HomeMy WebLinkAboutSOUTH HILLS BLK 4 LT 3South Hills Block 4 Lot 3 #017-072-12 Inspection Report_1-1-1Ydoc Municipality of Anchorage Community Development Department Page 1 of 3 On -Site Water and Wastewater Program 4700 Elmore St. • P.O. Box 196650 Anchorage, AK 99519-6650 • http:l/www.muni.org/onsite • (907) 343-7904 ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP141518 PID Number: 017-072-12 ❑ New ❑✓ Upgrade Name: ABSORPTION FIELD Peter Bockman ❑ Deep Trench ❑✓ Shallow Trench ❑ Bed ❑ Mound Address 7635 Old Hillside Way ❑ Other Phone Number of Bedrooms Soil Rating Total depth from original grade 4 1.2 GPD/SF 8/6 Ft. LEGAL DESCRIPTION Depth to pipe invert from original grade 7/4 Ft. Gravel depth beneath pipe 1.0 Ft. Subdivision Block Lot South Hills 4 3 Fill added above original grade 0-1 Ft. Gravel length 90.0 Ft. Township Range Section Gravel width 5Ft. Beds: Number of Lines N/A Distance between lines N/A Ft. SEPARATION DISTANCES To Septic Absorption Holding Sewer Total absorption area Number of trenches Dist. between trenches From Tank Field Lift Station Tank Line 517 Ftp 2 13.OFt. Well 100+ 193.9 NA N/A 25+ TANK ❑ Septic ❑ S.T.E.P. ❑ Holding ❑ Other Manufacturer Existing Capacity I 1250G31. Surface Water 100+ 100+ N/A N/A Material Number of compartments 2 Lot Line 5+ 12.7 N/A N/A NA FoundationLIFT 5+ 176.9 N/A N/A STATION Manufacturer Capacity Gal. Curtain Drain 50+ 50+ N/A N/A Pump on level at Pump off level at High water alarm at Remarks in. in. in. Pump make and model Electrical Inspections performed by PIPE MATERIAL House to tank Tank to 3034 drainfield Installer A+ Home Services Drainfield 3034 CO/MT 3034 Inspector Pannone Engineering Services BENCHMARK (Assumed elevation) 100ft Inspection„ 12/15/14 a 12/15/14 Location and description dates: 2 Concrete Stair Stoop 3” 12/15/14 0 12/16/14 COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL Engineer's Stamp +�"ft, 1 Conditional Approval: Date ......... �►ig�P THOAF • • ��everi �E$, t�a�ntirae �o#ti�,/ CE 8149 .Ag/ Y. i� Approved Date Inspection Report_1-1-1Ydoc I DRAIN FIELD (E) IN FAILURE REMOVED AND REPLACED W/ (I EA) 5'W x 45LF x 1.0'ED x 8.0'TD (S) & (1 EA 5'W x 45LF x 1.O'ED x 5.O'TD (N) - REPLACED REMOVED BIOMATT BELOW TO WITH (1'+) SAND AS NEEDED 12.7 r SEPTIC AREA. (E) -M TNO WELLS/ SEPTICS /M M � WITHIN 200' OLD RABBIT CREEK CAD IZ 1 I N o V- I WELL (E) 1 16.4 I M3 1 -M I I \ M TH-4 (ANDERSON 2002) NOTES: RECORD DRAWING PLAN TH-6 ( ANDERSON 2002) CO AND FS (E)v\ _W—W\ ps \ I I �,,-5, LOT 3 PREVIOUSLY ABANDONED WELL (E) DRAIN \IFIELD (E) 1 + 7 z Iw DRIVEWAY A 4 B i HOUSEE (E) WELL (E) 70'DT�1,�ENT - �� ' 90uTh "lLiSiDE Wqy PANNONE ENG SVC, LLC P.O. BOX 100217 ANCHORAGE, AK 99510 PHONE (907) 272-8218 FAX (907) 272-8211 SOUTH HILLS, BLOCK 4, LOT 3 PETER BOOKMAN 7635 OLD HILLSIDE WAY ANCHORAGE. AK 99516 2 12509 SEPTIC TANK (E) yI SEPTIC AREA (E) 1 s N I � OF Al--"�\l h 2/18/2014 StevenR. Pannone pERM1T N0. �• CE 8149 .'cam// OSPt 41518 Vis' r �T�PROFES5101��'�� Sheet 2 OF 3 A B C1 180.1 194.3 Mi 181.3 195.8 C2 181.8 204.0 M2 180.5 202.4 C3 200.1 211.2 M3 201.3 212.6 C4197.8 216.6 M4 196.5 215.1 I DRAIN FIELD (E) IN FAILURE REMOVED AND REPLACED W/ (I EA) 5'W x 45LF x 1.0'ED x 8.0'TD (S) & (1 EA 5'W x 45LF x 1.O'ED x 5.O'TD (N) - REPLACED REMOVED BIOMATT BELOW TO WITH (1'+) SAND AS NEEDED 12.7 r SEPTIC AREA. (E) -M TNO WELLS/ SEPTICS /M M � WITHIN 200' OLD RABBIT CREEK CAD IZ 1 I N o V- I WELL (E) 1 16.4 I M3 1 -M I I \ M TH-4 (ANDERSON 2002) NOTES: RECORD DRAWING PLAN TH-6 ( ANDERSON 2002) CO AND FS (E)v\ _W—W\ ps \ I I �,,-5, LOT 3 PREVIOUSLY ABANDONED WELL (E) DRAIN \IFIELD (E) 1 + 7 z Iw DRIVEWAY A 4 B i HOUSEE (E) WELL (E) 70'DT�1,�ENT - �� ' 90uTh "lLiSiDE Wqy PANNONE ENG SVC, LLC P.O. BOX 100217 ANCHORAGE, AK 99510 PHONE (907) 272-8218 FAX (907) 272-8211 SOUTH HILLS, BLOCK 4, LOT 3 PETER BOOKMAN 7635 OLD HILLSIDE WAY ANCHORAGE. AK 99516 2 12509 SEPTIC TANK (E) yI SEPTIC AREA (E) 1 s N I � OF Al--"�\l h 2/18/2014 StevenR. Pannone pERM1T N0. �• CE 8149 .'cam// OSPt 41518 Vis' r �T�PROFES5101��'�� Sheet 2 OF 3 SPECIAL PROVISIONS TO SPECIFICATIONS 1 . ALL CONSTRUCTION WAS INSTALLED AS SPECIFIED IN THE MOST CURRENT EDITION OF THE MUNICIPALITY OF ANCHORAGE STANDARD SPECIFICATIONS (MASS) FOR COMPONENT PARTS AND MATERIALS USED IN CONSTRUCTION OF ON-SITE WASTEWATER DISPOSAL SYSTEMS AND ATTACHED PES SPECIAL .PROVISIONS. 3. SCOPE OF WORK: REMOVED EXISTING SOIL ABSORPTION SYSTEM AND ALL BIOMATTED MATERIAL, REPLACED BIOMATTED MATERIAL WITH 1'+ SAND AND INSTALLED UPGRADE SOIL ABSORPTION SYSTEM. 4. GROUNDWATER WAS NOT ENCOUNTERED TO A DEPTH OF 17.0 FEET BELOW EXISTING GRADE AS EVIDENCED BY THE SOIL TEST HOLE. AN APPARENT WATER TABLE WAS NOT OBSERVED IN ANY OF THE EXCAVATIONS LESS THAN 17.0 FEET BELOW EXISTING GRADE. TH-4 (ANDERSON 2002) -LO 0� o; ,37 .5 ML FABRIC a PERE PIPE ROCK 6' ABOVE PIPE INV TH-6 FROM TANK (E) PROFILE DESIGN PARAMETERS PRIMARY/RESERVE SEPTIC SYSTEM NO BEDROOM: 4 (600 gpd) TANK SIZE: 12509 (E) SOIL RATING: 1.2 GPD/SF AREA ROD: 500 SF SYS. TYPE: WIDE TRENCH LC'ED RF: 0.87 MIN LENGTH: 87 LF USED: (I EA) 5'W x 45LF x 1.0'ED x 8.0'TD (S) & (IEA 5'W x 45LF x 1.O'ED x 5.0'TD (N) TOTAL AREA: 517 SF 33.6 29.6 (N) 7LI0 L TAT 'w,Tl ANDERSON 2002) -28.6 (N) 29 5 (S) -7,0 1/ AND REPLACE WITH SAND AS 40 1 -1.0 Og 0 CU COPPER 1. s 30.0 1-0 - 'P7`'_28.6 -29.6 TEST HOLE Mt FC FOUNDATION CLEAN OUT SP/ T# TANK CLEAN OUT NO. 5 C# CLEAN OUT NO. M# MONITOR TUBE NC. SM RIGID INSULATION DRAIN ROCK _. DOUBLE CLEAN OUT - 4.0 DV DIVERTER VALVE FS FLOW SPLITTER SAPID AS NEEDED BELOW FINISH GRADE Sp/ ORIGINAL GRADE FG FINISH GRADE 5.0 TO REPLACE REMOVED 5-0 TOPSOIL & VEGETATE Op -14.0 BIOMATTED MATERIAL -ISO C+x -80 110 bL ML -17.0 w SECTION w -;za P Y w m F m F FROM TANK (E) PROFILE DESIGN PARAMETERS PRIMARY/RESERVE SEPTIC SYSTEM NO BEDROOM: 4 (600 gpd) TANK SIZE: 12509 (E) SOIL RATING: 1.2 GPD/SF AREA ROD: 500 SF SYS. TYPE: WIDE TRENCH LC'ED RF: 0.87 MIN LENGTH: 87 LF USED: (I EA) 5'W x 45LF x 1.0'ED x 8.0'TD (S) & (IEA 5'W x 45LF x 1.O'ED x 5.0'TD (N) TOTAL AREA: 517 SF 33.6 29.6 (N) NOTES: PANNONE ENG SVC, LLC RECORD DRAWING P.O. BOX 100217 ANCHORAGE, AK 99510 PHONE (907) 272-8218 FAX (907) 272-8211 SOUTH HILLS, BLOCK 4, LOT 3 PETER BOCKMAN 7635 OLD HILLSIDE WAY DESIGN DETAILS ANCHORAGE, AK 99516 Steven.R,.Pannone• -P- -. CE 8149 -•Po: Date 2/18/2014 Scale NTS P.I.D. NO 017-072-12 'ERMIT N0. OSP141518 Sheet 3 OF -305 (S) -28.6 (N) 29 5 (S) -REMOVE ALL BIOMATTED MATERIAL AND REPLACE WITH SAND AS NECESSARY ABBREVIATIONS CU COPPER LEGEND DIP DUCTILE IRON PIPE W WATER LINE/ TH TEST HOLE WELL RADIUS FC FOUNDATION CLEAN OUT T# TANK CLEAN OUT NO. SS NEW SEPTIC C# CLEAN OUT NO. M# MONITOR TUBE NC. R RIGID INSULATION DCO DOUBLE CLEAN OUT DV DIVERTER VALVE FS FLOW SPLITTER BFG BELOW FINISH GRADE OG ORIGINAL GRADE FG FINISH GRADE TS&V TOPSOIL & VEGETATE NOTES: PANNONE ENG SVC, LLC RECORD DRAWING P.O. BOX 100217 ANCHORAGE, AK 99510 PHONE (907) 272-8218 FAX (907) 272-8211 SOUTH HILLS, BLOCK 4, LOT 3 PETER BOCKMAN 7635 OLD HILLSIDE WAY DESIGN DETAILS ANCHORAGE, AK 99516 Steven.R,.Pannone• -P- -. CE 8149 -•Po: Date 2/18/2014 Scale NTS P.I.D. NO 017-072-12 'ERMIT N0. OSP141518 Sheet 3 OF On -Site Wastewater Disposal System Permit MUNICIPALITY OF ANCHORAGE Development Services Department On -Site Water & Wastewater Program 4700 Elmore Road, PO Box 196650 Anchorage, AK 99519-6650 Telephone: (907) 343-7904 Permit Number: OSP141518 Tax Code Number: 01707212000 Work Type: Septic Upgrade Permit Effective Dates: December 08, 2014 to December 08, 2015 Design Engineer: PANNONE ENGINEERING SERVICE Subdivision: SOUTH HILLS Site Legal Address: SOUTH HILLS BLK 4 LT 3 G:2940 Owner/Address: BOCKMAN PETER JR 7635 OLD HILLSIDE WAY ANCHORAGE AK 995160000 Site Mailing Address: 7635 OLD HILLSIDE WAY, Anchorage This permit is for the construction of: Y Disposal Field N Septic Tank N Holding Tank N Privy Lot Size in Sq Ft: 51411 Total Bedrooms: 4 N Private Well N Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80). 3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either: A. Open and Close on the same day. B. Covered, sealed, and heated to prevent freezing. Received Issued By. MUNICIPALITY OF ANCHORAGE Community Development Department Phone: 907-343-7904 Development Services Division Fax: 907-343-7997 On -Site Water & Wastewater Program ON-SITE SEWER/WELL PERMIT APPLICATION H!Parcel I.D. 017-072-12 Property owner(s) Peter Bockman Day phone Mailing address 7635 Old Hillside Way, Anchorage, AK 99516 Site address 7635 Old Hillside Way Legal description (Sub'd., Block & Lot) South Hills, Block 4, Lot 3 Legal description (Township, Range & Section) Lot Size 51,411 Sq. Ft. Number of Bedrooms 4 APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING: (® all that apply) i Absorption Field ❑X Initial ❑ Single Family (SF) ❑X (w/wo ADU) Septic Tank ElUpgrade Duplex (D) ❑ Holding Tank ❑ Renewal ❑ Multiple Dwellings ❑ Privy ❑ (SF and/or D) Private Well ❑ " Water Storage ❑ THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR: Distance: I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal Codes. property owner or Permit/Rush Fees: J%I t -NN"D :gI°'yb Waiver Fees: Date of Payment: 121311s ( Date of Payment: Receipt Number: M?) (_ (4 Receipt Number: Permit No. bS19Iq 151� Waiver No. Permit App_:; 1L..k. Pannone Engineering Services uc Steven R. Pannone, Principal Registered Professional Engineer E-mail: steveCiiloanenaak.com December 03, 2014 Municipality of Anchorage Development Services Department On -Site Water & Wastewater Program 4700 Elmore Rd. P. O. Box 196650 Anchorage, Alaska 99519 Subject: South Hills, Block 4, Lot 3 Septic System Permit Request Ladies and Gentlemen: I am writing request a permit to construct an upgrade four (4) bedroom septic system on this property. Currently the lot is developed. The existing drain field is in failure and will be removed and replaced per the original design, with sand added as needed to replace removed biomatted material. The surrounding lots are served by private wells that are over 100' from this system. Soils. Michael E. Anderson performed two test holes in the vicinity of the drain field in 2002, and groundwater was monitored for seven days. Ground water was not observed to a depth of 17.0 feet below the ground elevation in the test hole 4 monitor tube and 12.0 feet below the ground elevation in the test hole 6 monitor tube. It is my opinion, based on the results of the soils tests and overall soils appearance; an application rate of 1.2 gallons/day/square feet should be used for a conventional wastewater system. 1. Soil Absorption System Design. a. See Sheet 2 of the design package. 2. Surface Water: There is no surface water within 100 feet of the proposed septic tank and drain field. The proposed drain field upgrade will maintain at least 100 feet from all surface water and drainage ditches. 3. Topography: The existing topography slopes from south to north at approximately 35% above the field with a slope of approximately 15% across the area of the upgrade, and 25% below the drain field. There are no steep slopes within 50' of the drain field. Mailing: P.O. Box 100217, Anchorage, AK 99510-0217 Physical: 332 East Manor, Anchorage, AK 99501 Telephone: (907) 272-8218 FAX: (907) 272-8211 Page 2 of 2 4. Drawing Markings: The Drawings are marked "For MoA Review Only". When written notification that the review is complete and that there are no further comments is received from MoA On -Site Department, the note will be removed and "Issued for Construction" drawings will be issued. The proposed installation will not affect the future development of the surrounding or existing lots. There are no surrounding wells within 100 feet of the proposed septic location. If you have any questions or concerns, please contact me at 272-8218. Sincerely, Steven R. Pannone, P.E. Owner/Civil Engineer Mailing: P.O. Box 100217, Anchorage, AK 99510-0217 Physical: 332 East Manor Ave, Anchorage, AK 99501 Telephone: (907) 272-8218 FAX: (907) 272-8211 T NO WELLS/ SEPTICS \M M M\ WITHIN 200' %A, Z OLD RABBIT CREEK OAD is • I N I \ WELL (E) p� 16.4 I DRAIN FIELD (E) IN FAILURE 1 REMOVE AND REPLACE W/ (1 EA) 5'W x 45LF x 1.O'ED x 8.0'TD (S) & (1 EA 5'W x 45LF x 1.0'ED x 5.0'TD ( N ) - REPLACE REMOVED BIOMATT BELOW TD ss p \ WITH SAND AS NEEDED_...:- s13.0 1 12-7 SEPTIC AREA (E) es TH-6 5 ( ANDERSON 2002) �v 3 —M TH-4 CO AND FS. (E) \ ��— W� W/ M M \ (ANDERSON 2002) N pN �\ I I �k LOT \k PREVIOUSLY ABANDONED //� I L DRAIN FIELD (E) z Z> w y 1250g SEPTIC TANK (E) J H WELL (E) SEPTIC AREA (E) DRIVEWAY I i 4 BR Zj o HOUSE (E) I p WELL (E) I H 10' UTILITY EASEMENT \ ` Sour W� W� H qs W E WAY Z NOTES: 7�♦7�7�T 7�T�+ �+7�7 �7 T 7 �r s��� �� Date FOR CONSTRUCTION PAMONE ENG SVC, LLC of qC ill 12/5/2014 P.O. BOX 100217 ANCHORAGE, AK 99510 �� 4S �� PHONE (907) 272-8218 FAX (907) 272-8211 Scale j . ... .. ... .. ... P.I.D.NO SOUTH HILLS, BLOCK 4, LOT 3 017-072-12 •Steven •R�Pannone PETER BOCKMAN / PERMIT 10. / Pte'. CE 8149 .'4�% 7635 OLD HILLSIDE WAY j�cs•, .•�,r OSP141518 PLAN ANCHORAGE, AK 995161ll�RFDasso P: Sheet 1 OF 2 SPECIAL PROVISIONS TO SPECIFICATIONS 1. ALL CONSTRUCTION SHALL BE INSTALLED AS SPECIFIED IN THE MOST CURRENT EDITION OF THE MUNICIPALITY OF ANCHORAGE STANDARD SPECIFICATIONS (MASS) FOR COMPONENT PARTS AND MATERIALS USED IN CONSTRUCTION OF ON-SITE WASTEWATER DISPOSAL SYSTEMS AND ATTACHED PES SPECIAL PROVISIONS, 3. SCOPE OF WORK: REMOVE EXISTING SOIL ABSORPTION SYSTEM AND ALL BIOMATTED MATERIAL. REPLACE BIOMATTED MATERIAL WITH SAND AND INSTALL UPGRADE SOIL ABSORPTION SYSTEM. 4. GROUNDWATER WAS NOT ENCOUNTERED TO A DEPTH OF 17.0 FEET BELOW EXISTING GRADE AS EVIDENCED BY THE SOIL TEST HOLE. IF AN APPARENT WATER TABLE IS OBSERVED IN ANY OF THE EXCAVATIONS LESS THAN 17.0 FEET BELOW EXISTING GRADE NOTIFY THE ENGINEER IMMEDIATELY. FILTER FABRIC TH-4 (ANOL ll-DRAIN DERSON 2002) 4" P PERF PIPE -1A ROCK 6" ABOVE PIPE INV FROM PROFILE AND REPLACE WITH SAND AS NECESSARY DESIGN PARAMETERS PRIMARY/RESERVE SEPTIC SYSTEM NO. BEDROOM: 4 (600 gpd) TANK SIZE: 12509-(E) SOIL RATING: 1.2 GPD/SF AREA ROD: 500 SF SYS. TYPE: WIDE TRENCH 1.O'ED RF: 0.87 MIN LENGTH: 87 LF USE: (1 EA) 5'W x 45LF x 1.O'ED x 8.0'TD (S) & (1 EA 5'W x 45LF x 1.O'ED x 5.0'TD (N) TOTAL AREA: 517 SF - LEGEND W WATER LINE/ WELL RADIUS — SS — NEW SEPTIC NOTES: PANNONE ENG SVC, LLC FOR CONSTRUCTION P.O. BOX 100217 ANCHORAGE, AK 99510 PHONE (907) 272-8218 FAX (907) 272-8211 SOUTH HILLS, BLOCK 4, LOT 3 PETER BOCKMAN 7635 OLD HILLSIDE WAY DESIGN DETAILS ANCHORAGE, AK 99516 ABBREVIATIONS CU MLTH-6 DIP DUCTILE IRON PIPE TH TEST HOLE FC FOUNDATION CLEAN OUT T# 7.0(ANDERSON C# 7 di o -E M# MONITOR TUBE NO. R.I. 2002) DCO DOUBLE CLEAN OUT I DIVERTER VALVE FS FLOW SPLITTER BFG BELOW FINISH GRADE OG -7.0 FG FINISH GRADE TS&V 40 -1.0 00 OL 1.OJI-L 1.01 '� ML SP/ SM DRAIN ROCK -4.0 SAND AS NEEDED SPS - 5.0 TO REPLACE REMOVED 50 CP -14A SIOMATTED MATERIAL SO - 5.0 13.0 -ML -17A M( SECTION w - 20 cad m m FROM PROFILE AND REPLACE WITH SAND AS NECESSARY DESIGN PARAMETERS PRIMARY/RESERVE SEPTIC SYSTEM NO. BEDROOM: 4 (600 gpd) TANK SIZE: 12509-(E) SOIL RATING: 1.2 GPD/SF AREA ROD: 500 SF SYS. TYPE: WIDE TRENCH 1.O'ED RF: 0.87 MIN LENGTH: 87 LF USE: (1 EA) 5'W x 45LF x 1.O'ED x 8.0'TD (S) & (1 EA 5'W x 45LF x 1.O'ED x 5.0'TD (N) TOTAL AREA: 517 SF - LEGEND W WATER LINE/ WELL RADIUS — SS — NEW SEPTIC NOTES: PANNONE ENG SVC, LLC FOR CONSTRUCTION P.O. BOX 100217 ANCHORAGE, AK 99510 PHONE (907) 272-8218 FAX (907) 272-8211 SOUTH HILLS, BLOCK 4, LOT 3 PETER BOCKMAN 7635 OLD HILLSIDE WAY DESIGN DETAILS ANCHORAGE, AK 99516 ABBREVIATIONS CU COPPER DIP DUCTILE IRON PIPE TH TEST HOLE FC FOUNDATION CLEAN OUT T# TANK CLEAN OUT NO. C# CLEAN OUT NO. M# MONITOR TUBE NO. R.I. RIGID INSULATION DCO DOUBLE CLEAN OUT DV DIVERTER VALVE FS FLOW SPLITTER BFG BELOW FINISH GRADE OG ORIGINAL GRADE FG FINISH GRADE TS&V TOPSOIL & VEGETATE \\� Date OF.4 q41 , 12/5/2014 I) NTS ..... .... . .. ..... P LD. NO ............ .. / 017-072-12 Steven R. •Pannone PERMIT N0. +Pc j CE 8149 •.�=/� OSP141518 +<<lkF,PNOFESSIO Sheet \ 2 OF 2 all Municipality of Anchorage Page 1 of 3 Development Services Department • On -Site Water and wastewater Program 4700 South Bragaw Street P.O. Box 198850 Anchorage, AK 99519-6650 www.d.anchorage.ak.us (907) 343-7904 ON-SITE WASTEWATER DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT Permit Number: SW020318 PID Number. 017-072-12 Name: Wastewater System: Upgrade Sonia r' Address: 3321SpottswoodAve.ABSORPTION i N 111 FIELD Ph": Number ofBedroane S' Wide Shallow.Trench 901-327-5734 Four 4 Sol Rating: Total Depth from original grade'. LEGAL DESCRIPTION 1.2 GPDIF1s 8/5 Ft. Block: Lot: Subdivision: Depth to pipe bottom from orVW grade: Gravel depth beneath pipe: 4 3 South Hills 7/4 Ft. 1 FL Township: Range: Section: Fa added above original grade: Gravel Length 1.5 FI. 90 Ft. Well: Existing Gravel wMBt: 5 Number of linea: 2 D obetween once tines: 13 Ft. Ft. Classification (Private. A. B. C): Total Depth: Cased to: Total absorption area: Pipe Material: Private Ft. I Fl 517 FP ASTM D3034 PVC Driller, Date Drilled: Static Water Leval: Installer. Date Installed: Ft. Thomas Development, 9/13-17/02 Yield: Pump Set at cling Haight Above Grouw: TANK GPM Ft. Ft. SEPARATION DISTANCES ® Septic ❑ Holding ❑ S.T.E.P. ❑ Other. To Septic Absorption Lift Holding ubrKJPdvato �'a-r Anchorage Tank Capacity n Gallons: 11250 From Tank Field Station Tank seww Line wet >100' >100' N/A N/A >25' Steel Ste Nur woo Canpetr erNs: Two 2 Surfaee Waler >100' >100' N/A N/A LIFT STATION — NONE ON LOT Lot Lne >5' >10' N/A N/A ize: Gal. scorer: >59 >10' N/A N/A -P=P on level at *Pump on' level at: High water alarm at: Foundation In. n. In. None Noted I I zS Pwip Make 'Model Electrical Inspections performed by: Curtain Drain Remarks BENCH MARK Existing Septic Tank was Pumped, Crushedand Location and Description: 11, Site..ack-lilled On Concrete Stair Stoop. Assumed Elevation: 100.0 FL Engineers Stamp �. .......... -,q�1�♦ Inspections performed by: Alan Harala Dates: 1 a 9/14/02 ■' �`a9tn %`�+++ 2nd 9/16/02 i ........ ......_..............L!r... Department of Health and Human Services approval I+�:ti ICMAEL E. ANDERSON i� No. L °7++i� ., CE -4381 r a ••.., ••'''�: Reviewed and approved by: Date: ♦f', (Rev. I"g) �Sra�„��'•• all I ?ermi n SW020318 PID No. 017-072-12. Page 2 of 3 LOT 3,BLOCK 41 S�UTH HILLS l Lower trench' CO 9 CO 10 New ' MT1 (2) 6'W x 45 LF x'1E.D. CO 7: TH 6 absorption trenches I13 1 BEL MT2 Flow Splitter C08 TH 4 Upper trench ' —co 6 ` P 4" PVC L . f ASTM 3034 Abandoned _ Trench '� _ -t CO NEW 3 1,250 Gallon'.. V` SepticTank' f � c CO 1 & 2% v 3 o o r. LEGEND CO Cleanout SP Standpipe MT Monitor Tube intercepted : `• 49th•�i s driveway � 7'*-* c:.c:�:r .. y �0M!CHACL E. AVDERso10 N• �� A`r•;•, NO. CE-�381`' f• =i Four BR HsePROFEss / I. ���.....a - . c � existing well. PLAN VIEW AS-Blt Scale 1" _ .30' Hillside Way — L mumupaury ul Anvilulaue DEVEOPMENT SERVICES DEPARTMENT 4700 South Bragaw Street Anchorage, AK. 99519-6655 - 343-7904 On -Site Wastewater Disposal System or Well Inspection Report Permit Number: SW020318 PID No. 017-072-12 M U 77.3 N N N 1250 Gallon ieptic Tank 5.17 1 .V .- f U UPPER TRENCH U S U 7 LOWER TRENCH ___ 49th N PROFILE AS -BUILT ;MICIWEL C. ANDERSON Scale: 1" a 10' 406`f,--. . f,:,_ Nos EE -4381 MUNICIPALITY OF ANCHORAGE Development Services Department On -Site Water & Wastewater Program 4700 South Bragaw Street P.O. Box 196650, Anchorage, AK 99519-6650 (907) 343-7904 I s Y_A'5)PrC7-10A1_ ON McAlcH # Z 711410? /e:304.w. ON-SITE WASTEWATER DISPOSAL SYSTEM PERMIT Upgrade Permit Number: SW020318 Legal Description: SOUTH HILLS BLK 4 LT 3 Design Engineer: 0014 Anderson Engineering Owner Name: Sonia DiGregorio Owner Address: 3321 SPOTTSWOOD AVENUE MEMPHIS , TN 38111-4224 Date Issued: Aug 30, 2002 Expiration Date: Aug 30, 2003 Parcel ID: 017-072-12 Site Address: 007635 HILLSIDE WAY Lot Size: 51411 SO. FT. Total Bedrooms: 4 Permit Bedrooms: 4 This permit Is for the construction of: ❑✓ Disposal Field ❑✓ Septic Tank ❑ Holding Tank ❑ Privy All construction must be in accordance with: 1. The attached approved design. ❑ Private Well ❑ Water Storage 2. All requirements specified in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72 ) and Drinking Water Regulations (18AAC80 ). 3. The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 ( 24 hours ). ( Not required for a Water Supply Permit only ). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must be either: A. Open and closed on the same day. B. Covered, sealed, and heated to prevent freezing. Received By: Issued By: Date: Date: (6 OZ Municipality of Anchorage 00* Development Services Department Building Safety Division On -Site Water and Wastewater Program 4700 South Bragaw St. P.O. Box 196650 Anchorage, AK 99519-6650 www.ci.anchorage.ak.us (907) 343-7904 ON-SITE SEWER/WELL PERMIT APPLICATION FOR A SINGLE FAMILY DWELLING Parcel I.D. 017.072-12 Permit Number SWO203/1 Property owner(s) Sonia DiGregorio Day phone 901.327.5734 Mailing address (1) 3321 Spottswood Avenue Memphis, TN 38111 Mailing address (2) Zip Code Legal description (Lot, Block & Sub'd.) _ Lot 3, Block 4, South Hills Subdivision Legal description (Section, Township & Range) Lot Size 51.1411 Acres/Sq.Ft. Number of Bedrooms Four (4) THIS APPLICATION IS FOR: Sewer Only ❑ Well Only ❑ Sewer and Well ❑ Water Storage ❑ Sewer Upgrade THIS PROPERTY CONTAINS: Hot Tub ❑ Jacuzzi ❑ Swimming Pool ❑ Water Softening Unit ❑ Therapy Pool ❑ I certify that the above information is correct. I further certify that this application is being made for a Single Family Dwelling and is in accordance with applicable Municipal Codes. (Signature of property owner or authorized agent) Permit Fees: t7/po • a -'o Waiver Fees: Date of Payment: _ui 2. Receipt Number: coq (Rev. 12100) Date of Payment: Receipt Number: ANDERSON ENGINEERING P.O. BOX 240773 ANCHORAGE, AK 99524 522-7773 522-6779 (FAX) MEMORANDUM DATE: August 30, 2002 TO: Dan Roth FROM: Mike Anderson, P.E. SUBJECT: Lot 4, Block 3, South Hills Subdivision Septic System Construction Permit Attached are modified plan sheets for the construction of the septic system on the subject lot. Please substitute these sheets with those previously submitted. Please let me know if you have further questions. ANDERSON:ENGINEERING ':'ANCHORAGE; AK 99524 522-7773 522 August 20, 2002 Municipality of Anchorage Development Services Department On -Site Water and Wastewater Program 4700 South Bragaw Street Anchorage, AK 99519-6650 Subject: Lot 4, Block 3, South Hills Subdivision Septic System Design and Permit Application Impacts to Adjacent Properties Dear Onsite Services Engineer: The existing septic system on Lot 4, Block 3, South Hills Subdivision has failed and must be replaced to serve the four-bedroom home on the lot. We are therefore requesting a permit be issued for the construction of a new septic system to serve the home. The attached Site Plan and backup documentation identify the location and configuration of the new and existing septic system and the parameters used in the design. Also identified on the plans are the existing well location, test hole locations and the locations of the existing wells and systems on adjacent lots. Drainage arrows are also shown and current drainage patterns will be maintained after construction. The existing septic tank will be pumped, crushed and backfilled on site. The test holes placed near the location of the proposed absorption trenches indicated silty sand with gravel and varying amounts of silt and a percolation rate of less than 1 minute per inch in the accepting layer. We are therefore proposing to construct 2 — 5' wide by 45' long absorption trenches with 1' effective depth. The distribution piping depth will vary in the trenches to take advantage of the good soil material. Total depth of the trenches will be 5' and 8'. A Zabel Flow Splitter Valve will be placed to assure even flow to each trench. The ground surface on the lot slopes as shown on the attached Site Plan with fairly steep slopes from south to north. The new septic tank and absorption trenches will be constructed on slopes with grades approximating 20%, but in conformance with Municipal requirements and parallel to ground contours. All components of the new trench will be constructed a minimum of 100' from the well on the lot. The system will also be constructed a minimum of 100' from any surface water in the area and 10' from the water service line. If the system is constructed in accordance with our design the following statements apply: Loi 4, Block 3, South Hills August 20, 2002 Page Two 1. The system, if constructed as designed, will have no adverse impact on the wells in the area or those to be constructed in the future. 2. The system, if constructed as designed, will have no adverse impact on existing septic systems in the area or those to be constructed in the future. 3. The system, if constructed as designed, will have no adverse impact on reserve space, either surface or subsurface, on any lots located in the area. 4. The system, if constructed as designed, will have no adverse impact on drainage patterns in the area. The current drainage pattern will be maintained. Sincerely, Michael E. Anderson, P.E. Attachments WLI r 49th VCHAEL E. ANCERSCN . Nn Cf -4391 e Old Rabbi tCreek _ !sz 96 I s2.9 Road THIS 152.96 P40JECT well 4t o septic C? area N •. m R \ / 4 well f 1 �\wellI� Septic f area ' 8illsi Way 153.50 153.30 153.50 4 9 2 1; -75777�:' a9:n ''� �• ' �•�..,.e ........ ........ ... snt ..».� 101 uta EY 1... .». .. ... ....... •1 i^ V'CrAEE E. ANDERSON i cu i S Warranty C Bk 60 •I��sr:, No. CE -4381 d Now .�0 1� F,p' E a ti 1 S ��44 PFES50CA ;:•. e o N 13 ti AREA SYSTEM PLAN SCALE 1" = 100' t Existing Line S1TE PLAN SCALL �" = 40' LOT 3, BLOCK 4, SOUTH HILLS SUBDIVISION DESIGN FACTORS: 4 Bedroom House Perc. Rate: LT 1 MinJlnch Application Rate: 1.2 GPD/SF SYSTEM REQUIREMENTS: 5' Wide Trench System 1,250 Galion Septic Tank V Drainfield Rock 4 Bedrooms X 150 GPD/1.2 GPDISF (Application Rate) = 500 SF of Absorption Area 500 SF/5 LF (Width)* .87(Red. Factor) = 87 LF Trench Length Therefore: Construct Two 5' Wide Absorption Trenches Each 45' in Length For a Total Length of 90'. Flow Line Elevation in Trenches to be 7' and 4' Below Original Ground Surface. Total Depth to be 7.5' and 4.5' Below Existing Ground. A Zabel Flow Splitter Valve Must Be Placed to Assure Even Effluent Flow to Each Trench. Maintain 10' of Separation Between Each Trench. Provide 3' of Cover or Place 2" Insulation and 2" of Cover Over Trenches. 4' of Cover Required Over Septic Tank. Natural 3.5' Backfill or 6.5' 6" Geotextile Fabric 4" Perforated PVC (ASTM 3034) _Drainfield TYPICAL WIDE TRENCH SECTION (NO SCALE) NOTE: Grade Area Over Trench to Drain Away. Minimum 6' Separation From Bedrock. Minimum 4' Separation From Groundwater. Minimum 100' From Wells in the Area. Minimum 10' Separation From Water Service Line. 49th n M;CHAEL E. ANDERSON No. CE -4381 i ON ESS Municipality of Anchorage Developmental Services Department - On -Site Water and Wastewater Program 4700 South Bragaw, Anchorage, AK 99507 SOILS LOG - PERCOLATION TEST Performed For. Sonia DiGregorio Date Performed: 8/14/02 Legal Description: Lot 3. Block 4. South Hills Subdivision SLOPE SITE PLAN 1 1 1 1 1 1 1 1 1 2 OG/OL Was Groundwater Encountered? No If Yes, What Depth? SP Depth to Water After Monitoring None SM Date: 8/20102 Lenses GM ML Bottom of Hole See Site Plan a■ r .V_ A-- E. AIJERS0% L4, �Ic� : No. tE-A}9t i # V . d � 1� PF ' •.. E �• Reading Date Gross Time Net Time Depth To beater Net Drop 1 14 -Aug 2:25 2.25" 2 2:35 10 Dry 12.75" 3 2:36 2.5" 4 2:46 10 Dry 12.5" 5 1 2:47 1 2.5' 6 1 2:57 1 10 Dry 12.5" Perc. Rate: < 1 Min./Inch Perc. Hole Diameter. 6" Test Run Between 8 Ft. and 9 Ft. Comments: Percolation Cavity Presoaked Prior to Testing. Performed By: A. Harala. 1, Michael E. Anderson Certify That This Test Was Performed In Accordance With All State and Municipal Guidelines In Effect On This Date: 8120102 M. -M14 Municipality of Anchorage Developmental Services Department - On -Site Water and Wastewater Program • ... •••-••......•AEL_^•••••• ......•• 4700 South Bragaw, Anchorage, AK 99507 �� % +% y+No. cEA 438'0% SOILS LOG - PERCOLATION TEST # r/F1%. #1� Fp'"•....... .....• a". Performed For. Sonia DiGreciorio Date Performed: 8/14/02 441�i ;;5;.� � �� Legal Description: Lot 3. Block 4. South Hills Subdivision SLOPE SITE PLAN OG/OL ML TESTHOLE NO, 6 SP1GP ML Bedrock Was Groundwater Encountered? No If Yes, What Depth? Depth to Water After Monitoring None Date: 8/20/02 LI See Site Plan Reading Date Gross Time Net Time Depth To ."later Net Drop 1 14 -Aug 3:08 1.5" 2 3:18 10 Dry 11' 3 3:19 1.5" 4 3:29 10 Dry 11" 5 3:30 1 1.5" 6 3:40 10 Dry 11' Perc. Rate: < 1 MinJlnch Perc. Hole Diameter. 6" Test Run Between 4 Ft. and 5 Ft. Comments: Percolation Cavity Presoaked Prior to Testing. Performed By: A. Harala. 1, Michael E. Anderson Certify That This Test Was Performed In Accordance With All State and Municipal Guidelines In Effect On This Date: 8/20102 ONSITE WASTEWATER DISPOSAL SYSTEM CONSTRUCTION AND MATERIAL SPECIFICATIONS SUBJECT: LOT 3, BLOCK 4, SOUTH HILLS SUBDIVISION GENERAL: The scope of this project includes the pumping, crushing and backfilling the existing septic tank and the procurement and placement of a new 1,250 gallon septic tank at the location shown on the site plan and the construction of 2 - 45' long by 5' wide by 1' effective depth absorption trench also shown on the Site Plan. The total depth of the trenches will be 8' and 8' below existing ground and the distribution pipe will be placed at 4' and 7' below the surface. A Zabel Flow Distribution Valve must be placed to insure even effluent flow to each trench. All components of the septic tank and absorption trench must be constructed a minimum of 100' from the well on this and the adjacent lots. A minimum of 4' of fill must be placed atop the septic tank. In lieu of fill 2" of direct bury insulation may be placed with 2' of fill atop the insulation. 2. Construction shall be in accordance with the approved site plan, design drawings, Municipal Permit with any special provisions or conditions, and all applicable State and Municipal Wastewater Disposal Regulations. 3. The Contractor shall be responsible for obtaining all underground utility locates and for the layout of the septic system and verification of the location of all lot lines. 4. Unless specifically agreed otherwise, the contractor shall be responsible for final grading areas subsequently depressed from soil settling. Property owner shall be responsible for revegetation of affected areas unless specifically agreed otherwise. 5. Contractors installing wastewater disposal systems must be certified by the Municipal Department of Health and Human Services for system installations. Owners installing their own systems must receive prior approval from D.H.H.S. before beginning system installation. SEPTIC TANK INSTALLATION 1. The 1,250 -gallon septic tank must be procured from an approved septic tank manufacturer and installed at the location shown. 2. A septic tank is to be constructed by a certified septic tank manufacturer. Construction shall include two 4" cleanouts for pumping access. 3. The septic tank shall be sufficiently bedded to prevent settling or shifting of the tank. 4. All standpipes on the septic tank shall extend a minimum of 12 inches above final grade. Lot 3, Block 4, South Hills August 20, 2002 Page 2 of 2 5. Tanks installed without 4' of cover shall have a minimum of 2" of direct burial insulation. 6. A foundation cleanout shall be installed one to four feet from the building foundation. Two cleanouts are required between the tank and the drainfield. 7. Final grading over the tank shall be such that a positive slope exists away from the septic tank. DRAINFIELD CONSTRUCTION: 1. The drainfield shall be constructed to the dimensions shown on the design. The bottom of the trench shall be within 2" of level. 2. Distribution piping must be placed level with perforations' down atop a level bed of drainfield rock. Rock should then be placed over the pipe to provide a minimum of 2" of cover. 3. A silt barrier or,geotextile fabric must be placed between the drainfield rock and the natural soil backfill. 4. Monitor tubes must be 4" in diameter and installed at the locations shown on the design. The portion below ground must be perforated. 5. Contractor shall verify the septic tank and drainfield are a minimum 100' away from any private water wells in the area, 150' from a Class "C" Well or 200' from any community well. 6. Direct bury insulation must be placed over the distribution system if less than 3' of backfill depth is available. Finish grade over the trench must be mounded to prevent settlement or depressions. 7. Grade area surrounding the absorption trench to drain away. 8. A minimum 2' of accepting soil is required below the drainfield rock for a 5' wide trench. Contractor shall verify this condition prior to placement of the rock. All pockets of unacceptable materials must be removed and replaced. MATERIAL SPECIFICATIONS: 1. Septic tanks must be constructed by a municipally approved septic tank manufacturer. 2. The following pipe materials are approved for use in septic system installations in the Municipality of Anchorage: Cast Iron (perforated and solid), ASTM D3034 or P.V.C. (perforated and solid), ASTM F810 or H.D.P.E. (perforated, but not solid) and ASTM D2662 or A.B.S. (perforated and solid). 3. Insulation shall be at least 2" thick extruded direct burial polystyrene (Dow Chemical Co. Styrofoam HI or equal). Lot 3, Block 4, South Hills August 20, 2002 Page 3 of 3 4. Septic tank inlets and outlets shall be fitted with watertight couplings (Caulder, Fernco, or equal). 5. A permeable geotextile fabric (Typar, Mirafi or equal) must be installed between the final drain rock layer and the native soil layer. 6. All drain rock shall be .5" to 2.5" in diameter with less than 3% passing the #200 sieve. INSPECTIONS: Municipal Ordinance requires a minimum of two inspections. These inspections must be conducted under the supervision of a professional engineer registered in the State of Alaska. The first inspection must be conducted after the excavation of trenches, beds or pits and before the installation of any gravel. A septic tank may be set in place, but may not be backfilled. The second inspection must be conducted after the placement of the geotextile fabric, gravel, distribution piping, standpipes, cleanouts and insulation. No backfill should be in place at the time of inspection. Contractor shall provide a copy of all field survey layout and construction notes for use in preparing the certified as -built of the completed system. MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTECTION ENVIRONMENTAL ENGINEERING DIVISION 825 L Street - Anchorage, Alaska 99501 Telephone 264-4720 ON-SITE SEWAGE DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT NAME / . �-r�C Oji 4 �� C.'Lre-/ PHONE ,9.c. "'ASCO( NEW ED UPGRADE MAI LING ADDRESS / LEGAL DESCRIPTION LOCATION a NO. OF BEDROOMS V DISTANCE TO: Well 5 Absorption area _ �-- Dwelling PERMIT NO_Q. �!Y [7 ��� C7 F ZZ W� ManufacturerMaterialg (3 neer { ,,,, / I I No. of compar;menis L ti Lie. capacity in gallons �,) � IF HOMEMADE: Inside length — Width -- Liquid depth JaZ DISTANCE TO: Well Dwelling PERMIT NO. _ .. oz H Manufactur �------''— /"�--�'�_..Materia - Liquidcapacityingallons O LU Z DISTANCE TO: Well Foundation Nearest lot line PERMIT NO. J LL z 2 ¢ No. of lines '( Length of each line � Total length of lines `.. J L[ Trench width 7j� inches Distance betwee Danes H p Top of the to finish grade 3 • Material beneath the �T S', S }nUr Total effective absoyp�igfy r a w Length Width Depth PERMIT NO. Q F Type of crib ib diameter _ Crib d Total effective -ab! .,parea-_ - w w DISTANCE TO: Building foundation Nearest Iot line _j Clas , ) yt Depth Driller Distance to lot linejAt RMIT NO. W 3:DISTANCE TO:I Building foundation Sewer line Septic tank sorption areas) () OTHER .016 PIPE MATERIALS _T� C a (r b n d� SOI LTEST RATING INSTALLER REMARKS n 4, / F 3 APPROVED DATE LEGAL 72� Z� U�C Li A S 72-013 (Rev. 3'/78) _Al DEPARTMENT OF HEALT'll AND ENVIRUNMENT'Al.. PROTECTION 325 `L'' STREET, WICFIORAGE: A[.-,, 99501 ti 264--4,"20 0 P-4 T. 1- F"", EE R.4 E`-- F"_" F,_C Irl I IF F'ERNIT NO. 79("W..10 APPI-TCANT DEGRF,,:(30RIO '-SALVATORE 8960 BLACKBERR'ill LOCATION HILI SIDE DRIVE 1_0301_ L]" B4 SOUTH HILLS Sey..., t., o, r '5 1 .7 E :15'.02 FEF.r TYPE OF' SOIL ABscjF',.f.-,,,rION SYSTEM TREr4CH 111FIXIMUM NUMBER. OF BEDROOMS =. 37" =3OIL RATING t: SQ FT,-F.*.'R)=- 1.40 JHERE(..!UIRED SIZE OF THE SOIL ABSORPTION SYSTEM IS: F'-­F�'-F t -A THE LENGTH DIMENSION IS THE LENGTH (IN FEET) OF THE TRENCH OR DRAIr-*:'IE'l D. THE DEPTH OF A TRENCH OR PIT' IS THE DISTANCE BETWEEt-.1 THE OF THE .GF'.'OUN[') AND THE BOTTOM OF THE EXCAVATION r'IN FF`ET.). I'l IERE IS P-40 SET WIDTH FOR TRENCHES. THE GRAVEL DEPTH IS THE MINIMUM DEPTH OF GRAVEL BETWEEN THE OUTFALl... F -'I F E AN[.') T*HE BOTTOM OF THE EXCAVATION (IN FEET). F: -,Ml F -H 0 U I U.-.- ` F_'' F" -T* I ('--I- _r 1"I " IK' "=-. 127: F_ -:L IE:'z IL"I CA- F -H PA Pf; , :'RMIT APPI C IAt4T HAS THE RESPONSIBILITY TO INFORM THIS DEPARTMENT DURIM7.1' THF, Ihi'STALLATION INSPECTIONS OF ANY WELLS ADJACENT TO THIS- PROPERTY Atlr.? THE NUMBER OF' RESIDENCES THAT THE 14ELL 1,111.L. SERVE. 1W c 1.2'" > I I 1--sWE. @ M F'-' C-- FR E C.-FL.0 I D'ACKFILLING OF ANY SYSTEM WITHOUT FINAL INSPECTION AND APPROVAL BY THIS DE'.`F*ARTMf]--_.NT WILI BE SUBJECT TO PROSECUTION. MINIMUM BET14EEN A WELL AND ANY ON- :;ITE: SE1.4AGE DISM...'FIL SYSTEM I�` 100 FEET FOR A PRIVATE WELL.; OR .. ­­ ' 0 FROt .1-:5C-1 R" 2,00 FEET -1 A PUBLIC WELL DEPENDING UPON 'THE TYPE OF" F -IC WE i I 1__ OTHER REQUIF,.EMENTS MAY APPI Y. SPEC I FICATI ONS AND CONSTRUCI'lor-4 F0,1FULF"IBLE TO INSURE PROPER IN.','..-",'TALLATION. I _T...FEE- 1>U-- I _,7,::::1L, :f C'ERTIFY THAT' .1 1 AM FAMILIAR WITH THE REQUIREMEtcm FOR OWSITE SEWERS AND WELLS AS FORTH BY THE MUNICIPALITY OF ANCHORAGE' 2: 1 WILL Ira TALL THE SYSTEM IN ACCORDANCE WITH THE 1."ODE_:. I UNr:,ERSTFlND THAT THE ON--SIT'E SEWER SYSTEM MAY REQUIRE ENl...AR('. iEMEt4T IF' HIE RESIDENCE-- REMODELE1.1 'TO INCLUDE NOFZE THAN 3 BEDROOMS. I G N E D ALVATORE ISSUED E -.M -A / .. / . . .... 1_Z_Z --- V *'..".. 2 Russell Oyster 694-2774 O & E ENGINEERING & DEVELOPMENT CO. Box 90, Davis St., Eagle River, Alaska 99577 694-2774 or 688-2280 SOIL LOG Earl Ellis 688-2280 Performed for: Name: / • re -3 u S,;-AA U !` °`` Tel. No. 9 72- °rW � Mailing Address: gzle9' A • VDoe ,�/ 1' &C#6'��� Legal Description: Z.-07- -3, 4, d50 rJ'T/f e -s Depth (feet) 0 1 2 3 4 mw 5 6 7 8 9 12 Soil Characteristics 441 54/40`r) AA/ CUs b s,q mile r IlL., �fc r, IDEAI5.c 54AIeaY �GAI/EL® T2s E 4e'�% F6Lr- PLOT PLAN A16 SeAlt-x PERC. TEST 14 /L ale, e, 15 Sol- ," 16 Ground Water Encountered: Yes No K� If yes, what depth Proposed Installation: Seepage Pit Drain Field Comments: Performed by:Date: iso WATER WELLS 665 W. 87th Avenue Anchorage, Alaska 99502 WELL CONSTRUCTION LOG HOWARD TEAL 344-0498 MUNICIPALITY OF ANCHORAGE DEPT. 07 HALTH & ENvIRONwcvTAL P.�,rQCTION DEC 7 1978 RECEIVED Drilling Co. tZ `Z USGS no. L r^ Driller��7'_7 t'� �,�gk Type of rig �/r "''- ✓°�` Date well completed Well owner ��,rjNr��x.�rr�ij �r{ 1t9r�t�rE�. Nearest community Well location: (address & legal description) V`/ :67 Location sketch or remarks / Depth of well it. Casing: depth it. diam..—i n. i Static water aver Z— ft. (above, below) land surface. Date Finish of well: (open-end, screen, perforated, open -hole, other) Describe intervals and size: Well yield tested by (pumping, bailing, air) at l gal/min. Iorj_hours with—./ e ft. of drawdown from static level. DRILLER'S MATERIAL LOG Depth below land surface in feet Give description of (size of material, color, hardness strata penetrated of drilling, and water content) cl to Ot o 11 o VV ��,' ,�( A. f l Q t�> C7 o c to 7 40 iR. �l _� c- - yE_ x e- r _.� - to L� r 6 to to to to to to —to— to to to to to to 1: _T ��� ������ �0 �PHRTMEN,.JF HEALTH HND PROflasTION 825 'L' S T R EFET, FNCHORHGE, HK. 99501' 264--472(�*) PE�MIT �O( 78104� ) RPPLICANT SHLYHTORE D. QREGORICj o/o it TEFFIL (T - 'r LING) �44 04�8 LOCHTION HILLSIDEE DR LEGAL L] B4 SQUTH HILLS 'S/C) LQT SIZE �45]� SQUHRE FEET MINIMUM BETWEUN A WELL HND ANY ONSITE SEWHGE DISPOSAL SYSTEM IS 100 FWET FOR H PRIVATE WELL/ OR 150 TO 200 FlEET FROM F) PUFAIC WELL DEPENI)INQ UPON THE TYPE OF PUGLIC WELL LOGS ARE REQUIRED HND MUST BE RETURNED TO THE DEPHRTMENT WITHIN ]0 DHYS DF THE WEL� COMPLETION. OTHER REQUIREMENTS MAY APPLY. FiND C010TRUCTION DIHGR8MS ARE HVHIL8BLE TO INSURE.* PROPER INSTHLLHTION ��_y_ 1.: FRUMV EDO Q W K M EEO Q oFT �"a ::* IE," I CIRTIFY THHT 1: I HM FHMIL�R� WITH THE �EQUI��MENT� FO� ON�SITE S�WER� HND WELLS AS SET FORTH BY THE MUNICIPHLITY OF HNCH8R8GE. 2: f WILL INSTALL THE IN HCXOMHNCE� WITH THE,.' CODf.,i]:S. SIGNED� ~~~_~_­~~~~.~ MUNICIPALITY OF ANCHORAGE Development Services Department Phone: 907-343-7904 On -Site Water & Wastewater Section Fax: 907-343-7997 Certificate of On -Site Systems Approval Parcel I.D. 617-672-12 1. GENERAL INFORMATION Expiration Date Complete legal description SOUTH HILLS BLK 4 LT 3 Location (site address) 7635 OLD HILLSIDE WAY, ANCH AK Current property owner(s) STANCEL Mailing address Real estate agent SAME 2. TYPE OF DWELLING: El Single Family (w/wo ADU) ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF BEDROOMS: 4 Day phone Day phone Z3 -ZZ 4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Private Well El Private Septic ' Fx� Water Storage ❑ Holding Tank ❑ Community Well ❑ Community ❑ Public Water System ❑ Public Sewer ❑ Waiver request for: Distance: Received by: Date: COSA to be released to the engineer, unless otherwise requested by the engineer. COSA Fee $ 550 Date of Payment 3 ? 3 ' 2 2 Receipt Number az3 71q COSA#_'�JG2211 �3 Waiver Fee $ Date of Payment Receipt Number Waiver # 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is (are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. I acknowledge that On -Site staff may visit the site to verify the information submitted. Name of Firm MIKE N ANDERSON, P.E. Phone 727-$$64 Address 4661 NATRONA AVE ANCH AK Engineer's Printed Name MIKE N ANDERSON, P.E. Date 3/14/22 ,- �. - .. F 51 6. DSD SIGNATURE r 49TH System #1 Approved for 4 ,� ...... bedrooms • .... , System #2 Approved for ..... �. . N. bedrooms P ti�J,°,.• c� 94 9 Disapproved Conditional approval for bedrooms, with the following stipulatii4�t"- n� Original Certificate Date:_ 3 _Z 3 - Z Z The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 7. ATTACHMENTS: COSA Checklist X Nitrate Advisory Septic System Advisory Arsenic Advisory Well Flow Advisory Other COSA Cheddist blue sheet Legal Description: SOUTH HILLS BLK 4, LOT 3 If more than 1 septic system on lot: COSA Checklist # A. WELL DATA OR Well log is filed with Onsite (or attached) Date drilled 117114 Total depth 92 ft Cased to 92 ft ❑ Sanitary seal is functioning correctly ❑ Wires are properly protected Casing height (above ground) 24 in. Date of flow test for COSA 211522 Static water level at beginning of test 41 ft. Comments B. TANK DATA Age of tank(s) 18 years Tank type/material "P"C'S r Measured operating fluid level In septic tank 48 ❑ Standpipes/foundation cleanout per record drawing Date of pumping 3/12/22 Parcel ID: 017-072-12 of Structure served by this system D. ABSORPTION FIELD DATA TESTED NORTH TRENCH Which system tested (date installed) 121 15V14 ❑ ALL standpipes present per record drawing Total measured depth from grade 8/5 ft (max) Measured depth to pipe invert from grade 7/4 ft (min) ❑ N/A — pressurized field AN Monitor tubes go to bottom of effective. If not, state depth into effective ❑ Code -required soil cover over field ❑ System presoaked (Required if vacant for greater than 30 days prior to date of test) Gallons introduced 0 gallons Comments/Deficiencies: COSA Checklist yellow sheet Well production at time of test 3+ gpm Water storage tank volume 0 gallons Well disinfected for coliform test? ❑ Yes ❑ Nc ❑ Coliform bacteria is Negative Nitrate 0.718 mg/L ❑ Nitrate less than MRL (ND) Arsenic ug/L ❑ Arsenic less than MRL (ND) Collected by MNA Date of Sample 2/15/22 C. LIFT STATION ❑ Required maintenance completed Age of lift station years Lift station material Comments: Adequacy test date 2/15/22 Results Q Pass For 4 bedrooms Fluid depth prior to test 0 in Water added 600 gal New depth 3 in Elapsed time 1440 min Final fluid depth 0 in Absorption rate 800 gpd Any rejuvenation treatment (past 12 months) If yes, enter date E. SEPARATION DISTANCES From Private Well on Lot to: (Please enter distances if less than required or if community well) Septic Tank/Lift Station on Lot > 100' Yes Community Sewer Manhole/Cleanout > 100' r,7( Yes if No ft M Yes if No ft Neighboring Tank > 100'�j✓' Yes if No ft Private Sewer/Septic Line > 25' [Z] Yes if No ft Absorption Field on Lot > 100'✓Q Yes if No ft Holding Tank > 100' F✓ Yes if No ft Neighboring Absorption Fields > 100' r✓❑ Yes if No Animal Containment > 50' Q✓ Yes if No ft Yes if No ft if less than required) Building. Foundation > 10' 0 Yes Manure/Animal Excreta Storage > 100' ft Community Sewer Main > 75' ZYes if No ft M Yes if No ft From Septic/Holding Tank on Lot to: (Please enter distances if less than required) Building Foundations > 10' Q Yes if No ft Surface Water > 100' Q Yes if No ft Property Line > 5'✓Q Yes if No ft Wells on Adjacent Lots: Absorption Field > 5' Q✓ Yes if No ft Private Wells > 100' ✓V Yes if No VNiater Main > 10' Rtl Yes if No ft Community Wells > 200' M Yes if No Water Service Line > 10' El Yes if No ft If septic tank is under driveway comment below From Absorption Field on Lot to: (Please enter distances if less than required) Building. Foundation > 10' 0 Yes if No ft If absorption field is under driveway comment below Property. Line > 10' ✓M Yes if No ft Wells on Adjacent Lots: Water. Main >'10'✓(_j Yes if No ft Private Wells > 100' ® Yes if No Water Service Line > 10' Yes if No ft Community Wells > 200' F✓ Yes if No Surface Water > 100' Q Yes if No ft F. ENGINEER'S COMMENTS G. ENGINEER'S CERTIFICATION I certify that 1 have determined through held inspections and review of Municipal records that the above systems are in conformance with MOA COSA guidelines in effect on this date. COSA Checklist yellow sheet -Ry fir. '!t'•sp.a °a'. �' � .• A a, ° �J% MICHAEL N. Af;aLii 9 C s , � c - •,_ lit ' � ,� :;� =', •. lA � ft ft 10 ft FAGS $G • Municipality of Anchorage On -Site Water and Wastewater Program z (907) 343-7904 *0 S A E r Y � Je 7 Certificate of On -Site Systems Approval' 41 Parcel I.D. 017-072-12 Expiration Date: ' -2- 1. GENERAL INFORMATION Complete legal description South Hills, Block 4, Lot 3 Location (site address) 7635 Old Hillside Way Current Property owner(s) Peter Bockman Day phone Mailing address 7635 Old Hillside Way, Anchorage, AK 99516 Real Estate Agent Day phone 2. TYPE OF DWELLING: Fx1 Single Family (w/wo ADU) ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF BEDROOMS: 4. TYPE OF WATER SUPPLY: Individual Well Individual Water Storage Community Class Well Public Water System WaiverNadance request for., Received by: El UA TYPE OF WASTEWATER DISPOSAL: 0 Individual Fx I ❑ Holding Tank ❑ ❑ Community ❑ ❑ Public Sewer ❑ COSA to be released to the engineer, unless otherwise requested by the engineer. Date: COSA Fee $ G 2%5b i' I(ol,l0 = �iZ1,Lo Waiver Fee $ Date of Payment (22) VL -IN C&, Date of Payment Receipt Number t7 l b Receipt Number COSA# �C (y I��{'1 Waiver# 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. In conducting an adequacy test, I attempt to provide a thorough, conscientious engineering analysis of the system in accordance with MoA COSA guidelines and regulations. The reported results describe the performance of the system under the conditions encountered at the time of the test, and separation distances measured to readily identifiable features. The operational life of all wells and septic systems depend on the local soil condition, ground water levels that may fluctuate during the year, and the water usage of the family being served by the system. These conditions are outside the control of the evaluator of this system. All systems eventually fail and satisfactory test results do not guarantee future performance of the system, nor do they guarantee that there are no hidden defects or encroachments. Therefore we cannot provide any warranty for future performance, nor can we estimate remaining life of the system. The content of this report is for the sole benefit of the owner listed above. Name of Firm Pannone Engineering Services LLC Phone (907) 272-8218 Address P.O. Box 100217, Anchorage Ak. 99510 Engineer's Printed Name Steven R Pannone Date 12/19/2014 f *,• Tri 1 6. DSD SIGNATURE ' V System #1 Approved for bedrooms Steven W oris g CE -8149 System #2 Approved for bedrooms s •• Disapproved Conditional approval for bedrooms, with the following stipulations: By: G��eP Original Certificate Date: 1:� The i uni alt chorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 7. ATTACHMENTS: COSA Checklist X Nitrate Advisory Septic System Advisory Arsenic Advisory Well Flow Advisory Other COSA blue sheet ° c If more than 1 septic system is on the lot: COSA Checklist # I of Structure served by this system 1 Certificate of On -Site Systems Approval Checklist Legal Description: South Hills, Block 4, Lot 3 Parcel ID: 017-072-12 A. WELL DATA Well type Private If A, B, or C provide PWSID # Date completed 11/17/14 Sanitary seal (Y/N) Y Total depth 92 ft. Cased to 92 ft. FROM WELL LOG Date of test 11/4/78 Static water level 35 Well production 15 WATER SAMPLE RESULTS ft. Well Log (Y/N) Y Wires properly protected (Y/N) Y Casing height (above ground) 24 in. AT INSPECTION 11/17/14 34 3+ Coliform Neg colonies/100 mL Nitrate 1.23 mg/L Arsenic ND ug/L Date of sample: 11/17/2014 Collected by: PES B. SEPTIC/HOLDING TANK DATA ft. 9 - p.m - Tank Type/Material Septic/Steel Date installed 9116/02 Tank size 1,250 gal. Number of Compartments 2 Cleanouts (Y/N) Y Foundation cleanout (Y/N) Y Depression over tank (Y/N) N High water alarm (Y/N) N Date of pumping s =ue tZ t�"q Pumper Ar-�>l u = -Or" "o L ' uc- C. ABSORPTION FIELD DATA Date installed 12/15/14 Soil rating (g.p.d./ft2 or 112lbdrm) 1.2 GPD/SF System type Wide Trench Length 90.0 ft. Width 5.0 ft. Gravel below pipe 1.0 ft. Total depth 7/4 ft. Eff. absorption area 517 ft2 Monitoring tube Y Depression over field N Date of adequacy test New Results (Pass/Fail) Pass For 4 bedrooms Fluid depth in absorption field before test New in. Water added New gal. New depth New in. Elapsed Time: New min. Final fluid depth New in. Absorption rate >= 600+ g.p.d. Any rejuvenation treatment (past 12 mo.) (Y/N & type) No If yes, give date D. LIFT STATION Date installed "Pump on" level at Datum Size in gallons _ in. "Pump off' level at E. SEPARATION DISTANCES WELL ON LOT TO: Cycles tested Septic tank/lift station on lot 100+ Absorption field on lot 100+ Public sewer main 75+ Sewer /septic service line 25+ Animal containment areas 50+ Manhole/Access (Y/N) _ in. High water alarm level at Meets alarm & circuit requirements? On adjacent lots 100+ On adjacent lots 100+ Public sewer manhole/cleanout 100+ Holding tank 100+ Manure/animal excrete storage areas 100+ SEPTIC/HOLDING TANK ON LOT TO: Building foundation 5+ Property line 5+ Water main 10+ Water service line 10+ Wells on adjacent lots 100+ ABSORPTION FIELD ON LOT TO: Property line 10+ Building foundation 10+ Water Service line 10+ Surface water 100+ Curtain drain 50+ Wells on adjacent lots 100+ F. COMMENTS G. ENGINEER'S CERTIFICATION i certify that i have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA COSA guidelines in effect on this date. Engineer's Printed Name Steven R. Pannone Date 12/19/2014 COSA brown sheet 10-10-12.doc Absorption field 5+ Surface water 100+ Water main 10+ Driveway, parking/vehicle storage11 0+ rip ---- - _ OL_ASBIT CREEK ROAD 8408A 0 LO 0 — — S85052'1011E 152.95 LO I I — — I I I I I I I I I I I I I Septic vents I s CY) LOI rn ceie Co +- Septic vents M M �I e M M E ° mSeptic vents Lot 2 l o WI o MI M 2 _ 0 �I J 0 0 of z z i Lot 4 Septic vent ° I I I I I s SCALE: V= 30' I C° I ` 3 I N I e OF & hed '•49th •'9 �j PlT �/ ktr17.8 � ••,• � .Fred Walatka. i �� saF • 3255 - SGravel driveway O Well o9. ' FEsslosm-de\L jhed iZ-Z4-14 0'UtilityfEasement I -- — (� _ N r; _ _ _ N AS -BUILT NO CORNERS SET THIS DATE Cn S83 042 I hereby certify that I have performed a Mortgagee's inspection '00"" _ 153.50 of the following described property: LOT 3. BLOCK 4 SOUTH HILLS SUBDIVISION -- OLD _HILLSIDE WAY o Anchorage Recording District, Alaska, and that the M improvements situated thereon are within the property lines and do not overlap or encroach on the property lying adjacent thereto, that no improvements on the property lying ------ adjacent thereto encroach on the premises in question and that there are no roadways, transmission lines or other visible easements on said property except as indicated hereon. Dated at Anchorage, Alaska EASEMENTS OF RECORD, OTHER THAN this 24th day of December ,2014. THOSE SHOWN ON THE RECORDED FRED WALATKA & ASSOCIATES PLAT ARE NOT SHOWN HEREON. FB 14-11, pg 49 BE (907-248-1666) Engineers and Surveyors Municipality of Anchorage k Development Services Department °` Building Safety Division ' On -Site Water and Wastewater Program E ' ° 4700 South Bragaw St. P.O. Box 196650 Anchorage, AK 99519-6650 www.ci.anchorage.ak.us (907)343-7904 CERTIFICATE OF HEALTH AUTHORITY APPROVAL FOR A SINGLE FAMILY DWELLING47-) Parcel I.D. 017.072-12 HAA # d K? Expiration Date: 1. GENERAL INFORMATION Complete legal description Lot 3, Block 4, South Hills Subdivision Location (site address or directions) 7635 Hillside Way Current Property owner(s) Sonia DiGreporio Day phone 901327.5766 Mailing address Lending agency Mailing address Real Estate Agent Mailing Address 3321 Spottswood Avenue Memphis, TN 36111 Unless otherwise requested, HAA will be held by DSD for pickup. 2. NUMBER OF BEDROOMS: 3. TYPE OF WATER SUPPLY: Individual Well Individual Water Storage Community Class - Well Public Water System Four 4 Day phone Day phone TYPE OF WASTEWATER DISPOSAL: ® Individual On-site ❑ Individual Holding tank ❑ ❑ Community On-site ❑ ❑ Public Sewer ❑ The Municipality of Anchorage Development Services Department (DSD) Issues Certificates of Health Authority Approval (HAA) based only upon the representations given In paragraph 5 by an independent professional civil engineer registered in the State of Alaska. Certificates of Health Authority Approval are required for the transfer of title (except between spouses) for properties served by a single family on-site wastewater, disposal and/or water supply system. DSD also issues HAAs upon request to homeowners. Certificates of Health Authority Approval are valid for 90 days from the date of Issue for properties served by a private or Class C well and may be reissued with new water sample results less than 30 days old. (Certificates may be reissued for a period of up to one year with valid water samples.) Certificates are valid for one year for properties served by Class A or B wells or a public water system. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 4. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Health Authority Approval Guidelines for this application, shows that the on- site water supply and/or wastewater disposal. system is(are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm Anderson Engineering Phone 522.7773 Address P.O. Box 240773 Anchoraoe. AK 99524 Engineer's Printed Name Michael E. Anderson. P.E. Date 2/3/2003 ' 49th1 �....i........... r.......... • IiY"k!..1.� ... ......... f �n WCMAEL E. ANDERSON } ly s 5. DSD SIGNATURE ,p No. CE -4381 ./ • r Approved for bedrooms. ♦��� ��0'Essta'P:��• Disapproved. Conditional approval for bedrooms, with the following stipulations: `J VIV-JIIC �� Additional Comments 1 tN4 T ER AND M WASTEWATER Hl!_ =. f -NTS_ ,.��. Attachments: HAA Checklist X Maintenance Agreements Septic System Advisory Supplemental Engineer's Report Well Flow Advisory Other By: Original Certificate Date: ? 1s1c + \ 1 (Rev. 12/DO) Municipality of Anchorage •A, •' Development Services Department Building Safety Division On -Site Water & Wastewater Program `" `* 4700 South Bragaw SL P.O. Box 196650 Anchorage, AK 99519-6650 www.ci.anchomge.ak.us (907) 343.7904 HEALTH AUTHORITY APPROVAL CHECKLIST Legal Description: Lot 3. Block 4. South Hills Subdivision Parcel ID: Q17-072.12 A. WELL DATA Well type P1lvate If A, B. or C provide PWSID # _ Date completed 1114/1978 Sanitary seal (Y/N) Y Total depth JL_fL Cased to fit. FROM WELL LOG Date of test 111411978 Static water level 35 f . Well production 15 g.pm. WATER SAMPLE RESULTS: Well Log (Y/N) Y Wires properly protected (YM) Y Casing height (above ground) >,24 in. AT INSPECTION 33 ft. 2.6 g.p.m. Coliform _g,_colonles/100 mL Nitrate * .20 mgA. Other bacteria . 5 colonies/1 oo ml. Date of sample: 112912003 Collected by: A. Harsh B. SEPTICIHOLDING TANK DATA Tank Type/Material SepfleMeel Tank size .1.250 gat. Number of Compartments 2 Foundation cleanout (YM) Y Depression over tank (Y/N) N Date of pumping Pumper ,Now Construction C. ABSORPTION FIELD DATA Date installed X312002 Cleanouts (YM) Y High water alarm (Y/N) H Date installed 9117/2002 Soo rating (g.p.dAf or ft2/bdrm)1.2 OPDISF System type S Wide Trench Length 90 ft. Width 5 ft. Gravel below pipe I . ft. Total depth 215 fL Elf. absorption area RLftz Monitoring tube Y Depression over field N Date of adequacy test Results (Pass/Fail) Fluid depth in absorption field before test _ in. Water added gal. Elapsed Tlme: _ min. Final fluid depth _ in. Absorption rate >= For _ bedrooms New depth_ In. Any rejuvenation treatment (past 12 mo.) (Y/N & type) N If yes, give date g.p.d. D. LIFT STATION Date installed "Pump on' level at — in. Datum Size in gallons "Pump ofr level at — in. Cycles tested Manhole/Access (Y/N) _ High water alarm level at Meets alarm 8 drwit requirements? E. SEPARATION DISTANCES SEPARATION DISTANCES FROM WELL ON LOT TO: Septic tank/lift station on lot ->-100' On adjacent lots >100' Absorption field on lot MW On adjacent lots >100' Public sewer main NIA Public sewer manhole/cleanout NIA Sewer /septic service line >25' Holding tank NIA SEPARATION DISTANCES FROM SEPTICIHOLDING TANK ON LOT TO: Building foundation >S Property line >s Absorption field >S Water main NIA Water service line >10' Surface water >100' Wells on adjacent lots >100' SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO: Property line >1T Building foundation >10' Water main MW Water Service line MV Surface water MW Driveway, parking/vehide storage >25' Curtain drain None Noted Wells on adjacent lots >100' F. COMMENTS G. ENGINEER'S CERTIFICATION Al••�PIC AV ! certrty that 1 have determined through field inspections and : a review of Municipal records that the above systems are in ; . ..�9........ conformance with MOA HAA guidelines in effect on this date. MICHAEL E. ADDER! Engineer's Printed Name Michael E, Anderson. P.E. No. CE -4361 Date 2=3 •♦e�eirec - HAA Fee 3 3 7 5 Waiver Fee $ — Date of Payment 2-1-310.T Date of Payment Receipt Number 3 VAReceipt Number. (Rev. 12100) in. 01-31-03 11:44 FROM -CUE ENVIRONMENTAL SRV CUE Environmental Services Inc. Cd6A WAVAr"sig AV"AVrAW" r"ArJrii Cf&E Ref-# Client Name Project Name/# Client Sample ID Matrix 1030520001 Anderson Engineering L3, B4, South Hills SA) 13, B4, South Hills S/D Drinking Water 9075615301 T-597 P.02/03 F-661 All Dates/Times are Alaska Standard Time Printed Daterrime 01/31/2003 9.10 Collected Date/Time 01/29/2003 10:40 Received Date/Time 01/29/2003 1120 Technical Director Stephen . Ede Released ay/ Sample Remarks: Allowable Prep Analysis PAmmewr Results PQL Units hiedlud Limits Ihte Date Init Waters Department Nitrate -N 0.829 0.200 mg/I. EPA 300.0 (<-10) 01/29/03 JS Microbiology Laboratory Total Coliform r- 5 O8, No Cali col/1 OOml. SM 18 92228 (<=1) 01/29/03 KAP t 5. LEGAL DESCRIPTION DAfiE RECEIVED INSPECTION APPOINTMENTS TIME NLIMBEfl OF,BEDROOMS TIME TIME DATE .l DATE DATE INSPECTOR * ATTACH WELL LOG. A well log is required for all wells drilled INSPECTOR INSPECTOR ❑ PUBLIC UTILITY depth (attach log if available.) 8. SEWAGE DISPOSAL SYSTEM MUNICIPALITY OF ANCHORAGE INDIVIDUAL/ON-SITE** DEPT. OF ILALIN MUNICIPALITY OF ANCHORAGE ENVIRONMENTAL PROTECTION • DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTECTION 825 L Street - Anchorage, Alaska 99501 D E V rir 1979 NOTE: THE INSPECTION FEE MUST ACCOMPANY EACH REQUEST BEFORE PROCESSING CAN BE INITIATED. ENVIRONMENTAL SANITATION DIVISION Telephone 264-4720 RECEIVED REQUEST FOR APPROVAL OF INDIVIDUAL WATER AND SEWER FACILITIES DI RECTIONS: Complete al I parts on page 1. Incomplete requests will not be processed. Please allow ten (10) days for processing. 1. PROPERTYOWNER QkW7 1& PHONE MAILIN DRESS PROPERTY RESIDENT (If different from above) PHONE 2. BUYER PHONE MAILING ADDRESS 3. LENDING INSTITUTION Ml PHONE MAILING KESS /"17 ' / nS–(— 4. REALTOR/AGENT 711,J AI L PHONE MAILING ADDRESS /)) T !i/ � ' 4661/ z% r- 5. LEGAL DESCRIPTION STREET LOCATION f//CGS/� 6. TYPE OF RESIDENCE NLIMBEfl OF,BEDROOMS El One � Four El Other SINGLE FAMILY / ❑ Two ❑ Five ❑ MULTIPLE FAMILY ❑ Three ❑ Six 7. WATER SUPPLY _ INDIVIDUAL* * ATTACH WELL LOG. A well log is required for all wells drilled ❑ COMMUNITY since June 1975. For wells drilled prior to that date, give well ❑ PUBLIC UTILITY depth (attach log if available.) 8. SEWAGE DISPOSAL SYSTEM INDIVIDUAL/ON-SITE** YEAR ON-SITE SYSTEM WAS INSTALLED. ❑ PUBLIC UTILITY NOTE: THE INSPECTION FEE MUST ACCOMPANY EACH REQUEST BEFORE PROCESSING CAN BE INITIATED. 72-010 (Rev. 6/79) ' ` (J -}I J THIS SIDE FOR OFFICIAL USE ONLY 1. TYPE OF RESIDENCE ❑ SINGLEFAMILY ❑ MULTIPLE FAMILY NUMBER OF BEDROOMS ❑ ONE ❑ THREE ❑ FIVE ❑ OTHER ❑ TWO ❑ FOUR ❑ SIX 2. WATER SUPPLY ❑ INDIVIDUAL ❑ COMMUNITY ❑ PUBLIC UTILITY Connection Verified PERMIT NUMBER DEPTH OF WELL DATE DRILLED LOG RECEIVED 3. SEWAGE DISPOSAL SYSTEM ❑INDIVIDUAL/ON -SITE ❑PUBLIC UTILITY Connection Verified PERMIT NUMBER DATEINSTALLED INSTALLER ❑Septic Tank or ❑ Holding Tank Size: !'- S_0 If Tank is homemade give dimensions: SOI LS RATING l 1.41 TYPE OF TANK MANUFACTURER TOTAL ABSORPTION AREA MATERIAL _ 4. DISTANCES WELL TO: Septic/Holding Tank Absorption Area Sewer Line Nearest Lot Line Absorption Area to nearest Lot Line 5. COMMENTS LILY APPROVED FOR _ !i _ BEDROOMS ❑ CONDITIONAL APPROVAL (letter must aq omp ny certificate) ❑ DISAPPROVED DATE BY l i 72-010 (Rev. 6/79)