HomeMy WebLinkAboutRABBIT CREEK VIEW & HEIGHTS BLK 2H LT 9ARabbit Creek View &Heights Block 2H Lot 9A #020-551-08 Municipality of Anchorage On -Site Water and Wastewater Program . (907) 343-7904 Page 1 of 3 ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP171031 PID Number: 020-551-08 Dwelling: 0 Single Family (SF) ❑ Duplex (D) ❑ Multiple (SF and/or D) Project: 9 New ❑ Upgrade Name: Deas & Karlena Bode 16360 Diane Dr, Anchorage, AK 99516 Phone Number of Bedrooms 250-4989 3 LEGAL DESCRIPTION Subdivision Block Lot Rabbit Creek View & Heights 2H 9A Township Range Section (SEPARATION DISTANCES To Septic Absorption Holding Sewer From Tank Field Lift Station Tank Line Well >100' >100' >100' NSA >25' Surface water >100' >100' >100' N/A Lot Line 1 >5' 1 >10' 1 >5' 1 N/A Foundation 1 >5' 1 >10' 1 >5' 1 N/A Curtain Drain 1 None I Noted Remarks Owner installation Installer Deas Bode (Homeowner) Inspector C. Johansen 3SORPTION FIELD ❑ Deep Trench 9 Shallow Trench ❑ Bed ❑ Mound F1 Other Soil Rating Total depth from original grade 2.0 GPD/SF 0 Ft. Depth to pipe invert from original grade Gravel depth beneath pipe +0.5 Ft. 0.5 Ft. Fill added above original grade Gravel length 3.0 Ft. 45 Ft. Gravel width Beds: Number of Lines Distance between lines 5 Ft. ---- ---- Ft. Total absorption area Number of trenches Dist. between trenches 225 Fe 1 ---- Ft. TANK ❑ Septic ❑ S.T.E.P. ❑ Holding 9 Other Manufacturer Capacity Orenco/Advantex CAT III 1500 Gal. Material lNumber of compartments NA Fiberglass LIFT STATION Manufacturer Orenco Pump on level at i!i Capacity 100 Gal. mp off level at High water alarm at 48 in.l 42 Pump make and model Orenco/PF2005 in. 54 in. Electrical Inspections performed by MOA PIPE MATERIAL House to tank D3034 Tank to D 1785 drainfield Drainfield D 1785 Co/MTD3034 BENCH MARK (Assumed elevation) 100 ft Inspection i51 6/18/17 2nd 6/19/17 Location and description dates:3'" 6/20/17 a" Bottom of lower window COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL Engineer's Stamp !Vol ` �Iktl Conditional Approval: Date ���_. � • . `49 M ......:# / . ...�--... :-: f Be is in Schiller CE 1252 Approved �Le �G(`� ��vic�X Date .3 (5 j c �l, FO •' ; h ` �" i\ inspection rteport_u-­i-­iz.00c il RABOT CREEK SI H BLOCK 2H LOT 9A PERMIT # OSP171031 PID # 020-551-08 I � ,'i� tom+ tom: ' f � - !�: � '�.' C �•' � �, PERMIT # OSP171031 PID # 020-551-08 3:1 SLOPES VEGETATED I -I 811150.1 100.4 103.4 FINISH GRADE INSULATION r)PAINFIFI n Pnrx 2' MOA -APPROVED FILTER SAND 98.4 GROUNDWATER 5/21/17 93.4 45' PROFILE AS -BUILT (NO SCALE) E- -3:1 SLOPES VEGETATED 100.4 ORIGINAL GRADE I �- 100.9 100.4 �,~ j 4� be-Veliopal. en se -i -es D�f;3i3 ' 4men�: ^p p� .,� �'S iii -i a YF'J Q d �! t�W QSei%�Q F �7;'Q s"af 6�! i 4700 Elmore Road = = P.O. Qox 196650 Anchorage, AK 99507 Mark Begich s , E ; ,. Mayor }rrnv.MYa or /-Tisite (907) 3-r-.3-7904 Well Log Permit Number: OSP171031 Date of Issue: 5/30/17 Date Started: 6/5/17 Date Completed: 6/5/17 Is well located at approved permit location? Lj Yes [J No Legal Description: Rabbit crk view & hghts blk2H Iot9A Property Owner Name & Address: Bode Deas M 4910 Chuck Dr Unit A Anchorage, AK 99516 Borehole Data: Depth (ft) Soil Type, Thickness & Water Strata From To stickup _ �0 2 — overburden --�—=2 4 sandy gravel 4 16 boulder 16 18 dry gravel 18 23 silty gravel 23 27 sandy gravel 27 36 damp gravel wet gravel gravel w/ H2O 36 38 42 38 42 56 vv ater -.,,ampie xesuits: Arsenic: Nitrates: Total Coliform Bacteria: Other Bacteria: -IL u&L 3I16I\ b —t4- mg/L Sc4q �__ coloniesl100mL Vie- col/100mL Method of Drilling LJ air rotary L j cable tool Casing type: steel Wall Thickness: .250 inches Diameter_ ._ 6 . inches Depth: _56 _ feet Liner Type: __ Diameter: inches Depth: feet Casing stickup above ground: 2 feet Static water level (from ground level): 25 feet Pumping level:_ feet after hours pumping gpm Recovery Rate: 15 gpm Method of Testing: airlift Well Intake Opening Type: M Open End 1=1 Open Hole ❑ Screened Start feet Stopped feet R Perforations Start feet Stopped feet r vauiuc.�l 20' Start _ 0 feet Stopped _ 20 feet Pump: Intake .Depth feet Pump size hp Brand Name Well Disinfected Upon Completion? (1 Yes (1 No Method of Disinfection;_ chlorine tablets Comments: Well Driller_ Hefty Drilling, Inc. 3540 Akula Dr. Anchorage, AK 99516 Attention: The well dril ler shall provide a well log to DSD within 30 days of completion. Developmers,11- Services Department Building Safety Division On—Site Water Wasteviater Programrt 4700 Eirnore Road P.0, Box 196650 4i E T Y Mark Begich Anchorage, AK 99507 S A E T Y Mayor (907) 343-7904 Pump Installation Log Well Drilling Permit zap mbercw-D�f 171 D -2S Date of Issue: 5—' —1 —7 Parcel Identification Number: � Legal Description Property Owner Name & Address: Wt;lr UK vie&,, � R5tic q A Pump Installation Date: Pump Intake Depth Below Top of Well Casing: 0 feet Pump Manufacturer's Name: Pump Model: I ID 5 qG (2-7 — 200 Pump Size "I by Pitless Adapter Burial Depth: J() feet Pitless Adapter Manufacturer's Name: C -90f 6e /I R—/0 V Pitless Adapter Installer: Well Disinfected Upon Completion?Yes F, No Method of Disinfection: ' * 0 LA loriq� Comments: Pump Installer Name: Attention: The pump installer shall provide a pump installation log to the DSD within 30 days of pump installation. MUNICIPALITY OF ANCHORAGE On -Site Water & Wastewater Program PO Box 196650 4700 Elmore Road Anchorage, Alaska 99519-6650 Phone: (907) 343-7904 Fax: (907) 343-7997 hftp://www.muni.org/onsite On -Site Water & Wastewater System Permit Permit Number: OSP171031 Work Type: WellSeptic Initial Effective Date: Expiration Date: Tax Code Number: 02055108000 Site Legal Address: RABBIT CREEK VIEW & HEIGHTS BLK 2H LT 9A G:3340 Site Mailing Address: 16360 Diane DR, Anchorage Owner: BODE IDEAS M Design Engineer: ANDERSON ENGINEERING This permit is for the construction of: Q Disposal Field Q Septic Tank ❑ Holding Tank ❑ Privy mcnt S, �a c � e � r, epartmm" t 5/30/2017 6ficl3'W181[:3 Lot Size in Sq Ft: 20498 Total Bedrooms: Q Private Well ❑ Water Storage All construction shall be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80) 3. The wastewater code requires inspections during the installation. The engineer shall notify the Development Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather shall be either: a. Opened and Closed on the same day, or b. Covered, sealed, and heated to prevent freezing Received B3 Issued By: Date: Date: JC 30 /7 MUNICIPALITY OF ANCHORAGE Community Development Department Phone: 907 Development Services Division Fax: 907 On -Site Water & Wastewater Program ON-SITE SEWER/WELL PERMIT APPLICATION Parcel I.D. 020-551-08-000 Property owner(s) Bode, Deas & Karlena Mailing address 17015 Jacqueline Circle Site address Day phone 250-4989 1 8 9 / -' MAR 2 0 1017 Legal description (Sub'd., Block & Lot) Rabbit Creek View & Heights, BI 2H Lt 9A Legal description (Township, Range & Section) Lot Size 20,498 Sq. Ft. Number of Bedrooms 3 APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING: (® all that apply) Absorption Field ❑X Initial ❑X Single Family (SF) ❑X (w/wo ADU) Septic Tank ❑x Upgrade ❑ Duplex (D) ❑ Holding Tank ❑ Renewal 1_71 Multiple Dwellings ❑ Privy ❑ (SF and/or D) Private Well ❑X Water Storage ❑ THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR: Distance: I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal Codes. Permit/Rush Fees: Date of Payment: _ Receipt Number: _ Permit No. Permit App__- :L. -c: _rb-T_ Waiver Fees: 61 Date of Payment: SfZz/Z7 41' 02,11) i3-7 (44 Receipt Number: G 2121✓' Z O,SP/71 b3) Waiver No. 0 5 I7/0 3 u OK <�Pe owner -1v Gv I*r (�S5 YL ANDERSON ENGINEERING P.O. BOX 240773 ANCHORAGE, AK 99524 522-7773 677-7766 (F May 24, 2017 Municipality of Anchorage Development Services Dept- On -Site Water & Wastewater Program 4700 Elmore Rd Anchorage, AK 99507 Subject: Rabbit Creek View & Heights Sub, Block 2H Lot 9A Septic system design and permit application Dear On -Site Services Engineer: The owner of the above lot intends to build a 3 -bedroom home on the property, so we are submitting this permit application for the construction of a new well and septic system. The attached site plan identifies the location of the home as well as the proposed well, septic location and alternate site. No conflicts exist between this proposed system and any wells, whether on this lot or adjacent lots. Drainage arrows are shown on the site plan showing the direction of flow. The drainage pattern in general will not be changed by the construction. There was a test hole placed on the lot back in 2013; however, there are inconsistencies in the dates and perk calculations. The hole indicates very silty sand with some gravel, and n groundwater or bedrock was found down to 10'. Adjacent lots show water to be at 2' to 3' below grade after monitoring, with slightly better percolation rates. We dug a new test hole and placed a monitoring tube in it. We also performed two new perk tests on the site. We found similar results to the neighboring property, with perk rates between 30-60 min/in., and groundwater at 2' below grade. We are proposing to place a new 1500 -gallon septic tank w/ an Advantex System on the lot. An application rate of 2.0 gpd/sf was used in the design of the absorption system. The trench will be a 5' wide, shallow trench (6" effective), 45' long. The elevation of the distribution line will be 2.5' above the existing surface, for a 4' separation from bottom of rock to groundwater. Soil will be mounded 2' above the trench and sloped at 3:1 to the existing grade. A minimum of 2" of insulation and 2' of fill will be placed over the absorption trench and 4' over the septic tank. The ground surface on the lot slopes toward the road an average of 6-8%. There are no slopes of 25% or greater within 50' downslope of the bed. The new bed will be constructed parallel to the slope as much as possible. There will be 10' separation between the proposed and alternate sites. There will be a minimum of 100' separation from all wells and surface water, and more than 5' separation from the septic tank. If the system is constructed as designed, it will have no adverse impact: • On the wells in the area or those to be constructed in the future. • On existing septic systems in the area or those to be constructed in the future. • On reserve space, either surface or subsurface, on any lots located in the area. • On drainage patterns in the area. The current drainage pattern will be maintained. Sincerely, Benjamin Schiller, PE m `' 7HP k.s n� .......... :1g J Scliller c W pJ. ANDERSON ENGINEERING P.O. BOX 240773 ANCHORAGE, AK 99524 522-7773 677-7766 (FAX) May 22, 2017 Municipality of Anchorage Development Services Department On -Site Water and Wastewater Program P.O. Box 196650 Anchorage, AK 99519-6650 Subject: Rabbit Creek View & Heights, Block 2H Lot 9A Engineered receiving soils waiver Dear On -Site Services Engineer: The owner of the above lot is building a home with a new septic system and well on this lot. Due to the high groundwater, a mounded system will be necessary to achieve the required separation distance from groundwater. The test hole data shows peat for the first two feet, and gravelly silt under that. The seasonal high groundwater has been measured at 2', right at the top of the in-situ soils. Current code requires 2' of in-situ receiving soils above the seasonal high groundwater levels. We are asking for a waiver to allow 2' of classified fill (either Type II soils or well -graded sand) to be used in this case. The peat will be removed from under the trench, minimum of 2' of classified fill placed, then 2' of sand, and then the filter rock. Thus, the 4' separation to groundwater will be met. There are no adverse consequences to this proposal. The classified fill is better quality than the in-situ soils, and this waiver will allow for the required separation to groundwater. Thank you for considering this request. ``0v�LUW,11 i Of A4 Sincerely, IV IV .. . � .V Benjamin Schiller, P.E. � .Blit'•!►': I=�%� 0 Qb � �N+�: �: r 55•j7=�"� RABBIT CREEK VIEW & HEIGHTS, BK 2H LT 9A DESIGN FACTORS: Peak flow: 450 GPD (3 bedroom) Perk rate: 48 min/in Application rate: 2 GPD/SF (Cat III System) SYSTEM REQUIREMENTS: 450 GPD / 2 GPD/SF / 5' wide ' 1.0 reduction = 45 LF of trench 5 -Wide Trench 1500 -gallon septic tank Category III Advantex System THEREFORE: Construct a trench 5'x 45' x 0.5' effective depth. Flow line elevation in the trenches will be 2.5' above original ground surface. Provide 2' of MOA -approved sand below drainfield rock. Remove all peat and organics and provide sand or Type II classified fill down to in-situ soils. Provide insulation and 2' cover over absorption trenches and 4' cover over septic tank. 6" TOPSOIL t" PVC REVEGATE MOUND 10 x 1-16" DIAMETER HOLES 2" INSULATION AND 2' COVER V DRAINFIELD ROCK T 6" BELOW LATERAL i 2.0 SIDE SLOPES @ 1.0 J� EXISTING GRADE MOA -APPROVED a; J 2.0j COARSE SAND 2.5 T REMOVE ALL PEAT AND TYPE II CLASSIFIED FILL OR 5.0 ORGANICS MOA -APPROVED COARSE SAND IN-SITU SOILS 5' TRENCH SECTION (NO SCALE) NOTES: GRADE AREA OVER BED TO DRAIN AWAY MINIMUM 6' SEPARATION FROM BEDROCK MINIMUM 4' SEPARATION FROM BOTTOM OF BED TO GROUNDWATER MINIMUM 100' SEPARATION FROM WELLS OR SURFACE WATER AV AV ■ 49th NJAYN SCHILLER No. CE -12592 fROFESSt � G MUNICIPALITY OF ANCHORAGE DEVELOPMENT SERVICES DEPARTMENT 4700 ELMORE ROAD ANCHORAGE, AK 99519-6650 SOILS LOG AND PERCOLATION TEST LEGAL DESCRIPTION: RABBIT CREEK VIEW & HEIGHTS, 82H L9A PERFORMED FOR: DEAS BODE DATE: 5/11/2017 PROJECT No.: PARCEL ID#: TECHNICIAN: B. SCHILLER DEPTH Test Hole THI (feet) I ORGANICS/PEAT 2 3 BROWN SILTY GRAVEL 4 6 GREY CLAY WITH GRAVEL 7 8 9 II I 15 16 17 18 19 COMMENTS: WAS GROUNDWATER ENCOUNTERED?YES IF YES @WHAT DEPTH -0 DEPTH OF WATER AFTER MONITORING: 2.0 DATE OF MONITORING: 5/21/17 SITE PLAN SEE SITE PLAN DATE READING GROSS TIMEFNETTIME TES) WgTER (INCHES) NET DRO(MINUTES) (INCHES) TEST HOLE PRESOAKED PRIOR TO TESTING: PERCOLATION RATE;_(MIN/INCH) PERC. HOLE DIA_INCHES) TEST RUN BETWEEN: FT. and FT. MUNICIPALITY OF ANCHORAGE DEVELOPMENT SERVICES DEPARTMENT 4700 ELMORE ROAD ANCHORAGE, AK 99519-6650 SOILS LOG AND PERCOLATION TEST LEGAL DESCRIPTION: RABBIT CREEK VIEW & HEIGHTS, B2H 1-9A PERFORMED FOR: IDEAS BODE DATE: 5/22/2017 PROJECT No.: PARCEL IDn: TECHNICIAN: B. SCHILLER DEPTH (feel) I- 2 3 4 6 7 8 9 10- 11- 12- 13- 14- 15- 16 - IT 18- 19. COMMENTS: Perk Test P 1 SLOPE WAS GROUND WATER ENCOUNTERED? IF YES @a WHAT DEPTHS DEPTH OF WATER AFTER MONITORING: DATE OF MONITORING: SITE PLAN SEE SITE PLAN DATE READING GROSS TIM (MINUTES) NET TIME (MINUTES) DEPTH To WATER (INCHES) NET DROP (INCHES) TEST HOLE PRESOAKED PRIOR TO TESTING: 5/22 1 4:10 3.25" 2 4:40 30 4.63" 1.38" 3 4:45 1.75" 4 5:15 30 2.63" .88" 5 5:20 1.50" 6 5:50 30 2.38 .88" PERCOLATION RATE: 34.1(MINQNCH) PERC. HOLE DIA. 6)" (INCHES) TEST RUN BETWEEN: 2.0 FT. and 3.0 FT. MUNICIPALITY OF ANCHORAGE DEVELOPMENT SERVICES DEPARTMENT 4700 ELMORE ROAD ANCHORAGE, AK 99519-6650 SOILS LOG AND PERCOLATION TEST LEGAL DESCRIPTION: RABBIT CREEK VIEW d HEIGHTS, B21-1 L9A PERFORMED FOR: IDEAS BODE DATE: 5/22/2017 PROJECT No: PARCEL ID#: TECHNICIAN: B. SCHILLER DEPTH Perk Test P2 (feet) 1 2 3 4 6 7 8 9 10 11 12 13 14 15 16 17 18 19 COMMENTS: SLOPE WAS GROUND WATER ENCOUNTERED? IF YES @WHAT DEPTHI ,S DEPTH OF WATER AFTER MONITORING: IEPU� DATE OF MONITORING: Benj in Schiller • •' C 12592 •� i .' wra.mn `' i SITE PLAN SEE SITE PLAN DATE READING GROSS TIME (MINUTES) NET TIME (MINUTES) DEPTH TO WATER (IN CHES) NET DRO (INCHES) TEST HOLE PRESOAKED PRIOR TO TESTING: 5/22 1 4:10 2.00" 2 4:40 30 2.38" 0.38" 3 4:45 2.38" 4 5:15 30 3.00" 0.62 5 5:20 1.13" 6 5:50 30 1.75' 0.62 PERCOLATION RATE: 48•4(MINIINCH) PERC. HOLE DIA. 6" (INCHES) TEST RUN BETWEEN: 2.0 FT. and 3.0 FT. SOILS LOG - PERCOLATION TEST TEST HOLE 1 RRR���wwww 1 SLOPE / 6:35 OR CLASS 'C' WETLANDS n yy 2 x 3 / 8.82 4 TH-1 5 SM/ SERV SITU •� 6.30 6 GM SAND W/ SOME x LOT 9A GRAVEL GRAVEL IN 6.62 7 s 6 I II{ 6.30 9 a 10 I� /NI, BOH 11 J � / 12 � -0 '41 13 WAS GROUND WATER SLOPE 14 ENCOUNTERED?—N 15 IF YES, AT WHAT TH 1e DEPTH? x 17 DEPTH TO WATER AFTER MONITORING? -XX- 1s DATE: XOOf120XX WATER DATE PERFORMED: 4115113 READING DALE TME MET TYE LEVEL IEf DROP READING PEROLATION RATE 77 (minlinch) PERC HOLE DIAMETER 6 kxtms TEST RUN BETWEEN 3 FT AND 4 FF COMMENTS: Test hole excavated by BEEKS CONTRACTING. Prec hole was presoaked. Test run for one hour. Last 3 readings reported PERFORMED BY: Steven R. Pannone, P.E. 1 CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDLINES IN EFFECT ON�THE OF THIS TEST. "°�S' /�DATE PANNONE ENG SVC, LLA. P.O. BOX 102954 ANCHORAGE, AK 99510 ���` 14 . �oF.ACas1�' Dale 4„7„3 PHONE (907) 272-8218 FAX (907) 272-8211 THy�jl/ �..... .. .... J Scale P.I.D. NO RABBIT CREEK NEW & HEIGHTS, BLOCK 2H, LOT 9A _ 020-551-08 CHARLES PRESTON DIANNE DRIVE } LtWven ."OD none IIl CE 8149 .G+i/ lk��wais5a�� PERMIT NO. OSPXXXxxX sneer SOILS LOG ANCHORAGE, AK 99516 \ 1 OF 1 1 0822f12 6:35 — 8.30 — x 6:05 30 MIN 8.82 0.39 s 8O6 — 6.30 — 4 6:35 30 MIN 6.62 024 s 6:35 6.30 -- a 7:05 30 MIN 6.79 0.23 MUNICIPALITY OF ANCHORAGE Community Development Department Phone: 907-343-7904 On -Site Water & Wastewater Program Fax: 907-343-7997 Septic System Owner -installer Agreement A real estate property owner (Owner) may install their own septic system. The department may issue an approval for a homeowner to perform work on a conventional (not AW A/TS) on-site wastewater disposal system to serve that individual's owner -occupied, single-family or duplex home if the homeowner satisfies and agrees to the following requirements. The property owner and excavation equipment operator may perform work on no more than one owner installed project in a 12 -month period. As owner of (legal description) j.oi- I A/ OkA z H 1&bki Gff k I agree the following items are true and accurate. 1. My experience Inst Ilin septic systems is as follows. �6 s 4 94-, MOA 2. The name of the excavation equipment operator is. 19&c4s ( � There will not be compensation for installation services rendered. I will be actively involved with the septic system installation at all times. The name of the inspecting engineer is 13p�r 5c4Jte_r � 6. 1 agree to discuss the following items with the inspecting engineer: a. Permit design criteria and specifications. b. Inspection requirements set forth in AMC 15.65.150. C. 2 -hour minimum advance notice given to the On-site Water & Wastewater Program for all required municipal inspections. 7. 1 agree any changes I make to the items listed above will require a new approval before performing work. 8. 1 agree to have the project -specific On-site Wastewater Disposal System Permit available at the construction site for the duration of all related work. Owner's printed name: f0&l zJe Owner's signature Septic System Owner Installer Agreement_Feb2015.doc Date: 5- 2 2- 1 -:T MUNICIPALITY OF ANCHORAGE Development Services Department Phone: 907-343-7904 On -Site Water & Wastewater Section �" Fax: 907-343-7997 Certificate of On -Site Systems Approval Parcel I.D. 020-551-08 1. GENERAL INFORMATION Expiration Date: Complete legal description Rabbit Creek View & Heights, Block 2H, Lot 9A Location (site address) 16360 Diane Drive Anchorage. AK Current property owner(s) Deas Bode Day phone (907) 250-4989 Mailing address 16360 Diane Drive, Anchorage, AK 99516 Real estate agent 2. TYPE OF DWELLING: ❑■ Single Family (w/wo ADU) ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) Day phone 3. NUMBER OF BEDROOMS: 3 e 4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Private Well Q Private Septic FE Water Storage ❑ Holding Tank ❑ Community Well ❑ Community , ❑ Public Water System ❑ Public Sewer ❑ Waiver request for: Distance: Received by: Date: COSA to be released to the engineer, unless othemise requested by the engineer. COSA Fee $ �J 5� ` '-(� o� •S� Date of Payment 6 Receipt Number q(_1 D COSA# QSc as a52 Waiver Fee $ Date of Payment Receipt Number Waiver # I 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is (are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. I acknowledge that On -Site staff may visit the site to verify the information submitted. Name of Firm Forge Civil Engineering Phone 522-7773 Address P.O. Box 240773 Anchorage, AK 99524 Engineer's Printed Name Michael E. Anderson, P.E. 6. DSD SIGNATURE System #1 Approved for _a_ bedrooms System #2 Approved for bedrooms Disapproved Date 5/11/2020 t' Conditional approval for bedrooms, with the following stipulations: q T �= m, - � J n \\ JA By:1:;:�_J6L Original Certificate Date: �1 ®Z0 The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 7. ATTACHMENTS: COSA Checklist X Nitrate Advisory Septic System Advisory Arsenic Advisory Well Flow Advisory Other COSA Checklist blue sheet Legal Description: Rabbit Creek View & Heights, Block 2H, Lot 9A Parcel ID: 020-551-08 If more than 1 septic system on lot: COSA Checklist # of Structure served by this system A. WELL DATA ❑ Well log is filed with Onsite (or attached) Date drilled 6/5/17 Total depth 56 ft Cased to 56 ft ❑ Sanitary seal is functioning correctly ❑ Wires are properly protected Casing height (above ground) '24 in. Date of flow test for COSA 6/1/20 Static water level at beginning of test 24.9 ft. Comments B. TANK DATA Age of tank(s) 3 years Tank type/material Advantex/FAP Measured operating fluid level in septic tank N/A ❑ Standpipes/foundation cleanout per record drawing Date of pumping See Maintenance Log. D. ABSORPTION FIELD DATA 5' Wide Shallow Trench Which system tested (date installed) 6/20/17 ❑ ALL standpipes present per record drawing Total measured depth from grade 3 ft (max) Measured depth to pipe invert from grade ft (min) ❑ N/A — pressurized field ❑ Monitor tubes go to bottom of effective. If not, state depth into effective ❑ Code -required soil cover over field ❑ System presoaked (Required if vacant for greater than 30 days prior to date of test) Gallons introduced N/A gallons Comments/Deficiencies: COSA Checklist yellow sheet Well production at time of test 2.2 gpm Water storage tank volume 0 gallons Well disinfected for coliform test? ❑ Yes ❑ No OR Coliform bacteria is Negative Nitrate mg/L ❑ Nitrate less than MRL (ND) Arsenic ug/L ❑ Arsenic less than MRL (ND) Collected by FORGE ENGINEERING Date of Sample 6/1/20 C. LIFT STATION ❑ Required maintenance completed Age of lift station years Lift station material Comments: See Maintenance Log. Adequacy test date 6/1/20 Results ❑✓ Pass For 3 bedrooms Fluid depth prior to test 0 in Water added 475 gal New depth 0 in Elapsed time 30 min Final fluid depth 0 in Absorption rate >450 gpd Any rejuvenation treatment (past 12 months) If yes, enter date None E. SEPARATION DISTANCES From Private Well on Lot to: (Please enter distances if less than required or if community well) Septic Tank/Lift Station on Lot > 100' Q Yes Community Sewer Manhole/Cleanout > 100' Q Yes if No ft ✓, Yes if No Neighboring Tank > 100' 0 Yes if No ft Private Sewer/Septic Line > 25' E] Yes if No Absorption Field on Lot > 100' 0 Yes if No ft Holding Tank > 100' F,71 Yes if No Neighboring Absorption Fields > 100' Yes if No Animal Containment > 50' Q Yes if No Fv� Yes if No ft Manure/Animal Excreta Storage > 100' Community Sewer Main > 75' Q Yes if No ft E Yes if No From Septic/Holding Tank on Lot to: (Please enter distances if less than required) Building Foundations > 10'✓® Yes if No ft Surface Water > 100' ft ft ft ft ft Q✓ Yes if No ft Property Line > 5' Q Yes if No ft Wells on Adjacent Lots: Absorption Field > 5' F/� Yes if No ft Private Wells > 100' ❑✓ Yes if No Water Main > 10'✓Q F/� Yes if No ft Community Wells > 200' 0✓ Yes if No Water Service Line > 10' 0✓ Yes if No ft If septic tank is under driveway comment below From Absorption Field on Lot to: (Please enter distances if less than required) Building Foundation > 10' E✓ Yes if No ft If absorption field is under driveway comment below Property Line > 10' Q✓ Yes if No ft Wells on Adjacent Lots: Water Main > 10' ✓l Yes if No ft Private Wells > 100' a Yes if No Water Service Line > 10' F/� Yes if No ft Community Wells > 200' Q Yes if No Surface Water > 100' 0 Yes if No ft F. ENGINEER'S COMMENTS G. ENGINEER'S CERTIFICATION l certify that l have determined through field inspections and review Of Municipal records that the above systems are in conformance with MOA COSA guidelines in effect on this date. COSA Checklist yellow sheet 01 '1474 -� 49th �•��� s. ...... .........: ... •. ....� 0 6 ..........................................'.....0 MICHAEL E. ANDERSON No. CE -4381 6/15/20 ft ft ft ft _s° LOT 13A df �L RAP .50 P—: n N LOT 11A N 0 z z NOTE: ' Dimensions are measured to the wood trim. I hereby certify that an accurate survey of the following described property: RABBIT CREEK VIEW AND HEIGHTS (2004-91) LOT 9A, BLOCK 2H :9 f} was made on August 25. 2018 and that the improvement: i Fr 49TH :#� situated thereon are within the property lines and do not overlap or 0•, .encroach on the property lying adjacent thereto, that no improvements on the property Y in I adjacent thereto encroach on F. Lee Knrn6¢lnikoffi9 1 I �? the premises in question and that there are no roadways, �{ No. 3143-S..-* transmission lines or other visible easements on said property except ?Z�a� as indicated hereon. Ecsements other than those shown on the {k,i 4 record plat may not appear on this drawing. cJAnchorage Alaska, this 29th day of August 2018, M13NIC:IPALITY OF ANCHORAGE ADVANCED WASTEWATER TREATMENT SYSTEM MAINTENANCE ANIS REPAIR AGREEMENT THIS MAINTENANCE AND REPAIR. AGREEMENT, herein the "AGREEMENT" made and en — r entered into as of this Day of EA of 20'.Z, by and between herein the "017v ER," and the Municipality of Anchorage. herein the `°MUNICIPALITY"'; in accordance with Anchorage Municipal Code (AMC) 15.65.365. In consideration of the mutual covenants contained herein, the parties to this Agreement agree as follows: 1. Advanced Wasteivater Treatment Systems. The Municipality, grants permission to the Owner to utilize and operate an Advanced Wastewater Treatment System (AWVFS), described as Advantex Waste Water Treatment System located at (legal description) Rabbit Creek View & Heights B2H i_9A 2. Maintenance, Repairs and Alterations. (Owner is required to read, understand and initial each section) Throughout the term- of this Agreement, the Owner shall enter into a service agreement FAV with an AWWTS service and maintenance provider approved by the Municipality or the manufacturer's representative. The AWWTS shall be maintained in a satisfactory condition capable of performing as designed and producing treated septic effluent in accordance with the equipment's approval for operation in the Municipality. It shal l be the responsibility of the Ovrrrer during the term of this Agreement to pay.for all 1IW repair(s), maintenance, adjustment(s), replacement costs, and inspection costs. This includes an annual maintenance fee (typically $400 to $600). Owner agrees that only maintenance and repair personnel approved by the Municipality or the manufacturer's representative will inspect and make any necessary maintenance, repairs or permitted alterations to the system. Owner acknowledges that regular maintenance of an AWWTS reduces the potential failure of the systern, which could include sewage backup and costly repairs or drainfield replacement. (rev. 05/18/2018) Pagel of 3 Owner acknowledges that the Municipality may request records of maintenance and repairs from the manufacturer's representative or maintenance provider. t Owner acknowledges that the fine for 4 failing to maintain and repair an AWWTS may be assessed in accordance vtjith AMC 14..60.030. Owner agrees to grant the Municipality reasonable access to test and inspect the AWWTS. The Municipality will give at least 24-hour notice. Owner agrees that any sale or transfer of title of the propeity willnot occur without a new Certificate of On -Site Systems Approval, Owner agrees that the AWWTS installation and maintenance requirements .as provided by the AVWTS vendor/installer and approved by the Municipality are the governing t guidelines for the construction; maintenance and repair of the Owner's AWWTS. Owner agrees to maintain remote monitoring of the AWWTS as required by the AWWTS approval. 3. Term_ The term of this Agreement shall begin on the date of approval by the Municipality to operate the installed system, ;or upon transfer of title, and shall continue while the A�VWTS is operational or until title is transferred. 4. \ onwaiyer. The failure of the Municipality at any time to enforce a provision of this Agreement shall in no way constitute a waiver of the provisions, nor in any way affect the validity of the Agreement or any part hereof, or the right of the Municipality thereafter to enforce every provision hereof. 5. Amendment. This Agreement shall only be amended by authorized representatives of the Owner and Municipality. any attempt to amend this agreement by either an unauthorized representative or unauthorized means shall be void. 6. Jurisdiction: Choice of lv.,aw. Any civil action arising from this Agreement shall be brought in the Superior Court for the Third Judicial District of the State of Alaska at Anchorage. The laws of the State of Alaska shall govern the rights and obligations of the parties under this Agreement. 7. Severability, Any provisions of this Agreement decreed invalid by a court of competent jurisdiction shall not invalidate the remaining provisions of the Agreement. (rev. 05/18/2018) Page 2 of OWNER, B ��y (signature) C (aitue) Date. I Gi Y Q�c.t--2, (print name) M e k-, 5S, - STATE S c STATE OF ALASKA ) ss. THIRD JUDICIAL DISTPJCT ) The foregoi a instru�m�ent was acknowledged b fore me this � day of 1 PAZ& OTARY PUBLIC FOR AL-A-SkA 7 rf+ e My Commission empires: -///Z s� rn � � O� A -� IgUNICI 4 `_tt �SICA PALITj'• •�.���. (signature) Date: l0 C7 (print name) Title. (rev. 05/18/2018) Page 3 .of 3 f16/10r, 2E_l2F1 E_tc. 2L =68671,0 APL_LS 0610312020 11:01 Anc t,orage Tank an Field aWeVB O RePOrt J Annual ins ection-- ^—_.--- - ctClC.rty nµ'a+:t/7f 0; hlRp P — Deas & Kariena ! ocie Rn Al'un7an i' 163G0 Ciane Ol'i e., AnohoragE FSK 99516 .d.;{ RII) I L) li GlJ I r11•; !) II ^X•1 r�i1��r? i Ospi i 1031 Retrieve t'3&,t,'i l:t.r n -'Hy flnn•r_ _. Rer ire, rutin ---- T i+Y'.cr :,ettlnSY�: This is a'00,: k inspection. pease send' 1 "Forge Engineering Perform FEPtd S. ttp1BH9/pti5ervation? �!Tusi pi f (S.qS Gil 2-Fi L-------- ----------- ------ Otlor of sws)14 _ Typic:a! �7, �^ue:y - Gs.tHy (� i'Rnldy ' � 5ulflrir. `—,C.�f�hng�. �:'k•��ty 1 Of!y!itrn i:Y Ph't !Conn; it) Link i Ye;'- l No Check Control ane, Reclrc Rr)tp3 L11si tt+r,e futYps FV,tt1i!)le Y)nd vgs ;a! alornic OK. n! lona �LLIC'n atn/ nnfy) �Ye' /Z N6 1ngpactlC1oari "jMP S","rn Ir).pect Clean Splice,LSD"F.... ................ � Fled Cr-rdt , ..... I .... ..... ' �� F1Cstit9. . . . .. . ............. tiL I! Pu rrp ...... ...... Sinfube't FiKe .. � Etiolu�z Purilf Vault Re; ircuiatinr.; ,pliiter VC+Ivt:....... lt' Pax carr TAX?907 2T 3715 Is g MW JIMc ®® PAGE 01 P.0011001 AnchorageTank 907-272-3543 Upetaliu Larry Better --•-"'- --------------- -... — _.'�'Car:�:at Fh6nr- _______. I {y07) 250-4989 PoC RTU rliLit, r, pztn el La?t In?:qe r;ir:n X10f231201 c 4?nCiJ2 I RT i)134222 ' !Yl����r� SEu�dgQl>3ccuts Sfudg� Scuta ----•___.. __ Pr'evinLts ' 121 Corr�rilrtrceni Ce:rr n. Current I r'nevlas:^- ! j Frevinus I2 Id COr?'Y�rilt I t v4"rti.t?{ II G !rreri °revico2 1 L -- -- -------- ------------- ------- ----•- -.--------------� -- --- -- - - ------------ lnspectfCtcan Aei+. AnTax FiRP" inspec{ Geert Odor. hfDrrnor J R,:ngent I Let err,4rJOfifioes [ L/ . rf jVOrn)4t !_ etcenf- ive l;tpmah _ r^nd PDtrOrtS ! V?Ytt i� a �Nonr_ltOnnr ( ra..ce?snre �r,tlgin9i• p tiin�il !n28k^ Inst-acticl mr, Discharge PUMP system rl II'3poC1 e rJ' rser, titd j/ insp<:c' F1r_:1t CrDQn j' r}- Splin 8clt f- aurnp � X Fk:not Corns spec,.lsgX'viGF Qf:,'S9!' SysterY CamPor+ant5 Ins In°psct Clran }rt'1peCt Cii=EYi �+ Olsintecticr, 5C+'SYirvncnl _1 OlsAcrsel t,)iersls/Grir!cs; Y y!.. '-•� t_Y1ag.Cri'4!1!Cn9 __...�5!+"�'"L'�_...-1__�.Q` `S.L.--fl:.-- --_•___•-___...------'- Adalit;OMO!'$erVIcar5 Renrierarj F-1 ter,#i10 she>t;7 ! Rcpleccci UV itcn1s7 _ !;.p1:1cs,`iusc�d other items? Pa,lr Used: IN .- warranty, 113 F Bi41:+b1e (✓r 'pf)rGpriatC selrctiDnj w 8 Marr Number Vescript;oin I�� -- -_ Fina!lisafaty lnepoction VL :ds bolted on F/ RSV rehtetnlind IIMFlnifofu rCCCnr h:d; fluilh vaiv65 cklt'•'J C_:nntro! pGhcl retclt�+;ed SvmM rylRewmMenciations — ! ,�!tle!TY pGMJrnY1rY!�: no fixther eall:n ncoJed _ kink ne-:r P -r L -m g Cr t1 For lc,n';np plated farrrr, to 1-866-384,7404