HomeMy WebLinkAboutCREEKVIEW ESTATES LT 4kview Estates Lot 4 #017-161-21 Municipality of Anchorage On -Site Water and Wastewater Section • (907) 343-7904 Page 1 of 3 ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP181352 PID Number: 017-161-21 Dwelling: 0 Single Family (SF) ❑ with ADU ❑ Duplex (D) ❑ Two Single Family Project: ■❑ New ❑ Upgrade Name JEFF BOOL ABSORPTION FIELD ❑■ Deep Trench ❑ Wide Trench ❑ Bed ❑ Mound Site Address NHN RABBIT CREEK ROAD *ANCHORAGE, AK ❑ Other Phone Number of Bedrooms Soil Rating Total depth from original grade 907-317-3799 3 0.8 GPD/SF See Attached Letter Ft. LEGAL DESCRIPTION Depth to pipe invert from original grade See Attached Letter Ft. Gravel depth beneath pipe 7.02 Ft. Subdivision Block Lot CREEKVIEW ESTATES; LOT 4 Fill added above original grade SEE DWG. Ft. Gravel length 47 Ft. Township Range Section Gravel width 2.5 Ft. Beds: Number of Lines - Distance between lines - Ft. SEPARATION DISTANCES To Septic Absorption Lift Station Holding Sewer Total absorption area Number of trenches Dist. between trenches From Tank Field Tank Line 644 176 1 Ft. Well 100'+ 100'+ N/A N/A 25'+ TANK X Septic ❑ S.T.E.P. ❑ Holding ❑ Other Manufacturer Capacity Anchorage Tank 1000 Gal. Surface Water 100'+ 100'+ N/A N/A Material Number of compartments Lot Line 10'+ 10'+ N/A N/A NA Steel 2 Foundation 10'+ 10'+ N/A N/A LIFT STATION Manufacturer Capacity Remarks See attached letter regarding the install Gal. of the drainfield and septic tank. Alarm location Electrical installed by PIPE MATERIAL House to tankTank to drainfield D3034 Installer' Arctic Terra Drainfield D3034 Co/MT D3034 Inspector David Garness, P.E. and Tim Ecklund BENCH MARK (Assumed elevation) 110.45 ft Inspdection 1s` 5/29/2019 5/30/2019 Location and description 2nd GARAGE SLAB 3m 5/31/19 4`h ON-SITE WATER AND WASTEWATER SECTION APPROVAL Engineer's Stamp op60�QOO '.. Conditional Approval: Date oo •. ��0 o�...9H �. . Septic System i �O .Jef r Approv V" DateZ �� —79Gorness. ��� sf Note: this approval does not include well permit requirements. #AEcc88844�DO0o s"01 (Kev Ub/UL/18) .A e-14 Z Q PERMIT OSP181352 RECORD DRAWING A I B C •, DC01 67.3 29.6 21.9 DCO2 68.6 30.9 22.7 STI 70.3 32.7 23.8 ST2 76.3 39.3 29.3 DC03 78.7 41.7 31.2 DC04 80.1 43.0 32.1 COI 86.3 49.7 38.3 MTI 88.7 52.2 40.3 CO2 121.9 91.7 85.5 MT2 119.7 89.3 83.7 A DBL RESERVE SITE APPROXIMATE LOCATION OF GEG T.H.#1- PARCEL ID NUMBER: 017-161-21 SEWER LINE FROM HOUSE TO TANK WAS NOT INSPECTED; LOCATION IS ASSUMED /-NEW 1000 GALLON / STEEL SEPTIC TANK DBL3&4 IjT CO T1 GEG CONFIRMATION HOLE #2 (SOIL LOG ATTACHED) NEW DRANFIELD; PER THE OWNER, THE CREEK WAS SURVEYED AFTER THE ENGINEERING INSPECTIONS AND IS 100'+ TO THE DRAINFIELD - SEE ATTACHED LETTER \ BS CREEK SE?'BACIC \_'30' GREENBELT TRAIL \ ZS' STREAMEgM p_ON CREEK CENTERLINE WN V. = 40' GARNESS ENGINEERING GROUP, Ltd ENGINEERING o SALES o CONSULTING — 3701 E. TUDOR ROAD, SUITE 101 'ANCHORAGE, AK 99507 -PHONE (907) 3376179 -FAX (907) 3383246' WEBSITE: w gamessen&eenng.00m PREPARED FOR: PHONE NUMBER: PAGE NUMBER: JEFF BOOL 907-317-3799 2 OF 3 LEGAL DESCRIPTION: DRAWN BY: CREEKVIEW; LOT 4 D.J.G. TYPE OF WORK: DATE: I- SEPTIC SYSTEM RECORD DRAWINGS 12/5/2019 1132 PARCEL ID NUMBER:OSP85RECORD DRAWING 017-161-21 TOP OF TANK AT INLET = 96.32 INVERT OF BUNG AT INLET = 95.69 FINAL GRADE = 100.6-100.8 ST1 ST2 (� TOP OF TANK I I AT OUTLET = 96.32 NEW 1000 GALLON SEPTIC TANK MAX BURIAL DEPTH OF 10' AT TESTHOLE = 98.82 z GRADE AT HIGHEST POINT (FILL WAS ADDED I• OVER DRAINFIELD SITE) = 100.07 � MT CO 7.02 FEET RELATIVE ELEVATION @ BOTTOM OF T.H. = 78.32 GW @ 81.88 ON 6/7/2019 INVERT OF BUNG AT OUTLET = 95.52 GRADE = 99.5-100.2 FILTER FABRIC OF PIPE = 94.17 BOTTOM OF TRENCH = 87.15 Wrl.ff"lt.)•i GARNESS ENGINEERING GROUP, Ltd ----- -- ENGINE RIN o SA Ro f)NG I TING c---- --- - 3701 E. TUDOR ROAD, SUITE 101 • ANCHORAGE, AK 99507 - PHONE (907) 337-6179' FAX (907) 338-3246 • WEBSITE: www.gamessengineering.com PREPARED FOR: PHONE NUMBER: PAGE NUMBER: JEFF BOOL 907-317-3799 3 OF 3 PROJECT/LEGAL DESCRIPTION: DRAWN BY: CREEKVIEW; LOT 4 D.J.G. TYPE OF WORK: DATE: �, SEPTIC SYSTEM PROFILE RECORD DRAWING 11/5/2019 UNDISTURBED GRADE ADJACENT TO TRENCH = 95.41 0 ........... 0 .► :. 1 ... ....... 0 f Je I'e . Games : W E_ = Zi 1-ICENSE,I11TA"k"** • #AECC884 GARNESS ENGINEERRNG GROUP, Ltd 3701 E. TUDOR ROAD, SUITE 101 • ANCHORAGE, AK 99507 • PHONE (907) 3376179 -FAX (907)338-3246* WEBSITE: -gamessengineenng.00m SOIL LOG - PERCOLATION TEST LEGAL DESCRIPTION: CREEKVIEW ESTATES; LOT PERFORMED FOR: JEFF BOOL DATE: 5/31/2019 DEPTH (feet) TEST HOLE #2 1 ORG SOIL CLASSIFICATIONS 2 GW ORG GP r «; GP ML 3 rY a GM CL 4 GC OL 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 IIel1'11 WON R1111111 IV""" DEPTH TO DATE GROUNDWATER (WEEP) 19.5' 5/31/2019 16.92 6/7/2019 I SITE PLAN DATE READING CLOCK NET TIME WATER LEVEL NET DROP TIME (MINUTES) READING (INCHES) SEE ATTACHED LETTER REGARDING TRENCH INSTALLATION AND RECORD DRAWINGS PERCOLATION RATE - (MIN./INCH) PERC. HOLE DIA. - (INCHES) TEST RUN BETWEEN - FT. AND - FT. A FOUR HOUR PRESOAK WAS PERFORMED: ❑ YES NO B.O.H. SOILS LOGGED BY: DAVID GARNESS C'nMMFNTS,: PERCOLATION READINGS ARE WITHIN 1/16 OF INCH. PERFORMED BY GEG, Ltd. I, JEFFREY A. GARNESS, CERTIFY THAT THIS WASP RFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE: of u GARNESS ENGINEERING GROUP, Ltd y - -x--,-,--,-- ENGINEERING -SALES -CONSULTING �. November 411, 2019 Municipality of Anchorage Development Service Department On -Site Water & Wastewater Program 4700 Elmore Road Anchorage, AK 99507 Ref: Septic System Installation Creekview; Lot 4 To whom it may concern: During GEG inspections of the subject installation, there were several items that did not meet MOA onsite code. They are as follows: 1. A pre -construction layout did not take place with the contractor and Garness Engineering Group, Ltd. 2. The testhole monitoring tube pipe was damaged during the foundation excavation and non-functional for its purpose. It did not extend to the required depth and therefore could not be used for groundwater monitoring 3. The new trench does not run parallel with the slope contours. 4. Upon our arrival the trench was over excavated (approximately 12.92 feet deep) on the uphill side. 5. Most of the trench was installed outside the 30 -foot radius of T.H.#1 6. The trench appeared to be in the surface water setback (100' setback was not flagged). Per conversations with the owner on 5/29/2019, a surveyor went onsite after inspection and confirmed that the trench was in the surface water setbacks. The contractor then decommissioned (reportedly by removing the drainrock) and "moved" the trench outset the 100' setback without GEG concurrence or inspections. 7. Per the owner, the abandoned portion of the trench (which encroached on surface waters) was backfilled with native material. The excavated drainrock was then used in the "new portion" of the trench. It is unknown how "clean" the drainrock was prior to being "reused". Also, it is unknown how the excavation and backfilling of the decommissioned portion effected the remaining portion of the drainfield. 8. Based upon item #4 and item #5, a new testhole was excavated to confirm the separation distance to groundwater. See the attached soil log with groundwater monitoring. Please see the attached soil log for T.H.#2 which shows soil classifications and groundwater monitoring. Also, see attached profile drawing which shows the trench profile and separation distance to groundwater. In addition, Garness Engineering employee David Garness, P.E. met with Deb Wokenfuss at the MOA onsite department regarding the percolation test for the trench portion that extends outside the testhole radius. Per MOA records, the percolation rate for Creekview Estates; Lot 3 (T.H.#2) was 17min/inch (to the east of our client's lot). Per MOA records, the lot to the west Creekview Estates; Lot 5, the soils percolated at <1 min/inch. In addition, a portion of the drainfield is located within our initial percolation test of <1 min/inch and 3701 East Tudor Road, Suite 101 * Anchorage, Alaska 99507-1259 Phone: (907) 337-6179 * Fax: (907) 338-3246 * Website: www.garnessengineering.com Page 2 of 2 10.4 min/inch. In short, it is reasonable to believe that the soil around the trench has a similar percolation rate to our initial testhole. It should be noted that MOA onsite employee Tim Ecklund was onsite for the initial bottom of trench inspection and agreed with GEG assessment of the soil classification/s. In short, based upon these facts, an additional percolation test was not performed, and it is reasonable to believe the drainfield is not undersized for a 3 -bedroom home. Groundwater Monitoring: Testhole (TH#2) was excavated to a depth of 20.5 feet to confirm separation distance to groundwater/impermeable soils. The trench was excavated approximately 12.92' below the existing grade (including fill above original grade (OG)). As stated previously, the initial trench location was not encompassed by the 30' radius (prior to being moved by the owner and contractor). After the seven days groundwater was 16.92' below grade at T.H42. Elevation shots were taken at the testhole and the groundwater elevation was found to be 81.8 at the testhole. It should be noted that natural topography was sloping towards the drainfield. In theory, groundwater would be lower in elevation at the drainfield. In short, the elevation of the bottom of trench appears to meet the MOA requirement for separation to 3701 East Tudor Road, Suite 101 * Anchorage, Alaska 99507-1259 Phone: (907) 337-6179 * Fax: (907) 338-3246 * Website: www. garnessengineering.com Ferradt NnmaiheraaD 036 Dzte of Imues Parwil Ideaimflon Humbwg 017-161-12 ®� Bate r¢ec�: - Date cCo�ala4 : 4- 4_„_09 Is well located at approved permit lo€�tion? ® le 0 NO IID rlp�imma Rexview. Tonace Tract 13 -Lot 4 YMperty OvC--ear Name & Addams: Jeff ftnart G re l—, Ween Czfal-e y Lcs l 18 enhole DOD.- 2iD©FQh 00 Soil Type, T Ackness & water Strata From TO stick-up 0 18" organicsAsilt fair 3 gravelly sift 3 6 cobbly gravelly 8 33 water Saud & gravel 33 37 gravelly silt 37 43 water sand & graved 4 qpm 43 45 cobbly gravelly silt 46 63 water sand & gravel 63 66 WATER TESTING- - Collform VOLIALITY COU100ML lAtretes MgIL Arsenic D I'"AotbOd ®f IlDHIMR9 ® air rotary [3cable tool Casing type; geel Wall Thickness: Q25 inches Diameter: C aches . Deptli: 6„ 4 feet ILine r Type: _ . Diameter: , inches Depth: _ felt CasnnF'stEeWp above end: 182feet - . ftfic water >ievel.(from ground level): g8 feet Pumping level: 66 feet after 2 hours pumping.9 gpm Recovery Rate: A gpm etfbodof'lTenfing: ail' Well Entake opening T"ea ® Open End ❑ Open Hole ❑ Screened Start. feet •Stopped feet ❑ Perforations Start, feet Stopped f®et Groat 'like: bgntoilite anuks Volume: Depth: Start ft feet Stopped ? fest Damp: Intake Depth feet Pep S1z.e.-,4P Brand Name, Well DWiffected Upon Completion? M yes C] j30 Method of Disinfeetion: chlorine tablats Comments: WeDD Driller: Alpine Drilling & Enterprises P.O. Box 910496 Anchorage, •gK 0,951,1- .0496 Attention: The well driller shall provide a well log to the property owner within 34 days of completion and the property owner or the well driller shall provide a well log to the 0evelopment Services Department within 6G days of completion. Jul 1 P. 1: C,2: 19c ^,r,C;j rage 44`eli � Putnli SS_r ^0724.::-0'42 P. L)E!vel)opment Services bep artment � - Bolding Safety Division K}e 4700 Elmore ;Z3od _ • P.U. Box 15665L _.._..- �,S�,t'kJ'agJCi; r1t1eRQ?'LtJO,: AV x}9501 Ma for avt4iti.mur s,orn/cns i he Pump Installation Lo i tffi Drilling Permit Numbar.: ` -_05P131 :3 5 Z ;date of lssu(;: _ 10 08 1 f g F,areel Awatificatioaa N iuwbLx: 0 l�agai nescriptio3t �__ it Praperty Owner Nfame & Address. C�e k � I e -U-) es+aju I --- I'nnm Insw1ladon ;Urate: Pump .atake Depth rselu,<,e `l'ap cif• a„•eil Casirgy: ,�,,�, feet _�'�rx-rI4fazta3f>�eYurar's dare:' IP�e.a ava.saalC�3 Purr,n Size Z. hp Pitless _'i.r aprer Rurit►: b pth. t Z ful Pidess ? dapt-er "Onnuiiacturer's ' srne: Pide s Adapter Installer: i'l P -C tC- :: , u_:tZ” Weii Disinfected Upon Completion? .>7"Ves Y� No Method of Disir faction: Comments: Pump Installer Naane: � t■`F)�{',' �j�}'.,.py/� , J ( +e( f1 � j1 ( J ((t +/fir (%f, j t�A •'—� � t[�f+${/]'�}L�/ \�/'� � ;,.,/ ��,� V� C•.✓ 'J � Lr'�r ti.�Y��• f 1J i 'Utention: 1'115—,L ii`<,`.,jic'2' :1i1:� pravkr ; ;t p1' --C, .iLkaflation lag to fht D3D -within N days ol" Purnri ;21SCi3! F1Y1_r: ED C: rp Z) (1) co 0 rn arnmy� S2 I rJ rn rn may, co rn ED C) ��z m w c/) All co �-j rn m cz i rn r O i1 co �E o-, � - w Cyl 0- p rn mm rn0 G ro Z m rn C,) coo 0 G) 0 co 0 VA U) 30'00'00"E 419.05! C/) (31 CD rn co -n 0 QI C) -n 0 r1i . ........ 01 ED Q) Z) D 0 rn M CO ni u G) —i ril Q co (D 02 C) z 0 CIO n) -n ,n C) b S a g� i: a, 0 rTl Z, r ': -.)3 cr. ct) CD c co raM co r- 7J CD S2 C) P CD 0 c CD s W -n 0-1 CIO C)0- 70 Lq 0 0 C) m(D (D C) C........ "Ilk SOTUOTE 476.0,1 CD 0 ,czw Lp 0 &�;e In A co On _-F CD 0) CL (D .4 0 rn :- %�im ;Maw N'ct"AAL r. MUNICIPALITY OF ANCHORAGE y mens 4.4m.,., On-Site Water&Wastewater Program �o S^� PO Box 196650 4700 Elmore Road �. Anchorage,Alaska 99519-6650 Phone:(907)343-7904 Fax:(907)343-7997 ihttp://www.muni.org/onsite 4NcMOa AGE On-Site Wastewater Disposal System Permit Permit Number: OSP181352 Effective Date: 10/8/2018 Work Type: Septic Initial Expiration Date: 10/8/2019 Tax Code Number: 01716121000 Site Legal Address: CREEKVIEW ESTATES LT 4 G:3138 Site Mailing Address: Owner: BOOL JEFFREY JAY Lot Size in Sq Ft: 97254 Design Engineer: GARNESS ENGINEERING GROUP LTD Total Bedrooms: 3 This permit is for the construction of: 0 Disposal Field 2 Septic Tank ❑ Holding Tank ❑ Privy 0 Private Well 0 Water Storage All construction shall be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80) 3. The wastewater code requires inspections during the installation. The engineer shall notify the Development Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather shall be either: a. Opened and Closed on the same day, or b. Covered, sealed, and heated to prevent freezing N, - Received By: /,9-- Date: /6 £ (- Issued Issued By: 4,9,, / / _ Date: Al7g MUNICIPALITY OF ANCHORA . � � 56789,0 Or r ! Community Development Department �. Phone-t 87-343-79041 Development Services Fax: 90'- 343-7997 ' On-Site Water & Wastewater Program s 1,V Mayor Dan Sullivan 8 L 9 9 n On-Site Sewer/Well Permit Application For A Single Family Dwelling Parcel I.D. 017-161-21 Property owner(s) JEFF BOOL Day phone 907-317-3799 Mailing address NHN RABBIT CREEK ROAD'ANCHORAGE,AK 99516 Site address NHN RABBIT CREEK ROAD'ANCHORAGE,AK 99516 Legal description (Sub'd, Block & Lot) CREEKVIEW ESTATES, LOT 4 Legal description (Township. Section & Range) Lot Size Sq.Ft. Number of Bedrooms 3 APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DEWELLING: (®all that apply) Initial ® Single Family (SF) Absorption Field ® (w/wo ADU) Septic Tank ® Upgrade 111 Duplex (D) ❑ Renewal ❑ Holding Tank ❑ Multiple Dwellings I I Privy ❑ (SF and/or D) Private Well ❑ Water Storage I 1 THIS APPLICATION INCLUDES A VARIANCE/WAIVER REQUEST FOR: N/A Distance: - I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal codes. GARNESS ENGINEERING GROUP, Ltd. (Signature of property owner or authorized agent) Permit/Rush Fees: 51464 Waiver Fees: Date of Payment: /0/3/1? Date of Payment: Receipt Number: a532,6 Receipt Number: Permit No. 0S P 7i36-g Waiver No. (Rev.01/11) al A eummiles GARNESS ENGINEERING GROUP, Ltd Advanced T' v7rs » ENGINEERING SALES CONSULTING Dealer August 10th 2018 Municipality of Anchorage Development Service Department On-Site Water&Wastewater Program 4700 Elmore Road Anchorage, AK 99507 Ref: Proposed Septic System for Creekview; Lot 4 To whom it may concern: The subject lot is vacant with an existing well. Per conversations with the owner, he would like to construct a 3-bedroom home and septic system. We are proposing to install a new 1000-gallon HDPE septic tank and deep trench type drainfield. One testhole was excavated on the property and the drainfield is designed around its 30-foot radius. Comments regarding the design are summarized as follows: 1. SOILS: See the attached 2018 soil log which shows soil classification, percolation test, and groundwater monitoring. As can be seen on the attached soil log there is a GP material that perked faster than 1 min/inch from 0.5 feet to 5.5-6.0 feet. We are proposing that a sand filter not be utilized since there is a GM to SM material that perked at 10.4 minutes/inch below that layer. In short, the underlying soil profile will prevent effluent from entering the groundwater table at an accelerated rate. Additionally, the proposed trench will span both soil layers with approximately 4.5-5 feet of the effective depth being in the GM to SM layer and 2.5-2 feet in the GP layer. It should also be noted that as the soil was being excavated, it was "harder digging" with depth. We are proposing an average application rating of 0.7 gpd/ft2. Comments regarding the design are as follows: 2. DRAINFIELD DESIGN: See attached design drawing for drainfield specifications. 3. SURFACE WATERS: There is a creek to the south, however, it was professionally surveyed in and the proposed drainfield is greater than 100 feet from its location. 4. TOPOGRAPHY: See attached 100 scale with topography information. We are unaware of any adverse impacts this installation would have on adjacent wells or septic systems. If you have any q :stions, please contact us at 337-6179. Thank you for your assistance. S'. erely, - e •. - ess, P. . M.S. Presi•/ n 3701 East Tudor Road,Suite 101 *Anchorage,Alaska 99507-1259 Phone: (907)337-6179*Fax: (907)338-3246*Website: www.garnessengineering.com / / / ...\ REXVIEW TERRACE;TRACT A VACANT R0 BB1 C°4-V.414.- ,/ '00,44z,. Rp, I \\ } ...' 14 CREEKVIEW ESTATES;LOT 5 / \%amift, \ / , ..+^,h'?:. \ \\\. _ Memo ''}----- •r +.."....... \ ......:, :;':.42.....•..4 'at CREEKVIEW , \ '; \` \\\\ '; ESTATES;LOT 3 \ , i I I \ / / \•-8:5:CREEKS /Ns )k \\�. E►BACK \\ f\\\ /�� �i 30• \v �- - - — \\\ i �aEENeELr N \\/ / 2S PRoreC710N / S ALE' /\ // CREEK CENrER 4NE _// I 1' = 100' N/ .4�%\\\1111 m ♦A r OF 4 ax ,1 j • ��11 GARNESS ENGINEERING GROUP, Ltd ' 91;• . 1 • ENGINEERING SAL ES-CCNSLII TING 0 / • 3701 E.TUDOR ROAD,SUITE 101■NOWAK.AK 99007■ OE(907)337-6179■FAX(907)339-3246■VEBSITE.iv,asrr.ss.r tiw •ti . pcon . .. .. •.1 IC • ■ PREPARED FOR' PHONE NUMBER' PAGE NUMBER' ♦t^ - - •. Ga ss '4i• JEFF BOOL I 907-317-3799 1 OF 2 •.J,. E- •• '_� PROJECT/LEGAL DESCRIPTION' DRAWN BY' #. ., •. V 1 O I�'• CREEKVIEW ESTATES; LOT 4 D.J.G. 1� ♦. .. . .• 'P\, �• TYPE OF WORK' DATE' LICENSE,%111"`S 44 SEPTIC SYSTEM DESIGN 8/10/2018 LICENSE J DESIGN CRITERIA:11 GEG,Ltd.HAS A 8 PAGE SPECIFICATION NUMBER OF BEDROOMS:3 LETTER THAT PERTAINS TO THIS DESIGN.TO GALLONS PER DAY(GPD):450 \ OBTAIN A COPY OF THE LETTER CONTACT NOTE:THE CONTRACTOR SHALL HAVE THE PERCOLATION RATE/S:<1&10.4 MIN/INCH GEG.BY PROCEEDING FORWARD WITH THIS EAST LOT LINE AND ALL PERTINENT WELL PROPOSED APPLICATION RATE:'0.8 GPD/FT' INSTALLATION,THE ENGINEER,WELL DRILLER, RADAII FLAGGED BY A REGISTERED LAND MINIMUM DRAINFIELD SQ.FT.:562.5 FT' CONTRACTOR AND PROPERTY OWNER AGREE 'SEE ATTACHED DESIGN LETTER REGARDING THE THAT THEY HAVE READ THESE SURVEYOR PRIOR TO CONSTRUCTION PROPOSED APPLICATION RATING • SPECIFICATIONS AND AGREE TO ACCEPT THE DRAINFIELD DESIGN: TERMS AND CONDITIONS OUTLINED. MAXIMUM DEPTH:10 FEET WIDTH:2.5 FEET ;Fti' ••''y ••••' •• '..t ,. LENGTH:46 FEET t, EFFECTIVE:7 FEET . ACTUAL SQ.FT.:644 FT' } •4' .I• : SEPTIC RESERVE DESIGN CRITERIA: NUMBER OF BEDROOMS:3 4'...I.••+: ••:,•. GALLONS PER DAY(GPD):450 w••� • DRIVEWAY r:..: PERCOLATION RATE/S:<1 MIN/INCH PROPOSED APPLICATION RATE:'6.0 GPD/FT' . ' ••'''*.'• I.iw`l;:'.:%! MINIMUM DRAINFIELD SQ.FT.:75 FT' •-•' 'CAT III ADVANCED TREATMENT _ •/.• • :•- INSTALL FCO DRAINFIELD RESERVE DESIGN: �''•' '• `' MAXIMUM DEPTH:3 FEET / I PROPOSED 1000 HDPE SEPTIC TANK; LENGTH:15 FEET INSTALL DOUBLE CLEANOUTS BEFORE WIDTH:5 FEET PROPOSED 3 AND AFTER TANK.IF BURIAL DEPTH EFFECTIVE:0.5 FEET BEDROOM HOUSE ' DOES NOT ALLOW,A 1000 GALLON 1 ACTUAL SQ.FT.:75 FT' STEEL SEPTIC TANK WILL BE INSTALLED \ % DECK j RES I RVE SITE;CAT III \ T.H.#1 r••••... �` / COQ M� �:J ' ''. \, PROPOSED DRAINFIELD 1 T \ 1y1 / 100'CREEK SETBACK 0 \ ` I SEE ATTACHED PLOT PLAN BY CLINTON T.LANCASTER,PLS WHICH SHOWS SLOPE CONTOURS / 1 / / \--. _ / ---. , SALE: I 1 1"=40' '' �4•• •` ' 11 4444c 4114 �� GARNESS ENGINEERING GROUP, Ltd • '9 I' _ Iiii 'E NEEB G tef�� C �J � •, 3701 E.TUDOR ROAD,SUITE 101`ANCH E,AK 9950 HON�(907)39179' 75 �RSRE:www.g9TeuengNMafng.Can �Q • PREPARED FOR: PHONE NUMBER: PAGE NUMBER: 0 fn; J- `�y A. - .14-i a JEFF BOOL 907-317-3799 2 OF 2 0��.- . I -79 3 , : s. 4/ PROJECT/LEGAL DESCRIPTION: DRAWN BY: •,.� •• ' .. <c7 CREEKVIEW ESTATE; LOT 4 D.J.G. �1 ♦ �''' �o "�,�. TYPE OF WORK: DATE: ,41PROF_ L )\as SEPTIC SYSTEM DESIGN 8/10/2018 #AECC884 � \\u\\ 4 GARNESS ENGINEERING GROUP, Ltd' ; 410 "ri I I .4' OF 4 / *. ;7 l , A� • * ♦♦ ENGINEERING GROUP, Ltd 9 " GARNESS ���, ///+++ '�yI E��Jp�� /v� �/y�EcJ � • 3/01 E SURE 101•ANCHOR 59SOi'PHOh ,90i)3P61/9'FL(190/ +k W G rn ,,,...r, •• • ♦g': re re.•• Garne SOIL LOG - PERCOLATION TEST ♦ 0 . / ♦ /1)798 LEGAL DESCRIPTION: CREEKVIEW ESTATES.LOT4 •A%-y. -447 � *<<,0** ............. . /! •���'�.PERFORMED FOR: JEFF BOOL DATE: 6/20/2018 •♦ ?RE ��1(y�1p`44 � DEPTH (feet) '� -.72.:::= TEST HOLE #1 - LOWER BENCH .. SOIL CLASSIFICATIONS SITE PLAN 2 —.z,.:4;:,-, :d,=''o' GW �.. ORG 3--4.1:1 •" •` .:«•- GP ML ` , GM J CL `� i7J GP WITH LARGE GC ��' OL P� 4Z..--i ,!..=,a BOULDERS =`_.,;^ .. 000000 Q .,a: Q•a Rt. SW MH Lo- 5 �3. t • SM ' /rt ,� OH Q , P • i .7 . • GR UNDWATGER DATE A' N 5 8 • • ! GM TO SM DRY 6/20/2018 • • DRY 6/27/2018 SCALE: 9 —/ i°=lop. • • • • • • 10 - • • • DATE READING CLOCK NET TIME WATER LEVEL NET DROP 11 TIME (MINUTES) READING (INCHES) • • • 12 —t • • • 6/21/2018 1 3:45 - 6" - • ' • 2 4:15 30 3-1/8" 2-7/8" • , • 13 3 4:15 6" 4 4:45 30 3-1/8" 2-7/8" • • • 14 5 4:45 - 6" • • Re 6 5:15 30 3-1/8" 2-7/8" 15 • • M 16 E3.C).f I. 17 18 ...---'"------- PERCOLATION PERCOLATION RATE 10.4 (MIN./INCH) PERC. HOLE DIA. 6 (INCHES) 19 TEST RUN BETWEEN 6.5 FT. AND 7.5 FT. 20 A FOUR HOUR PRESOAK WAS PERFORMED: • YES E NO SOILS LOGGED BY: JODY MAUS PERCOLATION TEST PERFORMED BY: ERIK WIDGER COMMENTS: PERCOLATION READINGS ARE WITHIN 1/16 OF INCH. PERFORMED BY GEG, Ltd. I, JEFFREY A. GARNESS, CERTIFY THAT THIS WAS PET() ED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE: '? /3/8 ALPINE DRILLING & ENTERPRISES Permit Number: #SW090036 DateofIssue: 4-21-09 Date Started: 4-23-09 Date Completed: 4-24-09 Legal Description: Property Owner Name & Address: Borehole Data: Soil Type, Thickness & Water Strata stick-up organics & silt gravelly silt cobbly gravelly water sand & gravel gravelly silt water sand & gravel 4 gpm cobbly gravelly silt water sand & gravel Parcel Identification Number: 017-161-~2 is well located at approved permit location? [] Yes- [] No Rexview Terrace Tract B Lot 4. JeffRegnart ) Cr~, [/,'e~ ~4r~-e~ L,~- ~ ~'- Anchorage, Alaska 99516 Depth (ft) Method of Drilling [] air rotary [] cable tool From To Casing type: steel 0 18" Wall Thickness:. 025 inches 18" 3 Diameter: _O i~ches Depth: 66 feet 3 8 Liner Type: ,, 8 33 Diameter: ~ inches Depth: ~ feet Casing stickup above ground: 18" feet 33 37 Static water level (from ground level): 28feet 37 43 Pumping level: 66 feet at, er 43 45 _2 hours pumping _5 gpm 45 63 Recovery Rate: _5 gpm 63 66 Method of Testing: air lift Well Intake Opening Type: [] Open End [] Open Hole [] Screened Start feet Stopped feet [] Perforations Start ~ feet Stopped feet Grout Type: bentonite granules Volume: £ bgs Depth: Start _0 feet Stopped ? feet Pump: Intake Depth feet Pump size , hp Brand Name __ Well Disinfected Upon Completion? [] Yes [] No Method of Disinfection: chlorine tablets Comments: Well Driller: Alpine Drilling & Enterprises P.O. Box 1~0496 Anchorage, AK.995~-0496 Attention: The well driller shall provide a well log to the property owner within 30 days of completion and the property owner or the well driller shall provide a well log to the Development Services Department within 60 days of completion. MUNICIPALITY OF ANCHORA GE Deve/opment Services Department On-Site Water & Wastewater Program 4700 South Bragaw Street P,O, Box 196650, Anchorage, AK 99519-6650 (907) 343-7904 ON-SITE WASTEWATER DISPOSAL SYSTEM PERMIT Initial Date Issued: Apr 21, 2009 Expiration Date: Apr 21, 2010 Permit Number: SW090036 Legal Description: REXVIEW TERRACE TR B Design Engineer: 0855 GARNESS ENGINEERING GROUF Owner Name: JEFF REGNART Owner Address: 5820 RABBIT CREEK RD ANCHORAGE, AK 99516-4342 ParcellD: 017-161-12 Site Address: 005820 RABBIT CREEK RD Lot Size: 1159567 SQ. FT. Total Bedrooms: 0 Permit Bedrooms: 0 This permit is for the construction of: [] Disposal Field [] Septic Tank [] Holding Tank [] Privy [] Private Well [] Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations ( 18AAC72 ) and Drinking Water Regulations ( 18AAC80 ). 3. The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 ( 24 hours ). ( Not required for a Water Supply Permit only ). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must be either: A. Open and closed on the same day. B. Covered, sealed, and heated to prevent freezing. 5. The following special provisions. LOT 4 (PROPOSED~ THIS PERMIT IS FOR AN EXPLORATORYWELL ONLY. THE WELL SHALL NOT BE USED AS A DOMESTIC WATER SOURCE PRIOR TO AN MOA APPROVED SEPTIC SYSTEM BEING CONSTRUCTED ON THE PROPOSED LOT. THE WELL SHALL BE CONSTRUCTED IN ACCORDANCE WITH AMC 15.55.060. Received By:~ J--~ / Issued By: . ,, - Date: ivlunicipality of Anchorage Development Services Department Building Safety Division On-Site Water & Wastewater Program 4700 Bragaw St. P.O. Box 196650 Anchorage, AK 99519-6650 www.ci.anchorage.ak, us (907) 343-7904 ON-SITE SEWER/WELL PERHIT APPLIOATION FOR A SINGLE FAHILY DWELLING Parcel I.D. Ol?'l~l'l"~ Property owner(s) JEFF REGNART Day phone 240-8978 Mailing address 15131 OXFORD BLUFF CIRCLE * ANCHORAGE. AK Site address Zip Code 99515 Legal description (Sub'd, Block& Lot) REXVIEW TERRACE: TRACT B (PROPOSED CREEK VIEW EST.. Legal description (Township, Section & Range) LotSize l? I.ER¢5'~'7 Sq. Ft. N/A Number of Bedrooms N/A THIS APPLICATION IS FOR ( E~]all that apply): THIS APPLICATION IS AN: Absorption Field [] Initial * [] Septic Tank [] Upgrade [] Holding Tank [] Renewal [] Privy [] Private Well [] *NOTE: THIS IS FOR AN Water Storage [] EXPLORATORY WELL PERMIT FOR SUBDIVISION PURPOSE ONLY. t certify that the above information is correct. I further certify that this application is being made for a Single Family Dwelling and is in accordance with applicable Municipal codes. GARNESS ENGINEERING GROUP, Ltd. Permit/Rush Fees:'~ Receipt Number: (Rev. 11/05) Waiver FeesL Date of Payment: Receipt Number: GARNESS ENGINEERING GROUP, Ltd. Apfil15,2009 Municipahty of Anchorage Development Service Department On-Site Water & Wastewater Program 4700 Elmore Road P.O. Box 196650, Anchorage, Ak 99519-6650 (907) 343-7904 Attention: Dan Roth Ref: Exploratory Well Permits for a new subdivision to be known as Creek View Estates (subdivision of Tract B, Rexview Terrace S/D) Mr. Roth: We have been h/red by Mr. Jeff Regnart, the developer of this subdivision, to obtain exploratory well permits and perform an aquifer study for the purpose subdividing the referenced property. Attached is a site map that shows the majority of the subdivision with the proposed well and septic sites. There is an existing well located on proposed lot 6. We are proposing that two additional wells be drilled and a well drawdown test be completed using these three wells. We are proposing the well located on Lot 6 be inspected and documented. If the well is found to not meet MOA well ordinance requirements, we would propose a new well be drilled next to this one and the existing well be abandoned per MOA code. We are proposing a well be drilled on Lot 5 approximately 200 feet northeast of the well on Lot 6. We are also proposing that a th/rd well be drilled on Lot 4 which is approximately 140 feet nm~da/northeast of the well on Lot 5. We will require all wells to be surveyed and staked prior to drilling to insure proper separation distances to the proposed platted reserve sites. These well locations were chosen for the accessibility for a well rig. All other lots would require extensive grading and driveways to be installed in order to drill wells on any other lots. We request three exploratory well permits be issued for the purpose of perform'mg an aquifer test (see attached permit applications). We are unaware of any adverse impacts this installation would have on adjacent wells or septic systems. If you have any q~e~s~tions, please contact us at 337-6179. Thank you for your assistance. Sincerely,,, .,.' Jeffrez;A; ~e~,E. M.S. Presid}nt 3701 E. Tudor Road, Suite 101 * Anchorage, AK 99507-1259 Ph: (907) 337-6179 * Fax: (907) 338-3246 * Website: www.gamessengineering.¢om