DEPT. OF ENVIRONMENTAL CONSERVATION
DIVISION OF WATER
WASTEWATER DISCHARGE AUTHORIZATION PROGRAM
August 24, 2011
Jeffery A. Garness, P.E.
Garness Engineering Group
3701 East Tudor Road, Suite 101
Anchorage, Alaska 99507
Sean Parnell, GOVERNOR
555 CORDOVA
ANCHORAGE, AK 99501
Phone: (907) 269-7519
Fax: (907) 269-3487
http://www.state.ak.us/dec/
Re: Coronado Subdivision, Lot 4, Block 2 -Eagle River -Final Operational
Approval for a Wastewater Collection System-ADEC Plan Tracking
Number 8443
Dear Mr. Garness:
On July 26, 2011 the Department received the document and record drawings
for an onlot domestic wastewater treatment system with a new 2,000 gallon,
two compartment septic tank and a new soil absorption system (Deep Trench
with an effective depth of 7 feet) for the 6 bedroom Duplex at the above
location.
The new 2,000 gallon septic tank was installed and now allows the effluent to
enter the midpoint of the 65 foot long deep trench system. You submitted a
field sample of the deeper sands from the site. This sand was not required to
be replaced because the existing homes are connected to public water from the
city and this sand material will provide the adequate treatment of the effluent
from the septic tank.
The soil absorption system was designed providing 65'x (2x7') = 910 ft2 which
was within engineering standards for this type of design.
The Department has reviewed the documentation and the record drawings
submitted for the onsite wastewater disposal and treatment system and per the
Wastewater Regulations 18 AAC 72.240, Final Operational Approval for the
proposed system is hereby issued. A "Certificate to Construct" for the duplex
wastewater system is enclosed. Please use the referenced plan number in
correspondence regarding this system.
This approval does not imply the granting of additional authorizations nor
obligate any state, federal or local regulatory body to grant required
authorizations.
Any person who disagrees with this decision may request an adjudicatory
hearing in accordance with 18 AAC 15.195- 18 AAC 15.340 or an informal
review by the Division Director in accordance with 18 AAC 15.185. Informal
review requests must be delivered to the Division Director, 555 Cordova
Street, Anchorage, Alaska 99501, within 15 days of receiving the decision.
Guidance information on the informal review process may be found at
http://www.dec.state.ak.usZcommish/ReviewGuidance.htm. Adjudicatory
hearings requests must be delivered to the Commissioner of the Department
of Environmental Conservation, 410 Willoughby Avenue, Suite 303, P.O. Box
111800, Juneau, Alaska 99801, within 30 days of the decision. If a hearing is
not requested within 30 days, the right to appeal is waived.
Thank you for your cooperation. If you have any questions please do not
hesitate to contact me at 269-7519.
Respectfully,
William R. Rieth, P.E.
Environmental Engineer
Enclosure: As stated
cc: William Smyth, WW, w/o enc.
ST.ATc OF ALASKA
-���ar,+.,"vr o==wv��o,v�,EPlr.al CCN3�RvArCw
CONSTRUCTION AND OPERATION CERTIFICATE
for .
D0MESTIC WASTE'NATER t7ISPOSAL SYSMAS
A. APPROVAL TO CONSTRUCT A.I)EC- MAM TrA -K(OG. MU WER )5 4-5
Plans for the construction or modlflcatlon of 2 Dao S aga
Y domestic wastewater disposal system
located In , Alaska, submitted in accordance with 18 AAC 72.2251
by.10.E
6eah reviewed and ora
❑ approved.
�ondltlonall approved (sea attached conditlons). 4ae—
U&
rm- OATS
rf banstructlan'has not started, hva years at the approva► dale, hfs Certlfrcat0 !s void and new plan4 and
3paciffeatfons mustbs 3ubmitt8d Forravlaw and apprcva! 6ef0rs canstruatfan.
I. APPROVED CHANGE 01`110ERS
Chang9 (aontractarderno. ordajcep wa r9far3naa)
APPROVAL rO OPERATE
i'r
Approved by pate
'APP.00VAL TO OPEaATE" 33ct!'on must b3 Como and 3tgn3d 3
3.3r#�'rl3rlt :3�Ar3 "1113 3 jV-3M '3 m3d3 a'/3113b13 f-Zr U3�
'_c !cn cf t1, 3 ZC�OD S jT �h� � Ems= 7 I� — (o fT'
.JJ
.
f'3 3/3t3M `3'iaraGy
13 �C3i 3 `.3 -OCt 30 , 1
3/3
CA i
.--
3 - : U!
3-:'::!t l^3 3�:^.IT'i:`.3� �!'f'i'3 `..`'3 ^'`3r'l1 3�Cr0'/3I C9ft:�, :r 3n 'n303clCn �' q�3
i.3.'m =n t. '�'•3 �:r1�'i Tad !i 3 3 f 3!3m .V33 .Cn3ii�:c!sd scccrJn !0 'i'3 3u"pr7'13 j 3I3r? 3.
,.'3 3/3!311 13 i13i 3by ~r1n'3,j ht -21 3oorroe11 t - ►
,. ■■■/,/�y��.�+ , . � / � '.�C 3■rr3.3 )yam/fes
Date Received
STATE OF ALASKA
DEPARTMENT OF ENVIRONMENTAL CONSERVATION
DOCUMENTATION OF CONSTRUCTION
1. GENERAL INFORMATION I
Legal Description of the Location
CORONADO S/D; BLOCK 2, LOT 4
Submitted by:
❑ Certified Installer
❑ Approved Homeowner
M Registered Engineer
Installer Name:
GREEN GENERAL CONTRACTING _
Mailing Address
15939 DIVISION ST * CHUGIAK, AK * 99567
Onsite Wastewater System Serves:
❑ Single Family. Number of Bedrooms
■ Duplex. Number of Bedrooms 6
❑ Small Commercial Facility With Estimated
Design Flow of less than 500 GPD.
11. WATER SUPPLY SYSTEM (SECTION II IS OPTIONAL)
rce of water and Containment (Check all that Apply)
❑ Dl•111er1 or Driven) ❑ Surface (Identify)
❑ Roo F nlent
❑ Holding Fan ❑ Other (Idents)
type of Water Supply System
❑ SF/Duplex
Public
Treatment of Water (Check all that Apply)
❑ None ❑ Chlorination
❑ Filtration ❑ Mineral Remova
❑ Other: 7
Wtil Data
Is the height o e well casing more than 12" above the round? ❑ Yes Q No
Is a sanitary seal or wC r installed on the well casin '?es ❑ No
Is druina a directed away frons round the casing within a radius of 10 feet of the well casino ❑ Yes ❑ No
Is well wires enclosed in conduit? ❑ Yes ❑ No
wic 07-Med Depth ofweil (Feer) Static Water Level (Feel) Yield (If available) Pump Rate (If available)
Scparatiott Dtstanoe rom t rc c Casting to ca r othcl;oilowingsobeso ontatntnauon
Septic/Holding Tank on Lotwer
Feet
Ines of
Feet
sorption Area on of
Absorption
Closest Septic/Holding Tank on A Jacent Lot
Feet
pleat Sewer mel an slit Lot
Feet
Closest Edge of an Absorption Area on
Adjacent Lot Feet
Indicate separation distance from toxic material including fuel tanks, paints, lu nts and other
petroleum based materials, pesticides, Fungicides or herbicides to well cal'
On Lot
Feel
On Adjacent Lot
Feet
Water Samples Taken by-. (Name)
Sampler is:
❑ Buyer ❑ Engineer
❑ Banker ❑ Government Official
Address
Water Sample Results:
Attach Ca ❑ Satisfactory - Date ❑ Unsatisfactor - e
Comme tits/Recommendat i o
Ice jfvtar ion, and that iprovi e 3 in ouraltaclied drawilis i •
ct•
5i azure
Typed/Printed Name
JEFFREY A. GARNESS, P.E.
Title
PROFESSIONAL ENGINEER
Date
7/5/2011
Note 1. 11 ss [ iWh �b,,!Spiby a Certified Installer, Professional Engineer, DEC staff, or Owner/Builder
2. 1 pl it water,receive ADECpIan approval prior to construction. See 18 AAC 80 Slate ofAlaska Drinking Water
ebr lrwrsfm•specefrcrequirements.
TIL WASTEWATER DISPOSAL Legal Description: CORONADO S/D; bLOCK 2, LOT 4
Type of Wastewater System:
■ Septic Tank with Conventional Soil Absorption System ❑ Package Treatment Plant (requires engineered design)
❑ Holding Tank: Material Type: Size in Gallons: Manufacturer:
❑ Other - Specify Type: ❑ Alternate Onsite (requires engineered design)
❑ Small Commercial System (<500 GPD) With Estimated Daily Wastewater Flow of: Gallons Per Day (GPD)
Criteria Used to Estimate Daily Wastewater Quantity,
■ NEW SYSTEM ❑ REPAIR TO EXISTING SYSTEM I Certified Installer Installation Notification Date:
Name of Installer: GREEN GENERAL CONTRACTING
Date Installed: 4/25-26/2011
System Installed: ❑ By a Registered Engineer ■ With Inspection by a Registered Engineer
❑ By Approved Homeowner (attach copy of approval letter) ❑ By a Certified Installer/Installer Number
Septic Tank: Material: Manufacturer: Size (Gallons): Number of Compartments:
STEEL ANCHORAGE TANK 2000 2
Type of Soil Absorption System: ■ Deep Trench ❑ Shallow Trench ❑ Seepage Pit ❑ Bed
❑ Mound ❑ Other, Specify
Soil Classification: GP TO SP
Soil Rating: 1.0 GPD FT 2
Dimensions/Size of Absorption Area: 65' x 2.5'
Grading/Size of Distribution Rock: 1.5"-2.5"
Thickness/Depth of Distribution Rock: 7,09' 922 SQ. FT
Percolation Test Results, Attach Copy of Report:
<1 Minutes per Inch N/A Sq. ft. per bedroom
Percolation Test Performed by:
GEG, Ltd.
percolation test results must be scaled/signed by a registered engineer.
List ground cover in feet over: Septic Tank: 4'+ Absorption Area: 4'+ Sewer Pipes: 4'+
Cleanout Pipes/Caps Installed: Foundation Cleanout: YES Septic Tank: YES Monitor Tubes: YES
Indicate separation distances from septic tank or absorption area, whichever is closest to, to all nearby:
Public drinking water sources within 200 feet: 200'+ Private drinking water sources within 100 feet: 100'+
Nearest water bodies (see 18 AAC 72.020(b)): 100'+ Lot Line: 10'+
Separation Distance from Onlot Sewer Lines to: Public Drinking Water Sources: 100'+ Private Sources: 25'+
Separation Distance from Bottom of Distribution Rock to: Groundwater Table: 4'+ Bedrock: 6'+
Separation Distance from Absorption Area to Slope exceeding 25%: 50'+
Comments/Recommendations:
I certify that the above information, and that provided in our attached drawings, is correct:
Signature
Typed/Printed Name
JEFFREY A. GARNESS, P.E.
Title, Reg./Cert No., Inst. No.
PROFESSIONAL ENGINEER
Date
7/5/2011
NOTE: Must be signed by a Certified Installer, Professional Engineer, DEC staff, or Approved Homeowner. If engineering seal bears printed name,
registration number, and is signed, those blocks need not be completed for engineered submittals.
SEAL
Registered Professional
Engineer
o f e s siang4a
(Rev. 01/05)
TOP OF TANK X
INLET = 95.50
INVERT OF BUN(
AT INLET = 94.8
AS -BUILT DRAWING
w FINAL GRADE _
98.90-99.90
ORIGINAL GRADE = 98.00
O HIGHEST POINT
FILTER FABRIC
BENCHMARK = TOP OF SLAB
® SOUTH MAN DOOR, EAST
WALL. ELEVATION = 98.29
INVERT OF PIPE
94.09
BOTTOM OF
TRENCH - 87.00
RELATIVE ELEVATION OF BOTTOM
OF TESTHOLE = 80.50 (DRY)
GARNESS ENGINEERING GROUP, Ltd.
CONSULTANTS & GENERAL CONTRACTORS
3701 E. TUDOR ROAD, SUITE 101 • ANCHORAGE, AK 99507 • PHONE (907)337-8179 • FAX (907)338-3249 • WEBSITE: www.gammengln"ring.com
PREPARED FOR: PHONE NUMBER: PAGE NUMBER:
JOHN THOMSON 907-240-2020 4 OF 4
LEGAL DESCRIPTION: DRAWN BY:
CORONADO S/D; BLOCK 2, LOT 4 A.J.G.
TYPE OF WORK: DATE'
PROFILE AS BUILT OF NEW SEPTIC SYSTEM 7/5/2011
(Rev 01/05)
OP OF TANK AT
)UTLET = 95.50
INVERT OF BUNG AT
OUTLET = 94.71
TH#1 & TH#2
CE 797 3
��4hyr �'`]���1-,•��o/
u0�npro € es sten°cy�/
GARNESS ENGINEERING GROUP, Ltd.
CONSULTANTS & GENERAL CONTRACTORS
3701 E. TUDOR RW. MM 101 • NCWXM0E. AK. MM7 • PRUNE: (907)337-4179 • FAX: 90 -3246 • WEMM- gom■p■nghme*
SOIL LOG — PERCOLATION TEST
LEGAL DESCRIPTION: CORONADO SUBDIVISRON; LOT 4, BLOCK 2
PERFORMED FOR: JOHN THOMSON DATE: 8/16/2010
DEPTH
(feet) �'.;•: TEST HOLE 1
2
.�-
GW
.%::ob
ORG
*600 V
3
....■�■
G M
CL
GC
I
Sp
14
SW
MH
owl ; o
SP
CH
GP TO SP
5-
f '
OH
15
'■":
6 6
7
►■■
"Ogg*
.. ;.� �•
B.O.H.
18
8
9
10
11
SOIL
.-■ ■ ■-
GW
.%::ob
ORG
*600 V
13
'•' `•`'
G M
CL
GC
I
Sp
14
SW
MH
owl ; o
SP
CH
SM
f '
OH
15
'■":
17
.. ;.� �•
B.O.H.
18
SOIL
CLASSIFICATIONS
GW
ORG
GP
ML
G M
CL
GC
I
OL
Z,nuo
SW
MH
owl ; o
SP
CH
SM
f '
OH
SC
DEPTH TO DATE
GROUNDWATER
DRY 8/16/2010
DRY 9/3/2010
f r G ness.-
CE-79 3 m�
�hpr f essiol- 4l
SEE SITE PLAN
DATE READING CLOCK NET TIME WATER LEVEL NET DROP
TIME (MINUTES) READING (INCHES)
\399
1r�0��F-�F�AN� �� 0
ov �p �4 Z FEES
/ 051, 09 N No -
19 PERCOLATION RATE <1 (MIN./INCH) PERC. HOLE DIA. 6 (INCHES)
TEST RUN BETWEEN 5 FT. AND 6 FT.
20 A FOUR HOUR PRESOAK WAS PERFORMED: ❑ YES ❑ NO
SOILS LOGGED BY: JODY MAUS PERCOLATION TEST PERFORMED BY: JODY MAUS
COMMENTS:
PERFORMED BY GEG, Ltd. I, JEFFREY A. GARNESS, CERTIFY THAT THIS WAS P FORMED IN ACCORDANCE
WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE: % Z
GARNESS ENGINEERING GROUP, Ltd.
CONSULTANTS & GENERAL CONTRACTORS
1 E ROAD. SUITE 101 ► AHGiO W& AK, 99307 • 00 7-0179 • VAX: 9Q 3M-ti'}246 • WE&ATE 9•�•►aen9MearY
SOIL LOG — PERCOLATION TEST
LEGAL DESCRIPTION: CORONADO SUBDIVISION; LOT 4, BLOCK 2
PERFORMED FOR: JOHN THOMSON DATE: $/16/2010
DEPTH
(feet) .�. TEST HOLE #2
1
r
444Qo�pdQ
05
,�
' 4 rg.H g
J f r y A. arness:
A CE 7 . 3
�inpr❑ f e s sign°ate
7
8
9
10
DEPTH TO
GROUNDWATER
:•:■
SOIL CLASSIFICATIONS
8/16/2010
DRY
9/3/2010
..•,s.
0
GP j ML
3
.es
o. ■�•
GM 11i -Ll' CL
''"•
GP TO SP (ion
'°°° SW MH
woo
too
Sm OH
••►•
- Sc
SEE SITE PLAN
6
r
r •
,
n. ..■a■
7
8
9
10
DEPTH TO
GROUNDWATER
DATE
DRY
8/16/2010
DRY
9/3/2010
DATE READING CLOCK NET TIME WATER LEVEL NET DROP
11 •or, @I TIME (MINUTES) READING (INCHES)
r• i r"■•
spo
■ • ■ .
PI-10�
9�*o«o
••: ■•■•
foot 9-p
r • r r ��(t Pc� ¢` c�1J
15
■r ■be
•�• ��5 aFoL PHP p��N
■•i ■•■• -
16 •"' `■•" �N D F��� PND
■■•�•r�
So�gF,p
.■■�■•■ —PSP� 9 �p� — —
17—
18 B.O.H. f Nb 17 X
� -
19 PERCOLATION RATE <1 (MIN./INCH) PERC. HOLE DIA. 6 (INCHES)
TEST RUN BETWEEN 5 FT. AND 6 FT.
20 A FOUR HOUR PRESOAK WAS PERFORMED: ❑ YES ❑ NO
SOILS LOGGED BY:. JODY MAUS PERCOLATION TEST PERFORMED BY: JODY MAUS
C'0MMFNITc,-
PERFORMED BY GEG, Ltd. I, JEFFREY A. GARNESS, CERTIFY THAT THIS WAS P R ORMED IN ACCORDANCE
WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE: l Z 111/0