W/GRAVELS: GM
BOH
AND
NO IHPERHEABLES [NCOUNTERED / HOLE PRESOAKED PRIOR TO TEST
SITE PLAN
TH2
TH1
L
O%
GROSS NET DEPTH OF NET
READING DATE
TIME TIME WATER DROP
Staff 8/2/2002 11:00 12"
I 11:10 10 2" 10"
Recharge 11:10 12"
2 11:20 10 2" 10"
12"
10 2" 10"
PERC. HOLE DIAMETER: 6"
FT.
TEST PERFORMED BY: T.L. KIMBROUGH
I, MICHAEL E. ANDERSON, CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE
WITH ALL STATE AND MUNICIPAL GUIDELINES ON THIS DATE:
PROJECT ~:
PERFORMED FOR:
MUNICIPALITY OF ANCHORAGE
DEPARTMENT OF HEALTH & HUMAN SERVICES
$25 L STREET, ANCHORAGE, AK 99502-0605
SOILS LOG - PERCOLATION TEST
M0238
PAUL MYERS / HM&M CONSTRUCTION
DATE PERFORMED:
8/2/02
LEGAL DESCRIPTtON: LOT 12. BLOCK 5, KNIK VIEW SUBDIVISION
TEST HOLE ¢¢ TH #2 SLOPE
OB / OG
SLIGHTLY DENSE
WELL GRADED
SANDY-GRAVELS:
WAS GROUNDWATER
ENCOUNTERED?
IF YES, WHAT DEPTH?
DEPTH OF WATER
AFTER hIONiTOR~NG:
DATE:
O%
NO S
L
O
~ P
DATE
8~2~2002
SITE PLAN
TH2
TH1
O%
O%
GROSS NET DEPTH OF NET
TIME TIME WATER DROP
11:05 12"
11:1.5 10 2.125" 9.8'/5"
11:15 12°.
11:25 10 2.2S" 9.75"
11:25 12"
11:35 10 2.25" 9.75"
18
PERC RATE: 103 MIN./INCH PERC. HOLE DIAMETER: 6"
TEST RUN BETWEEN 3.5 FT. AND /.5 FT.
COMMENTS:
NO IMPERMEABLES ENCOUNTERED / HOLE PRESOAKED PRIOR TO TEST
TEST PERFORMED BY: T.L. KIMBROUGH
I, MICHAEL E. ANDERSON, CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE
WITH ALL STATE AND MUNICIPAL GUIDELINES ON THIS DATE:
ON-SITE WASTEWATER DISPOSAL SYSTEM
CONSTRUCTION AND MATERIAL SPECIFICATIONS
SUBJECT: LOT 12, BLOCK 5, KNIKVlEW ESTATES SUBDIVISION
GENERAL:
The scope of this project includes the procurement and placement of a
new 1,250 gallon septic tank at the location shown on the site plan and
the construction of a 50' long by 5' wide by 4' effective depth
absorption trench also shown on the Site Plan. The total depth of the
trench will be 7.5' below existing ground and the distribution pipe will
be placed at 3.5' below the surface. All components of the septic tank
and absorption trench must be constructed a minimum of 10' from the
water service line on this lot. A minimum of 4' of fill must be placed
atop the septic tank and 3' of fill atop the absorption trench. In lieu of
fill 2" of direct bury insulation may be placed with 2' of fill atop the
insulation.
Construction shall be in accordance with the approved site plan,
design drawings, Municipal Permit with any special provisions or
conditions, and ali applicable State and Municipal Wastewater
Disposal Regulations.
The Contractor shall be responsible for obtaining all underground utility
locates and for the layout of the septic system and verification of the
location of all lot lines.
Unless specifically agreed otherwise, the contractor shall be
responsible for final grading areas subsequently depressed from soil
settling. Property owner shall be responsible for revegetation of
affected areas unless specifically agreed otherwise.
Contractors installing wastewater disposal systems must be certified
by the Municipal Department of Health and Human Services for
system installations. Owners installing their own systems must receive
prior approval from D.H.H.S. before beginning system installation.
SEPTIC TANK INSTALLATION
1. The 1,250-gallon Septic tank must be procured from an approved
septic tank manufacturer and installed at the location shown.
A septic tank is to be constructed by a certified septic tank
manufacturer. Construction shall include two 4" cleanouts for pumping
access.
3. The septic tank shall be sufficiently bedded to prevent settling or
shifting of the tank.
4. All standpipes on the septic tank shall extend a minimum of 12 inches
above final grade.
5. Tanks installed without 4' of cover shall have a minimum of 2" of direct
burial insulation.
Lot 12, Block 5, Knik View Estates
August 15, 2002
Page 2 of 2
6. A foundation cleanout shall be installed one to four feet from the
building foundation. Two cleanouts are required between the tank and
the drainfield.
7. Final grading over the tank shall be such that a positive slope exists
away from the septic tank.
DRAINFIELD CONSTRUCTION:
The drainfield shall be constructed to the dimensions shown on the
design. The bottom of the trench shall be within 2" of level.
Distribution piping must be placed level with perforations down atop a
level bed of drainfield rock. Rock should then be placed over the pipe
to provide a minimum of 2" of cover.
A silt barrier or geotextile fabric must be placed between the drainfield
rock and the natural soil backfill.
o
Monitor tubes must be 4" in diameter and installed at the locations
shown on the design. The portion below ground must be perforated.
Contractor shall verify the septic tank and drainfield are a minimum
100' away from any private water wells in the area, 150' from a Class
"C" Well or 200' from any community well.
Direct bury insulation must be placed over the distribution system if
less than 3' of backfill depth is available. Finish grade over the trench
must be mounded to prevent settlement or depressions.
Grade area surrounding the absorption trench to drain away.
A minimum 2' of accepting soil is required below the drainfield rock for
a 5' wide trench. Contractor shall verify this condition prior to
placement of the rock. All pockets of unacceptable materials must be
removed and replaced.
MATERIAL SPECIFICATIONS:
1. Septic tanks must be constructed by a municipally approved septic
tank manufacturer.
°
The following pipe materials are approved for use in septic system
installations in the Municipality of Anchorage:
Cast Iron (perforated and solid), ASTM D3034 or P°VoC. (perforated
and solid), ASTM F810 or H.D.P.E. (perforated, but not Solid) and
ASTM D2662 or A.B.S. (perforated and solid).
Insulation shall be at least 2" thick extruded direct burial polystyrene
(Dow Chemical Co. Styrofoam HI or equal).
Septic tank inlets and outlets shall be fitted with watertight couplings
(Caulder, Fernco, or equal).
Lot 12, Block 5, Knik View Estates
August 15, 2002
Page 3 of 3
5. A permeable geotextile fabric (Typar, Mirafi or equal) must be installed
between the final drain rock layer and the native soil layer.
6. All drain rock shall be .5" to 2.5" in diameter with less than 3% passing
the #200 sieve.
INSPECTIONS:
Municipal Ordinance requires a minimum of two inspections. These
inspections must be conducted under the supervision of a professional
engineer registered in the State of Alaska. The first inspection must be
conducted after the excavation of trenches, beds or pits and before the
installation of any gravel. A septic tank may be set in place, but may not
be backfilled.
The second inspection must be conducted after the placement of the
geotextile fabric, gravel, distribution piping, standpipes, cleanouts and
insulation. No backfill should be in place at the time of inspection.
Contractor shall provide a copy of all field survey layout and construction
notes for use in preparing the certified as-built of the completed system.
Parcel I.D. 051-043,52
Municipality of Anchorage
Development Services Department
Building Safety Division
On-Site Water and Wastewater Program
4700 South Bragaw St.
P.O. Box 196650 Anchorage, AK 99519-6650
www.ci.anchorage.ak.us
(907) 343-7904
CERTIFICATE OF HEALTH AUTHORITY APPROVAL
FOR A SINGLE FAMILY DWELLING
Expiration Date:
GENERAL INFORMATION
Complete legal description Lot 12, Block 5, Knik View Estates Subdivision
Location (site address or directions) 22542 Judd Street
Current Property owner(s) MM&M Contracting
Mailing address P.O. Box 670495 Chuqiak, AK 99567
Lending agency
Mailing address
Real Estate Agent
Mailing Address
Unless otherwise requested, HAA will be held by DSD for pickup.
NUMBER OF BEDROOMS: Four (4)
Day phone 688-1236
Day phone
Day phone
TYPE OF WATER SUPPLY:
Individual Well
Community Class A Well
Public Water System
TYPE OF WASTEWATER DISPOSAL:
[] Individual On-site []
,,,u,v,uu,~, ,'~u,u u tank
[] Community On-site
[] Public Sewer []
The Municipality of Anchorage Development Services Department (DSD) Issues Certificates of Health Authority
Approval (HAA) based only upon the representations given in paragraph 5 by an independent professional civil
engineer registered in the State of Alaska. Certificates of Health Authority Approval are required for the transfer of
flue (except between spouses) for properties served by a single family on-site wastewater disposal and/or water
supply system. DSD also issues HAAs upon request to homeowners. Certificates of Health Authority Approval are
valid for 90 days from the date of issue for properties served by a private or CIass C well and may be reissued with
new water sample results less than 30 days Did. (Certificates may be reissued for a period of up to one year with
valid water samples.) Certificates are valid for one year for properties served by Class A or B wells or a public
water system. The Municipality of Anchorage is not responsible for errors or omissions in the professional
engineer's work.
4. STATEMENT OF INSPECTION BY ENGINEER
As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation,
based on procedures outlined in the Health Authority Approval Guidelines for this application, shows that the
on-site water supply and/or wastewater disposal system is(are) safe, functional and adequate for the number of
bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the
Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or
wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances,
and regulations in effect at the time of installation.
Name of Firm Anderson Enaineering
Address P.O. Box 240773 Anchorage, AK 99524
Engineer's Printed Name Michael E. Anderson, P.E.
Phone 522-7773
Date 11/23102
DSD SIGNATURE
"~ Approved for ~ bedrooms.
Disapproved.
Conditional approval for
bedrooms, with the following stipulations:
Additional Comments
Attachments:
HAA Checklist
Septic System Advisory
Well Flow Advisory
Maintenance Agreements
Supplemental Engineer's Report
Other
By:
(Rev. 12f00)
Original Certificate Date:
-;': '.' '.'"'" Ca~ihg~hei~l:i~,(~:bOVi~;gmbr~d.)
:AT
:New depth' ,. in.
If y~s,:'gi, ve:date
D. .LIFT STATION
Date installed
Size in gallons
"Pump off" level.at "."ih'! '"~'~: .~
Cycles tested ' ' "
SEPARATION DISTANCES
SEPAI:~TION .DISTANCES'FROM WELL ON LOT TO:'
Septic tanM~..Stat o.n on.Jot, NIA
Manhole/Access (Y/N)'
.i?ig.~. water alarm level at
· Me,ts alarm & circuit requirements?' ~ '
On a~jacent~l.ots...~ NIA', ~'
Absorption field on lot NIA
On adjacent lots NIA.
Public sewer ma~n NIA
':'..Public sewer manholelcleanout NIA
.Sewer/septic Sen/ice line-
Holding ..tank,...'~NIA
SEPARATION;DISTANCES FROM SEPTIC/HOLDING TANK"ON LOFF TO:,
Building foundation '>5'
>200'
Property tine >5'
'Absorption: field >5'
Water service.line >10'
· Surface water >100'
in:
SEPARATION DISTANCE FROM ABSORPTION'FIELD ON.;EOT TO:
Property line · >10'
Watei' Serviceline >'10'
Cudain drain None Noted
COMMENTS
Building foundation >10'
.Surface water >100" '
Wells on adjacent lots >200':
Water main >10"
Driveway, park!rig/vehicle.storage. >25"
Lot is served by AWWU.'water system.
G; ENGINEER'S' CERTIEICATION
I certify that I have determined through field inspections end
review of Municipal records that the above systems are id
confon?~ance with MOA HAA guide,5~3es in effect on this date.
Engineer's Printed Name _ Michael E. Anderson. P.E.
Date?Il/2312002 ' . .. -. ,
HAA Fee $
Date of Payment
Receipt Number
~Rev."l 2/00)