MUNICIPALITY OF ANCHORAGE
On -Site Water & Wastewater Program
PO Box 196650 4700 Elmore Road
Anchorage, Alaska 99519-6650 Phone: (907) 343-7904 Fax: (907) 343-7997
http://www.muni.org/onsite
On -Site Water & Wastewater System Permit
Permit Number: OSP231100
Work Type: WellSeptic Initial
Tax Code Number: 05147131000
Site Legal Address: SLEEPY HOLLOW #1 TR Al GA 160
Site Mailing Address:
Owner: JACKSON KIM & ERIC
Design Engineer: FORGE ENGINEERING
This permit is for the construction of:
Effective Date
Expiration Date:
Lot Size in Sq Ft:
Total Bedrooms:
U
Department
5/15/2023
5/14/2024
361022
Q Disposal Field Q Septic Tank ❑ Holding Tank ❑ Privy Q Private Well ❑ Water Storage
All construction shall be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska
Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80)
3. The wastewater code requires inspections during the installation. The engineer shall notify the Development
Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather
shall be either:
a. Opened and Closed on the same day, or
b. Covered, sealed, and heated to prevent freezing
Received By: I ( -D r (` C.
Issued By:
Date:
Date:
3
MUNICIPALITY OF ANCHORAGE
Community Development Department Phone: 907-343-7904
Development Services Division Fax: 907-343-7997
On -Site Water & Wastewater Program
ON-SITE SEWER/WELL PERMIT APPLICATION
Parcel I.D. 051-471-31
Property owner(s) Kim Jackson
Mailing address PO Box 671387, Chugiak, AK 99567
Site address NHN Mountain Rd
Day phone 907-351-7679
Legal description (Sub'd., Block & Lot) Sleepy Hollow #1, Tract Al
Legal description (Township, Range & Section)
Lot Size 361,022 Sq. Ft. Number of Bedrooms 3
APPLICATION IS FOR:
APPLICATION IS AN:
TYPE OF DWELLING:
(® all that apply)
Absorption Field
❑X
Initial ❑x
Single Family (SF)
❑X
(w/wo ADU)
Septic Tank
1ZUpgrade
❑
❑
(D)
Holding Tank
❑
Renewal ElDuplex
Multiple Dwellings
❑
Privy
❑
(SF and/or D)
Private Well
❑x
Water Storage
❑
THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR:
Distance:
I certify that the above information is correct. I further certify that this is in accordance with
applicable Municipal Codes.
(Signature of property owner or authorized agent)
Permit/Rush Fees: 52.0 Waiver Fees:
Date of Payment: /iT2.:�2! Date of Payment:
Receipt Number: 07s/ V,17 Receipt Number:
Permit No. 0-`�? P 2.3 I I dD Waiver No.
Permit App_::- : ,'-..:c
May 15, 2023
MOA Development Services, On-Site Water & Wastewater Program
4700 Elmore Rd
Anchorage, AK 99507
Subject: Sleepy Hollow #1 Tract A1 – NHN Mountain Rd
Septic system design
Dear On-Site Services Engineer:
The owner of the above lot intends to build a 3 -bedroom home on the property, so we are
submitting this permit application for the construction of a new well and septic system. The
attached site plan identifies the location of the home as well as the proposed well, septic location
and alternate site. No conflicts exist between this proposed system and any other well or septic
system, whether on this lot or adjacent lots.
The ground surface on the lot slopes mildly toward the north at between a 5-10% slope. There are
no slopes greater than 25% within 50 feet downslope of either the primary or alternate site.
Contours are shown on the site plan showing the grade and direction of flow. Stormwater drainage
will not impact this septic system. The new trench will be constructed parallel to the slope as much
as possible.
Wells on this and adjacent lots are shown. The new system will be a minimum of 100’ from all
wells and surface water, and more than 5’ away from the septic tank. The alternate site is located
more than 6’ away.
Please refer to the attached test hole log, plan and profile pages for the septic design. If this design
is followed, there will be no adverse impacts to adjacent properties.
Sincerely,
Benjamin Schiller, PE
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP231100, Curtis Townsend, 05/15/23
CO - CLEANOUT
2CO - DOUBLE CLEANOUT
FCO - FOUNDATION CLEANOUT
FD - FLOW DIVERTER VALVE
MH - MANHOLE
MT - MONITORING TUBE
SV - SEPTIC VENT
TH - TEST HOLE
LEGEND
1"=50'
3-BDRM HOME
FCO
SLEEPY HOLLOW #1, TRACT A1
FEET
0 50 100Benjamin Schiller
CE 12592REGISTEREDPROFESSION A L E N GINEER
M
O
U
N
T
A
I
N
R
O
A
D
5/8/23
1,060 GALLON
INFILTRATOR TANK
(2) 45' LONG x 5' WIDE
x 0.5' EFFECTIVE
DEPTH ABSORPTION
TRENCH
TH#1
520
ALTERNATE SITE
SEPTIC PLAN
PROPOSED WELL
LOCATION
530
540
2CO FSV
COMT
COMT
COMT
COMT
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP231100, Curtis Townsend, 05/15/23
SLEEPY HOLLOW #1, TRACT A1
TYPICAL TRENCH SECTION
(NO SCALE)
NOTES:
1. GRADE AREA OVER TRENCH TO DRAIN AWAY
2. PROVIDE 3' OF COVER OVER TRENCHES AND 4' OVER SEPTIC TANK, OR 2'
WITH 2" OF INSULATION
3. CHECK GROUNDWATER AT TIME OF CONSTRUCTION. IF LEVEL IS HIGHER
THAN PREVIOUSLY OBSERVED, CALL ENGINEER IMMEDIATELY
Benjamin Schiller
CE 12592REGISTEREDPROFESSION A L E N GINEER
4" PERFORATED PVC (HOLES DOWN)
DRAINFIELD ROCK
5'
6"
3'
DESIGN FACTORS:SYSTEM REQUIREMENTS:
450 GPD PEAK FLOW
PERK RATE: <1 MIN/IN
APPLICATION RATE: 1.0 GPD/SF
5'-WIDE TRENCH SYSTEM
1060-GAL INFILTRATOR SEPTIC TANK
BOTTOM OF TRENCH: 6' BELOW GRADE (CAN BE LOWERED TO MAXIMUM OF 10' BELOW GRADE)
FLOW LINE ELEVATION: 3.5' BELOW GRADE
450 GPD / 1.0 GPD/SF (/ 5' WIDE * 1 RED FACTOR [0.5 DEEP])= 90 LF TRENCH REQUIRED (90 LF SPECIFIED)
GEOTEXTILE FABRIC
5/8/23
6"
6"
MOA-APPROVED FILTER SAND
2'
ADDITIONAL SOIL ADDED
FOR SETTLEMENT
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP231100, Curtis Townsend, 05/15/23
LEGAL DESCRIPTION:
PERFORMED FOR:
DATE: PARCEL ID#:
SOILS LOG AND PERCOLATION TEST
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
DEPTH
(feet)
TEST HOLE 1
DATE READING START TIME NET TIME
(minutes)
DEPTH to
WATER NET DROP
PERCOLATION RATE: (MIN/INCH)
(inches)(inches)
DATE OF MONITORING
WAS WATER ENCOUNTERED?
DEPTH TO WATER AFTER MONITORING
IF YES @ WHAT DEPTH?
0.08
4/27/23 1
2
3
4
5
GM (SILTY SANDY GRAVEL)
Professional Engineers Stamp:
no
SLEEPY HOLLOW #1 TR A1
4/27/23 051-471-31
Kim and eric jackson
11:44 0
11:45
11:46
11:48
11:49
1' OB
00:28
Benjamin Schiller
CE 12592REGISTEREDPROFESSION A L E N GINEER
5/5/23
PERC TEST LOCATION
TECHNICIAN: l.tidwell
6
n/a
dry
5/4/23
COMMENTS:
6" DIAMETER TEST HOLE PRESOAKED PRIOR TO TESTING
SITE PLAN
6
USCS SOIL CLASSIFICATION WAS VISUALLY DETERMINED
00:28
00:30
00:33
00:32
0 6 6
0 6 6
0 6 6
0 6 6
1
6*
* WATER RAN OUT BEFORE 6TH TEST COULD BE RUN, DUE TO FAST ABSORPTION AND WASTE TRYING TO
FILL THE PERK HOLE TO 6"
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP231100, Curtis Townsend, 05/15/23