Loading...
HomeMy WebLinkAboutRIVERPARK VIEW BLK 2 LT 4Onsite File Municipality of Anchorage On-Site Water and Wastewater Program • (907) 343-7904 Page 1 of 3 ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP171054 PID Number: 067-011-26 Dwelling: 0 Single Family (SF) ❑ Duplex (D) ❑ Multiple (SF and/or D) Project: ❑■ New El Upgrade Name: Troy Davis Homes ABSORPTION FIELD Address ❑ Deep Trench il Shallow Trench ❑ Bed ❑ Mound 6811 Clemens Cir ❑ Other Phone Number of Bedrooms Soil Rating Total depth from original grade 907-310-2501 4 1.2 GPD/SF 7.7 Ft. LEGAL DESCRIPTION Depth to pipe invert from original grade Gravel depth beneath pipe Subdivision Block Lot 3.7 Ft.4.0 Ft. Riverpark View Estates 2 4 Fill added above original grade Gravel length Township Range Section 0.9 Ft. 50 Ft. Gravel width Beds:Number of Lines Distance between lines SEPARATION DISTANCES 5.0 Ft. Ft. To Septic Absorption Lift Station Holding Sewer Total absorption area Number of trenches Dist.between trenches From Tank Field Tank Line 500 Ftz 1 Ft. Well >100' >100' N/A N/A >25' TANK f Septic ❑S.T.E.P. ❑Holding 0 Other Manufacturer Capacity Surface Water >100' >100' N/A N/A Anchorage Tank 1250 Gal. Material Number of compartments Lot Line >5' 10' N/A N/A Steel 2 NA Foundation >5' >10' N/A N/A LIFT STATION Manufacturer Capacity Curtain Drain None Noted Gal. Pump on level at Pump off level at High water alarm at Remarks in. in. in. Pump make and model Electrical Inspections performed by PIPE MATERIAL House to tank 03034 Tank to D3034 Installer drainrield Northern Excavating Drainfield D3034 CO/MT 03034 Inspector Jacob Millette BENCH MARK (Assumed elevation) 100 ft Inspection 2 n 1u 4/26/17 ^° 4/27/17 Location and description dates: 3rd 4,h Bottom of siding, back of house COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL ' ' A +� C OF Conditional Approval: Date _ edir ,,•„, •,`St•t11 0+e• • 49Tr .f• -- .. aP * ';3ratn 1 tdiair”'if $ ... ci.r o, Approvedki ...k_CcuutzidDate i %o/2oT7 ft0111111 F1r$ 'oma Inspection Report_9-1-12.doc RIVERPARK VIEW ESTATES, BLOCK 2 LOT 4 PERMIT # OSP171054 PID # 067-011-26 _ _ — , _ � �`�7 _ LOT1 IA/ A B 0 FCO 2.2 53.9 / � � 2 ^ CO1 • 17.6 64.3 �/ / SV1 18.4 63.2 // -... SV2 22.8 60.5 RNERP BLOCK 2 STATES /S)III 2C0 26.7 60.0 CO2 30.0 59.7 \ I MT1 37.9 58.6 LOT 4 / CO3 76.6 74,3 __ m/ MT2 77.0 74,7 50'ELECTRIC EASEMENT-- / / 10'NON-EXCLUSIVE TERMf / / / LOT 3 TELECOMMUNICATIONS EASEMENV / // 20'T&E EASEMENT ` / // ��%,>% B / ago ALTERNATE SITE ` / // FCO TH 14 // Cal V2 CO2 TH 13 2C0 �MT1 CO3 �� MT2 .� 1250-GAL SEPTIC TANK 4 1 „,*:49m 1' ••* , LEGEND All -•••• . ,• MT-MONITORING TUBE Benj in Schiller / FCO-FOUNDATION CLEANOUT 4 1"'' AEL 12592 .•�-- TH-TEST HOLE ��;` a PRc� sc"�"�4 0 50 100 SV-SEPTIC VENT A�\"�� — MN ME MI FEET CO-CLEANOUT 1"=50' RIVERPARK VIEW ESTATES BLOCK 2 LOT 4 PERMIT # OSP171054 PID # 067-011-26 MUNICIPALITY OF ANCHORAGE DEVELOPMENT SERVICES DEPARTMENT: 343-7904 4700 ELMORE RD, ANCHORAGE, AK 99519-6655 WASTEWATER DISPOSAL SYSTEM OR WELL INSPECTION REPORT Or CV 0 0 LUL U) (I) N - - /96.3 - - - 91.9 >j 95.2 71 �----91.1 91.3 1250 GAL 91.2 SEPTIC TANK V -'"---87.2 /—95.5 FINISH94.6GRADE - Ug z 94.6 ORIGINAL GRADE g0 90-9 - '— �"---90.9 86.9 86.9 50' s. 76.6 M 2 NO GROUNDWATER 5/29/16 H OF Ski �ig'�P �1�''!y+O r*:49TH f ..*9� Be#'3' nin Schiller PROFILE AS-BUILT ri}�c�sl•• •�L111 2592 •• (NO SCALE) ��ki```.==74 Wheaton Water Well, Inc, 1190 N. Wasilla-Fishhook Road Wasilla, AK 99654 (907)376-2041 Name: Troy Davis Homes, Inc. Address: 1689 Knik Goose Bay Road, Suite 400 City: Wasilla State: AK Zip Code: 99654 Well Site: River Park View Lot: 4 Block: 2 Additional: Permit #: OSP 171006 Well Depth: 121 ft. From: To: Formation: Below Ground: 119 ft. 0 2 stick up Above Ground: 2 ft. 2 8 fill 8 27 sand, silt, gravel Gal/Min: 15 27 42 wet sand, gravel Static Level: 18 ft. 42 102 wet silt Casing: 121' of 6" ID Steel 102 108 silt, gravel, water 108 118 silt, gravel Liner Pipe: none 118 121 gravel, water Screened: none Perforated: none Grouted: Bentonite QUA Depth: 20' + WATER Nihsbes ITt �Develop. Method: Air sCOJ1 Use of Well: Residential ugot Drilling Method: Rotary Fluids Used: none Pump Installed: none Other: none f Date Drilled: 2-7-2017 Driller: Ben Mattson Development Services Department • • Building Safety Division • , s M..hoe PG£ Q4 On-Site Water & Wastewater Program t� a 4700 Elmore Road P.O. Box 196650 < on 1 i Mark Begich Anchorage, AK 99507 SA ET r Mayor www.muni.orq/onsite (907)343-7904 Pump Installation Log Well Drilling Permit Number: SW OSP171006 Date of Issue: 1-23-2017 Parcel Identification Number:067-011-04.000 Legal Description Property Owner Name& Address: River Park View Lot 4 Block 2 Troy Davis Homes,Inc. Clemens Circle 1689 Knik Goose Bay Road#400 Eagle River,AK Wasilla,AK 99654 Pump Installation Date: 10.5-2017 Pump Intake Depth Below Top of Well Casing: 93 feet Pump Manufacturer's Name: Goulds Pump Model: 10HS05412CL Pump Size 112 hp Pitless Adapter Burial Depth: 13 feet Pitless Adapter Manufacturer's Name: Harvard Pitless Adapter Installer: Unknown Well Disinfected Upon Completion? 0 Yes ❑ No Method of Disinfection: Chlorine tablets Comments: 10 GPM Pump Installer Name: Wheaton Water Well, Inc. 1190 N.Wasilla-Fishhook Road Wasilla,AK 99654 Attention: The pump installer shall provide a pump installation log to the DSD within 30 days of pump installation. MUNICIPALITY OF ANCHORAGE / On-Site Water&Wastewater Program �o enc S ^ PO Box 196650 4700 Elmore Road Anchorage,Alaska 99519-6650 Phone:(907)343-7904 Fax:(907)343-7997 ;' http://www.muni.org/onsite i" cpartmcnt 4h�HORpVE On-Site Wastewater Disposal System Permit '1/27/i7 Sot1 Permit Number: OSP171054 Effective Date: 4/21/2017 Work Type: Septic Initial Expiration Date: 4/21/2018 Tax Code Number: 06701126000 Site Legal Address: RIVERPARK VIEW BLK 2 LT 4 G:0364 Site Mailing Address: Owner: TROY DAVIS HOMES INC Lot Size in Sq Ft: 56459 Design Engineer: ANDERSON ENGINEERING Total Bedrooms: 4 This permit is for the construction of: 0 Disposal Field L Septic Tank ❑ Holding Tank ❑ Privy ❑ Private Well ❑ Water Storage All construction shall be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80) 3. The wastewater code requires inspections during the installation. The engineer shall notify the Development Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather shall be either: a. Opened and Closed on the same day, or b. Covered, sealed, and heated to prevent freezing Received By: Lip/041v yr_ Date: Issued By: Re L" ,((I * Date: G2417 MUNICIPALITY OF A► , -,HRAGE Community Development Department ;lE At'f 1 7 Lull ? one: 907-343-7904 litilli Development Services Division _ Fax: 907-343-7997 On-Site Water & Wastewater Program 16 ti r ON-SITE SEWER/WELL PERMI A ON 0._54.---4,:t+11"n . o';,_it f 011.2,b Parcel I.D. Property owner(s) Troy Davis Homes Day phone 310-2501 Mailing address 1689 S. Knik Goose Bay Road #400 Wasilla, AK 99654 Site address 21371 Conley Avenue Chugiak, AK 99567 Legal description (Sub'd., Block & Lot) Riverpark View, Block 2, Lot 4 Legal description (Township, Range & Section) Lot Size 56,459 Sq. Ft. Number of Bedrooms Four (4) APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING: (®all that apply) Absorption Field 0 Initial ix I Single Family (SF) 0 (w/wo ADU) Septic Tank 0 Upgrade ❑ Duplex (D) ❑ Holding Tank El Renewal ❑ Multiple Dwellings ❑ Privy ❑ (SF and/or D) Private Well [1 Water Storage ❑ THIS APPLICATION INCLUDES A VARIANCE /WAIVER REQUEST FOR: Distance: I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal Codes. 7741-4-LL E au„,L--, (Signature of property owner or authorized agent) Permit/Rush Fees: q-$T' 215 - 5'al Waiver Fees: Date of Payment: t-li rgl« Date of Payment: Receipt Number: 0 g3 04 Receipt Number: Permit No. 05P rftUS Waiver No. Permit App_9-1-12.doc ANDERSON ENGINEERING P.O. BOX 240773 ANCHORAGE, AK 99524 522-7773 677-7766 (FAX) April 18, 2017 Municipality of Anchorage Development Services Department On-Site Water and Wastewater Program 4700 South Bragaw Street Anchorage, AK 99519-6650 Subject: Lot 4, Block 2, Riverpark View Subdivision Septic System Design and Permit Application Impacts to Adjacent Properties Dear Onsite Services Engineer: The owner of Lot 4, Block 2, Riverpark View Subdivision intends to construct a new four-bedroom home on the lot. We are therefore requesting a permit be issued for the construction of a new well and septic system to accommodate the home. The attached Site Plan and backup documentation identify the location and configuration of the proposed well and septic system along with the alternate site. Also identified on the plans are the existing wells in the area and septic systems on surrounding lots. No conflicts exist between the proposed septic system and the existing septic systems and wells on this and adjacent lots. Drainage arrows and ground surface contours are shown on the site plan showing the grade and direction of flow on the lot. The drainage pattern will not be changed as a result of this project. The test holes placed on the lot in the area of the absorption trenches and alternate site indicate gravel (GM/GW) with varying amounts of sand and silt. The percolation rate of the soil was determined to be 1 to 5 minutes per inch. No groundwater was found during the placement of the test holes and none was found in either test hole during the monitoring period. An application rate of 1 .2 gallons per day per square foot was used in the design of the absorption system. We are proposing to place a new 1 ,250-gallon septic tank and a 50' long by 5' wide by 4' effective depth absorption trench to treat and dispose of the effluent generated in the house. The elevation of the distribution line in the absorption trench will be 4.0' below the surface and the total depth will be 8.0'. A minimum of 3' of fill or 2" of insulation and 2' of fill will be placed over the absorption trench and 4' over the septic tank. The ground surface on the lot in the area of the septic system slopes to the southwest at a shallow grade. The new trench will be constructed parallel to the ground contours in conformance with Municipal requirements. The new septic system will be constructed a minimum of 100' from all wells and any surface water and 10' the proposed and existing water services in the area. Lot 4, Block 2, Riverview Park April 18, 2017 Page Two If the system is constructed in accordance with our design the following statements apply: 1. The system, if constructed as designed, will have no adverse impact on the wells in the area or those to be constructed in the future. 2. The system, if constructed as designed, will have no adverse impact on existing septic systems in the area or those to be constructed in the future. 3. The system, if constructed as designed, will have no adverse impact on reserve space, either surface or subsurface, on any lots located in the area. 4. The system, if constructed as designed, will have no adverse impact on drainage patterns in the area. The current drainage pattern will be maintained. Sincerely, itt' `14-4-4t-L 4/" OF AI to Michael E. Anderson, P.E. �•• ''��� Attachments e•••• • MICHAEL E. ANDERr:L'N<< ����' • CE-4381 ..' la k PRO r- 3 3 K rriZ N BLOCK 2, LOT4 C") � RIVERPARK VIEW SUBDIVISION ...# ....... ..........s.---------„............... .......------......411) r VACANT 1 �``wNi'L"g VACANT 4:4G ' Existing " E .. .4 Existing 'ii ' 49th �N *•♦♦ R • O MICHAEL E. ANDERSON ;gal 110 C‘ No. CE-4381 +/ ♦ , A'ESSliti4. O..4 0 AREA MAP SCALE 1' = 100' i ,- -/ � \ \ / I • _ LOT 1 _/ I '\ / �- /L-rr /: tc / \ F7ffistin9 I I \ / i — --/ ..., \ / / // ,Well \ I te n -----LOT---44. / / ! \/ / / \ / / \ / \1 I I 11 \ / / "‹, •-. xistin• ��, / �. I C • % 50' ELECTRIC EASEMENT / / \ / . •I� I�`N \ ;i I / 1 1 , / \ I \ \ s , , \/' I,•• = _ -—(PExistin9 1 \ / (- - • �, // r—�—— I Well I \\ 10' NO't EXCLUSIVE TERM /�^ '�(/ ,/\\ / I \ / \ \� \ / TELECOMMUNICATIQNS EASEMENT, /' / •j\, / •t \. \\ \, ` / ! ,�\ // \\ ' �. LOT \ \, 20' T&E EASEMENT , \ / n ‘`. / .`` / FOUR BEDROOM \ S - �� / \ / \j....... � ANN �� // \\ %• /' /�\ HOME �� \, / \ \ '. — C / ) \ / / \ `_ / p N\ '�-, x-- __ ` --__..e,.` / \ .I / FCO 7---_ 7• i 'N \ / N. / / / 71./— 40 4� nit __ \ /� LEGEND // '�,� // / o f>� \.,� / \ , / s. '\ 1/ SV — Septic Vent -- e / \. / / - Sy 1+ ' TH13 \,\\ I- �t N. CO — Clean"GO -, /'� / 1,250 Gallon 2C0 e� -_ __—_- �\ 'I MT — Monitory ^ *7 X,\ Septic Tank c, �Q�P \ \ TN — Test Hole �u` \ \ `\ ,f \ CONTOUR INTERVAL — 4' + /Q � 50' Long x 5' Wide it c')/4.•.7., ` •, � /� \\ 4' Effective Depth �.N. `�-N. ar •we BLOCK 2, LOT 4 Q Absorption Trench — S . 49th `'` *its RIVERPARI< VUE -4p \\\ p \ SUBDIVISION \�` \ \, •:01.Mt ANDERSONlarg 56,459 s.f. \. \ S 89.21'59"W 142.28' 0,0'‘,..%p':,.. No. CE-4381 ,.•''ti No Conflicts with Wells •. ...' �,u.\...04,,,,,, SITE PLANN.SCALE 1' = 50' \.\ LOT 4, BLOCK 2, RIVERPARK VIEW SUBDIVISION DESIGN FACTORS: SYSTEM REQUIREMENTS: Four Bedroom Home 5'Wide Trench System Perc. Rate: 1 -5 Min./Inch 1,250 Gallon Septic Tank Application Rate: 1.2 GPD/SF 4' Drainfield Rock 4 Bedroom4 X 150 GPD/1.2 GPD/SF (Application Rate)= 500 SF Absorption Area 500 SF/5 SF/LF*.5 (Red. Factor) = 50 LF Trench Length THEREFORE: Construct a 50' Long x 5'Wide x 4' Effective Depth Absorption Trench at the Location Shown on the Site Plan. Flowline Elevation in the Trench to be Placed at 4' Below the Existing Ground. Total Depth of Trench to be 8' Below Existing Ground. Place a Minimum of 4'of Cover Over the Septic Tank and 3'of Cover Over the Trench or Place 2"of Insulation and 2' of Cover. All Elements of the Septic Sytem Must be a Minimum of 100' From All Private Wells in the Area. Natural Backfill 3'6" Geotextile Fabric 6" — O 4" Perforated PVC (Holes Down) Drainfield Rock 4'0" 5' I I TYPICAL DEEP TRENCH SECTION •••��'�����, (NO SCALE) • U. '•,j♦ • y ♦ NOTE: Grade Area Over Trench to Drain Away. �x � =. • ♦♦ Minimum 6' Separation From Bedrock. ; 49th Minimum 4' Separation From Groundwater. 0 Minimum 100' Separation From Private Wells in the Area. �♦��.:::Michael E.Anderson Minimum 100' Separation From Surface Water or Streams. / . / No, CE4381 4. Minimum 10' Separation From Water Service Line. 11;��o /t 47,.. MUNICIPALITY OF ANCHORAGE ♦10161k >a>,bs,_ DEVELOPMENT SERVICES DEPARTMENT �� 4700 BRAGAW STREET ANCHORAGE, AK 99519-6650 m4:*' • . a 5 49th SOILS LOG - PERCOLATION TEST I r}{,!j • i✓ � ? MICHAEL E. ANDERSON ;C, r ' No. CE-4381 LEGAL DESCRIPTION: LOT 4, BLOCK 2, RIVER PARK VIEW SUB. • 114(,'p'.... 1� M1C PERFORMED FOR: TROY DAVIS HOMFS 1#;;P' .10t.n DATE: 5/19/16 PROJECT No.: PARCEL ID#: TECHNICIAN: W. ROBERTS Professional Engineers Scamp: DEPTH TEST HOLE 13 (feet) OB/OG SLOPE SITE PLAN 1 2 3 A . 4 5 SEE SITE PLAN • A 6 . 7 a . 1 8 . • SILTY GRAVEL WITH SAND 9 J° GM/GW WAS GROUND WATER ENCOUNTERED? NO 10— a [F YES L?WHAT DEPTH'_ S DEPTH OF WATER AFTER MONITORING: NONE L 11 DATE OF MONITORING: 5/29/16 12 L DEPTH To DATE READING GROSS TIME NET TIMEWATER NET DROP 13 (MINUTES) (MINUTES) (INCHES) (INCHES) 14 TEST HOLE PRESOAKED PRIOR TO TESTING: 15 5/29 1 2:51/3:01 10 0.88"/4.00" 3.12" 2 3:02/3:12 10 1.00"/4.13" 3.13" 16 3 3:13/3:23 10 0.75"/3.88" 3.13" 17 4 3:24/3:34 10 1.00"/4.13" 3.13" 18 BOH @ 18.0 5 3:35/3:45 10 0-75"/3.88" 3.13" 19 6 3:46/3:56 10 1.00"4.13" 3.13" 20 PERCOLATION RATE: 3.2 (MIN/INCH) PERC.HOLE DIA. 6" (INCHES) TEST RUN BETWEEN: 4 FT. and 5 FT. COMMENTS: TEST HOLE PRE SOAKED PRIOR TO TEST. TEST PERFORMED BY ANDERSON ENGINEERING. I, MICHAEL E. ANDERSON CERTIFY THAT THIS WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPLE GUIDELINES IN EFFECT ON THIS DATE: 6/13/16 MUNICIPALITY OF ANCHORAGE .���Arr►Mtt�II�i,/ DEVELOPMENT SERVICES DEPARTMENT gs"0 .•': ".•Y •.0 • 4700 BRAGAW STREET ANCHORAGE, AK 99519-6650 �� o M ; 49th ti SOILS LOG - PERCOLATION TEST }}}}}},,, , MICHAEL E. ANDERSON ; .---1 ;-„pt,. LOT 4, BLOCK 2, RIVER PARK VIEW SUB. `�..• No ti` PERFORMED FOR: TROY DAVIS HOMES • I �� 0 DATE: 5/19/16 PROJECT No.: ',--"I"- PARCELID#: TECHNICIAN: W. ROBERTS Professional Engineers Stamp: DEPTH TEST HOLE 14 (feet) 1 OB/OG SLOPE SITE PLAN 4 2 a 3 4 Q 4 5 W SEE SITE PLAN 4 6 4 • 7 4 . a 8 • . • SILTY GRAVEL WITH SAND 9 ° I4 GM/GW A WAS GROUND WATER ENCOUNTERED? NO 1 O ° IF YES C;WHAT DEPTH? S DEPTH OF WATER AFTER MONITORING: NONE L 11 a DATE OF MONITORING: 5/29/16 •12 •G - GROSS TIME NET TIME DEPTH TO NET DROP 13— . DATE READING (MINUTES) (MINUTES) WATER (INCHES) (INCHES) 14—.' . TEST HOLE PRESOAKED PRIOR TO TESTING: 15— 5/29 1 4:11/4:21 10 O.75"/4.75" 4.00" 2 4:22/4:32 10 0.88"/4.88" 4.00" 16— 3 4:33/4:43 10 0.75"/4.75" 4.00" 17 Ud 4 4:44/4:54 10 0.63"/4.63" 4.00" 18 BOH @ 18.0 5 4:55/5:05 10 1.60"/4.63" 4.00" 19 6 5:06/5:16 10 0.88"/4.88" 4.00" 20 PERCOLATION RATE: 2.5 (MIN/INCH) PERC.HOLE DIA. 6" _(INCHES) TEST RUN BETWEEN: 4 FT. and 5 FT. COMMENTS: TEST HOLE PRE SOAKED PRIOR TO TEST. TEST PERFORMED BY ANDERSON ENGINEERING. I,MICHAEL E. ANDERSON CERTIFY THAT THIS WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPLE GUIDELINES IN EFFECT ON THIS DATE: 6/13/16 ON-SITE WASTEWATER DISPOSAL SYSTEM CONSTRUCTION AND MATERIAL SPECIFICATIONS SUBJECT: LOT 4, BLOCK 2, RIVERVIEW PARK VIEW GENERAL: 1. The scope of this project includes the procurement and placement of a new 1,250-gallon septic tank at the location shown on the Site Plan. Work also includes the construction of a new 50' long x 5' wide x 4' effective depth absorption trench at the location also shown on the Site Plan. The distribution line in the trench will be placed at 4.0' below the existing ground surface. Total depth of the trench will be 8.0' below the existing ground surface. The new absorption trench and septic tank must be placed a minimum of 100' from all private wells and any surface water in the area. A minimum of 2' of cover with insulation is required over the absorption trench and 4' of cover over the septic tank. 2. Construction shall be in accordance with the approved site plan, design drawings, Municipal Permit with any special provisions or conditions, and all applicable State and Municipal Wastewater Disposal Regulations. 3. The Contractor shall be responsible for obtaining all underground utility locates and for the layout of the septic system and verification of the location of all lot lines. The Contractor must also verify the location of wells in the area and assure that the separation distances are met. 4. Unless specifically agreed otherwise, the contractor shall be responsible for final grading areas subsequently depressed from soil settling. Property owner shall be responsible for revegetation of affected areas unless specifically agreed otherwise. 5. Contractors installing wastewater disposal systems must be certified by the Municipal Building Safety Division On-Site Water and Wastewater Program for system installations. Owners installing their own systems must receive prior approval from the On-Site Water and Wastewater Program before beginning system installation. SEPTIC TANK INSTALLATION 1. A new 1,250-gallon septic tank must be procured from an approved source and installed at the location shown. 2. A septic tank is to be constructed by a certified septic tank manufacturer. Construction shall include two 4" cleanouts for pumping access. 3. The septic tank shall be sufficiently bedded to prevent settling or shifting of the tank. 4. All standpipes on the septic tank shall extend a minimum of 12 inches above final grade. 5. Tanks installed without 4' of cover shall have a minimum of 2" of direct burial insulation. 6. A foundation cleanout shall be installed one to four feet from the building foundation. Two cleanouts are required between the tank and the drainfield. 7. Final grading over the tank shall be such that a positive slope exists away from the septic tank. DRAINFIELD CONSTRUCTION: 1. The drainfield shall be constructed to the dimensions shown on the design. The bottom of the trench shall be within 2" of level. 2. Distribution piping must be placed level with perforations down atop a level bed of drainfield rock. Rock should then be placed over the pipe to provide a minimum of 2" of cover. 3. A silt barrier or geotextile fabric must be placed between the drainfield rock and the natural soil backfill. 4. Monitor tubes must be 4" in diameter and installed at the locations shown on the design. The portion below ground must be perforated. 5. Contractor shall verify the septic tank and drainfield are a minimum 100' away from any private water wells in the area, 150' from a Class "C" Well or 200' from any community well. 6. Direct bury insulation must be placed over the distribution system if less than 3' of backfill depth is available. Finish grade over the trench must be mounded to prevent settlement or depressions. 7. The area surrounding the absorption trench must be graded to drain away from the trench. 8. A minimum 2' of accepting soil is required below the drainfield rock for a 5' wide trench. All pockets of unacceptable materials must be removed and replaced. MATERIAL SPECIFICATIONS: 1. Septic tanks must be constructed by a municipally approved septic tank manufacturer. 2. The following pipe materials are approved for use in septic system installations in the Municipality of Anchorage: Cast Iron (perforated and solid), ASTM D3034 or P.V.C. (perforated and solid), ASTM F810 or H.D.P.E. (perforated, but not solid) and ASTM D2662 or A.B.S. (perforated and solid). 3. Insulation shall be at least 2" thick extruded direct burial polystyrene (Dow Chemical Co. Styrofoam HI or equal). 4. Septic tank inlets and outlets shall be fitted with watertight couplings (Caulder, Fernco, or equal). 5. A permeable geotextile fabric (Typar, Mirafi or equal) must be installed between the final drain rock layer and the native soil layer. 6. All drain rock shall be .5" to 2.5" in diameter with less than 3% passing the #200 sieve. INSPECTIONS: Municipal Ordinance requires a minimum of two inspections. These inspections must be conducted under the supervision of a professional engineer registered in the State of Alaska. The first inspection must be conducted after the excavation of trenches, beds or pits and before the installation of any gravel. A septic tank may be set in place, but may not be backfilled. The second inspection must be conducted after the placement of the geotextile fabric, gravel, distribution piping, standpipes, cleanouts and insulation. No backfill should be in place at the time of inspection. Contractor shall provide a copy of all field survey layout and construction notes for use in preparing the certified as-built of the completed system. On -Site Water System Permit ,JACnt MUNICIPALITY OF ANCHORAGE c ' Development Services Department ri, , ..; On -Site Water & Wastewater Program 0611 fl" 4700 Elmore Road, PO Box 196650l L)cparCmunt Anchorage, AK 99519-6650 Telephone: (907) 343-7904 Permit Number: OSP171006 Tax Code Number: 06701104000 Work Type: Well Initial Permit Effective Dates: January 23, 2017 to January 23, 2018 Design Engineer: ANDERSON ENGINEERING Subdivision: T14N R1W SEC 24 Site Legal Address: T14N R1W SEC 24 W2SW4SW4SW4,SE4SW4SW4SW4 G:0364 Owner/Address: TROY DAVIS HOMS INC 1689 S KNIK GOOSE BAY ROAD WASILLA AK 996540000 Site Mailing Address: 6831 CLEMENS CIR, Eagle River Lot Size in Scl Ft: 301439 Total Bedrooms: 1 This permit is for the construction of: N Disposal Field N Septic Tank N Holding Tank N Privy Y Private Well N Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80). 3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either: A. Open and Close on the same day. B. Covered, sealed, and heated to prevent freezing. Special Provisions: When well testing is complete, the well driller shall place an approved sanitary seal on the well head and no pitless adapter or pump shall be installed until an approved wastewater disposal system has been constructed. Received B Issued By: By !l QA, Dater 4 Date: l /y 7 MUNICIPALITY OF ANCHORAGE - 60k))i Community Development Department Phone: 907-343-7904 Development Services Division Fax: 907-343-7997 On -Site Water & Wastewater Program ON-SITE SEWER/WELL PERMIT APPLICATION Parcel I.D. 067-011-04 Property owner(s) Troy Davis Homes Day phone Mailing address 1689 South Knik Goose Bay Rd, Wasilla, AK 99654 Site address 6831 Clemens Circle, Eagle River, AK 99577 Legal description (Sub'd., Block & Lot) Legal description (Township, Range & Section) T1 4N R1 W SEC 24 W2SW4SW4SW4 SE4SW4SW4SW4 Lot Size 301,439 Sq. Ft. Number of Bedrooms Loi-I(P) APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING: (® all that apply) Absorption Field ❑ Initial 0 Single Family (SF) ❑ (w/wo ADU) Septic Tank ElUpgrade ❑ Duplex ❑ (D) Holding Tank F-1Renewal F-1Multiple Dwellings ❑ Privy ❑ (SF and/or D) Private Well ❑X Water Storage ❑ THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR: Distance: I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal Codes. owner or authorized agent) Permit/Rush Fees: a16 Date of Payment:11/-4-IR Receipt Number: daff&L4&) Permit No. (35U1 _1L 1116 (0 Permit App__- : Waiver Fees: Date of Payment: Receipt Number: Waiver No, T14N R1W W2SW4SW4SW4, 1 "=100' SEC 24 SE4SW4SW4SW4 0 B in Schiller P�^�, •, AEL12592 ,••��i PROFESSIOHP�'�.��� BDIVISION gusH • eG, • Municipality of Anchorage h ° q° --4 O - On-Site Water and Wastewater Program r\7) :; t!s u' 2 (907) 343-7904 s a r e T r OCT 1 Certificate of On-Site Systems Approval \ °►. ti 067-011-26 Parcel I.D. Expiration Date: �0 X01 1. GENERAL INFORMATION Complete legal description River Park View Block 2 Lot 4 Location (site address) 6811 Clemens Cir Current Property owner(s) Troy Davis Home Inc. Day phone (907) 357-9394 Mailing address 1689 S Knik Goose Bay Rd #400, Wasilla, AK Real Estate Agent Day phone 2. TYPE OF DWELLING: Q Single Family (w/wo ADU) ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF BEDROOMS: 4 4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Individual Well 0 Individual 0 Individual Water Storage ❑ Holding Tank ❑ Community Class Well ❑ Community ❑ Public Water System ❑ Public Sewer ❑ WaiverNariance request for: Distance: Received by: ,._ Date: 10 ra q/ 7 COSA to be released to the en " eer,unless otherwise requested by the engineer. COSA Fee $ (.? 5b'i"d1 h h` I•WWaiver Fee $ Date of Payment 10'11 ` � 1 Date of Payment Receipt Number 0 ' °{t�p5 b Receipt Number COSA# () `1 l`[`0 u Waiver# 14 te 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On-Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm Forge Engineering Phone 907-522-9090 Address 1399 W. 34th Ave. Suite 203 Anchorage, AK 99503 Engineer's Printed Name Benjamin Schiller Date 1 0/1 1/17 * . 4 9 TN ? ..� '' 6. DSD SIGNATURE System #1 Approved for Li bedrooms r4.: System #2 Approved for bedrooms la ►, t7 . Disapproved . !' � Conditional approval for bedrooms, with the following stipulations: T /Yo - --- `y�Q� ec ; •="'7 ` poN-SITE c WATER AND WASTEWATER o PROGRAM SERA By: Ca 64iteall Original Certificate Date: /a a20 .2017 The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On-Site Systems Approval (COSA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 7. ATTACHMENTS: COSA Checklist X Nitrate Advisory Septic System Advisory Arsenic Advisory Well Flow Advisory Other COSA blue sheet j. c If more than 1 septic system is on the lot: COSA Checklist# of Structure served by this system Certificate of On-Site Systems Approval Checklist Legal Description River Park View Block 2 Lot 4 Parcel ID: 067-011-26 A. WELL DATA Well type Private If A, B, or C provide PWSID# Well Log (YIN) Y Date completed 2/7/17 Sanitary seal (Y/N) Y Wires properly protected (YIN) Y Total depth 1 21 ft. Cased to 121 ft. Casing height (above ground) 24 in. FROM WELL LOG AT INSPECTION Date of test 2/7/17 New Static water level 18 ft. ft. Well production 15 g.p.m. g p.m WATER SAMPLE RESULTS: Coliform ND __colonies/100 mL Nitrate ND mg/L ND 10/4/17 Wheaton Water Wells Arsenic ug/L Date of sample: Collected by: B. SEPTIC/HOLDING TANK DATA Tank Type/Material Steel Date installed 4/27/1 7 Tank size 1260 gal. Number of Compartments 2 Cleanouts (YIN) Y Foundation cleanout (YIN) Y Depression over tank (Y/N) N High water alarm (Y/N) N Date of pumping Pumper New Construction C. ABSORPTION FIELD DATA Date installed 4/26/17 Soil rating (g.p.d./ft2 or ft2/bdrm) 1.2 GPD/SF System type 5 Wide Length 50 ft. Width 5 ft. Gravel below pipe 4 ft. Total depth 8.6 ft. Eff. absorption area 500 ft2 Monitoring tube Y Depression over field N Date of adequacy test New Constr Results (Pass/Fail) For bedrooms Fluid depth in absorption field before test in. Water added gal. New depth in. Elapsed Time: min. Final fluid depth in. Absorption rate >= g.p.d. Any rejuvenation treatment (past 12 mo.) (Y/N & type) If yes, give date D. LIFT STATION Date installed Size in gallons Manhole/Access (Y/N) "Pump on" level at in. "Pump off' level at in. High water alarm level at in. Datum Cycles tested Meets alarm&circuit requirements? E. SEPARATION DISTANCES WELL ON LOT TO: Septic tank/lift station on lot >100On adjacent lots >100' Absorption field on lot >100'100' On adjacent lots 100' Public sewer main >75' Public sewer manhole/cleanout >100' Sewer/septic service line >25' Holding tank >75' Animal containment areas >50' Manure/animal excrete storage areas >100' SEPTIC/HOLDING TANK ON LOT TO: >5' >5' >5' Building foundation Property line Absorption field 100' Water main > Water service line > Surface water > Wells on adjacent lots >100' ABSORPTION FIELD ON LOT TO: Property line > Building foundation > Water main > 10' Water Service line > Surface water > Driveway, parking/vehicle storage > Curtain drain None Noted Wells on adjacent lots >100' F. COMMENTS G. ENGINEER'S CERTIFICATIONcar .4 $ cii"..........,,.,„4 . I certify that / have determined through field inspections and 410 '..r •**5? t review of Municipal records that the above systems are in ;,0* . 49 ..` conformance with MOA COSA guidelines in effect on this date. '. '' • 7.-.--.-- ..... Engineer's Printed Name Benjamin Schiller �, �`` ' ' • : o 1 0/1 5/1 7 #° ` CE•12,592 0* efr Date i♦ ...jolts/0o eolbss0'o ®, COSA brown sheet 10-10-12.doc i —j-- — — 33021IO SN3V4313 / _ ? _ _ ,OL'CLl M.9Z,lt'10 N -- _� / // / f..) 0. I I / I i I I I I °'r ! ! / m rli W !! i .� A i ^� v; / ! PI m ! ! / *.. A1C �`" \ — � � / I 0 -Or \ i i ! • \ \ N1 / / zo./ k) �c /\ \ i\ i o / AROTF \ / I \ m ss•s' r (-)4,;.. ..\.„ Ii 11 1 N / I I / r• id11� '' . •. ! NI 1 I/ / \ . NTO I \ l I- m i /\ 7-- --'•-••..L _f_. _ _ / / / n`°, g� `' // / O // O q0�C / N / / ,Lg1, r / 0 N W N 0 O_ x v W 0 X) •0 ..i () = 0 -.0 `O_. a CD . 0 C 4 t_tf>, # 0 . •-• 9 1913� v 7 l�0'� �� i 1 7 o T3 C,S o w P 1 a. O 0 �5��20F O > tigz • 1— co > .-- o "n " O Zr i / PLOT PLAN AS BUILT X SCALE 1' = 50' GRID SW 0364 Project No. 17-049/B5 pp�� Associates , 11500 Daryl Avenue. Anchorage, Alaska 99515-3049 Lang OL inc . (907) 522-6476 Phone (907) 522-4625 Fax C �O F A���d0 Professional Land Surveyors kenOlangsurvey.com v ••L,q 0 jonathanOlongsurvey.com G S''.1-iii oP • a I hereby certify that I have surveyed the following described property: 401(!).* 49TH /\ •.-9od LOT 4. BLOCK 2, RIVERPARK VIEW SUBDIVISION (PLAT 2017-23) * * �� Anchorage Recording District. Alaska, and that the improvements situated thereon are within the property lines and do not encroach onto the property adjacent thereto. that Q imem Q no Improvements on the property lying adjacent thereto encroach on the surveyed VO. ': KENNETH G. ■ y: At id premises and that there are no roadways, transmission lines or other visible no1/04.... �oLt`7 Q� easements on said property except as indicated hereon. p .p • - 20z .-t Dated this the ,V'J +, Day of C=ct; . 7-'0 . at Anchorage, Alaska mu- ' ,00 Q.. �SSiONAL 4p It is the responsibility of the owner to determine the existence of any easements, ODOvOo�� covenants, or restrictions which do not appear on the recorded subdivision plat. AECC963