HomeMy WebLinkAboutPARK HILLS RIDGE Lots 1, 2, 3 & 4 Plat# 94-162 S-9553 ANDERSON ENGINEERING P.O. BOX 240773 ANCHORAGE, ALASKA 99524 September 21, 1994 Municipality of Anchorage Department of Heath & Human Services 825 "L" Street Anchorage, AK 99502-0650 Attention: Jim Cross Subject: Park Ridge Hills Subdivision Surface Water Site Plan Dear Jim: On September 17th and 18th, we conducted a surface water study on Park Ridge Hills Subdivision. All areas where surface water was found are noted on the attached site plan. We noted that many areas which were wet earlier in the year are now dry. This may be due to the grading and drainage work completed by the owner of the property in August. Substantial grading will be required during development of the lots for driveways and homesites. At that time remaining drainage problems will be addressed. In addition, during construction of the septic systems for each lot any remaining problems with surface water will be taken care of. We hereby request your consent to allow this subdivision to proceed. Sincerely, Michael E. Anderson, P.E. September 2, 1994 James Cross Department of Health & Human Services 825 L Street Anchorage, Alaska RE: Park Hills Ridge Dear Mr. Cross, We have constructed a drainage system and improved the ditch all along the frontage of lot 1 and lot 2. In addition, we installed a drainage system up along the boundary between lot 1 and lot 2 a distance of about 200 feet. We installed a 2' by 2' 4" to 6" rock drainage system. This, along with improved grading along the ditches, has greatly improved the drainage of the area. There is no standing water within 100' of the proposed septic sites on all of the proposed lots, I through 4. I hope that this will satisfy your requirements and allow you to sign off on the plat. We created this subdivision with very large lots, and each lot has an excellent building site and suitable septic sites. Thank you for your consideration in this matter. Thankyou, Thomas H. Dreyer, P.LS. ANDERSON ENGINEERING P.O. BOX 240773 ANCHORAGE, ALASKA 99524 June 12, 1994 Municipality of Anchorage Department Of Heath & Human Services 825 "L" Street Anchorage, AK 99502-0650 Attention: Jim Cross Subject: Park Ridge Hills Subdivision Septic System and Well Placement RECEIVED JUN lj 3 1994 ~40~t~lity of Anchorage ~, H~alth & Human Services Dear Jim: Attached is the final groundwater monitoring information along with the locations of the septic systems and wells proposed for each lot of the Park Ridge Hills Subdivision. We have chosen to designate three areas for septic systems for each lot rather than to reserve a large area for system development. These systems were designed for three bedroom homes. We request, however, that a note be placed on the plat stating that if additional engineering information is provided, four bedroom homes may be constructed. We also understand that the septic system and well locations may be changed if additional engineering information is provided prior to obtaining the septic system permit which indicates more suitable sites are available. There is little development surrounding this subdivision. Two lots immediately south have been developed and the well information from these lots is attached. In addition, Forest Ridge Subdivision to the east has been recently developed. Well logs from lots in this subdivision are also attached. From information obtained during the field exploration phase of this subdivision and from the attached well logs it is logical to assume that sufficient potable water is available at reasonable depths to serve the requirements of the houses proposed for this subdivision. Hopefully, the attached information will satisfy the final requirements leading to the subdivision of this parcel. We, hereby, request a letter of nonobjection to this subdivision. Sincerely, Michael E. Anderson, P.E. xc: LanTech, Inc. Park Hills Ridge Subdivision Groundwater Readings Testhole No. 2/14/94 5/30/94 I 0/2/93 lA 5' 5' 8' 3 6.25' 4' 4.5' 4 16.2' 13' Dry 5 10' 9.5' Dry 6 Dry 11.2' Dry 7 Dry Dry 1 0' 8 13.6 9.9 7' 9 10.33' 7' 14' 10 10' 7' 12' 11 6.3' 6' 11' 12 8' 6' 13.5' 1 5 6.25' 6' 11 ' 16 15' 10.5' Dry 17 16.4' 11.5' Dry 1 8 Dry 8' N/A 1 9 Dry 1 ' N/A Comments Lot 4 System Lot 4 System Lot 3 System Lot 1 System Not Used Not Used Not Used Lot 2 System Lot 2 System Lot 2 System Lot 1 System Lot 1 System Not Used Lot 3 System Lot 3 System Not Used 1 Dry Lot 4 System ?tue of RL~A~ST FO~ APPROVAL OP I'M)TVXDUAL b'*~J~R & RAI~R FACI~L,/TIE~ FOR 1, Aoprovel Requested 6ys Leqml Ikecrtptiont Locations Typo o~ Foctlity to 'be Inspect.edt Wall Dstot &~ Tankt" 1, D.'. Seepage Pitt 1. ::i'~ DispO881 Field= Totel. bflgth of Lines ~,~ Well Tot Septic Tank -~ ' , Absorption Area ' Tko~st Lot Line ~ , Other Cont~utflsttou, A~o~ttm A~e to ~lmlt Lot Lt~ .WELL CERTIFICATION &~um~ test was conducted 'for Northridge Construction, at Lot 2, Block O, Fairmont Subdivision In Anchorage,-~.:', Alas~.' The results are as iolAows: Casing diameter: 6" ... S~tic.,Level: "1,~' ' ' · , , .: ...... ~ ~ %° Well ~as ~_~ed at t5 gallone ~er mlnute fOr ~ .1 ~. ~nu~es. Reduced ra~e to 6 gallons $,er minute for ]0 minutes at a ~ing level [)]'.~. Reduced 'rate to.~ g~llo~ ~e~,~lnute for ~.~ ~ .:'/.. hours mt' a ~~ ~evel oi D~'. ' .~. ~-~. '.~ A~I~ DRIVING ~. ~ ~,.~..,-..'~ ' }.0. ,~x 1.1.~96 ~.. ~, .7/ [; :/ ,..:'/.' ?.? ~,.. : Ancho~Ee, L~tfon (addren of: Township, Raafe, Section. ff known; or dfstance msi,, .... t~el~ & blk. i Forrest Ridge $,, . 141 easing _Ik~pth of Hol- 141 ~eet Card tn ~eet :. ~ ' lev,~! ,l___ft. (abov~~' ~low) land surface. Finish of well (check one) opea etd_( (minute) for 1 hours "2 St~Ickup penetrated, size of material, color and w/cobbles & occasional boulders- ·; 70 ~Vel 135 MUNICIPALITY OF ANCHORAGE MEMORANDUM DATE: TO: March 24, 1994 Departme~nt of Economic'Development and Planning zoning and Platting On-site Services FROM: John Smith, P. E., Program Manager, Department of Health and Human Services ~~ SUBJECT: Amended Comments S-9553: Lots 1, 2, 3, 4 park Hills Ridge Subdivision Some additional information has been provided to support the conclusion that the proposed four lots can be successfully served by on-site water and wastewater dispDSal systems. However, the following information and documentation is required: 1. The availability of sufficient potable groundwater supply must be documented. 2. Wastewater system reserve areas must be delineated for each lot ort three site specific individual wastewater systems must be designed for each lot and the location of each system must be shown on··the final plat~ The engineer must document that the reserve area and/or site specific design locations for the wastewater systems satisfy all ~requirements including slope restrictions, separation to surface water, separation to proposed well sites and adequa'~e vertical separation to groundwater. 3. DHHS will require that all well locations be shown on the final plat. 4. DHHS will require shallow groundwater monitoring through June 1, 1994 to determine seasonal high water at proposed wastewater system locations. JS[ljm Department of Economic Development and Planning March 1, 1994 Page Two S-9551: S-9552: S-9553: S-9554: S-9555: S-9556: Hillside North Subdivision #6 The following items must be addressed prior to final plat approval. 1. The availability of an adequate potable groundwater source must be documented. 2. With all lots having a soil percolation rate faster than 1 min/inch, 2 foot thick sand filters will be required on all on-site wastewater disposal systems. This requirement necessitates that either bed type systems be constructed on slopes not greater than 10% or that 5 foot wide drainfields be installed. The applicant must show adequate reserve areas with slopes not greater than 10% or plat the location of three specifically designed systems for each lot. Hiddenwoods Subdivision No objection. Ail proposed lots will[be served by public water and sewer. Lots 1, 2, 3, 4 Park Hills Ridge Subdivision The proposed four lots will be served by on-site water and wastewater disposal systems. Information provided in support of this plat does not meet preliminary plat submittal requirements as specified by AMC 15.65 and AMC 21.15. There was no information provided that would support the conclusion that these lots can be developed using on-site water and wastewater disposal systems. Lots 1 - 5 Sherwood Estates Subdivision No objection. Ail proposed lots will be served by public sewer and water. Rieman Subdivision No objection. Anchorage Townsite Subdivision No objection. JS/ljm [:'lease check or fill in the following: 1. Comprehensive Plan -- Land Use Classification Residential Commercial Parks/Open Space Transportation Related 2. Comprehensive Plan-- Land Use Intensity Special Study Marginal Land Commercial/Industrial Public Lands/Institutions Dwelling Units per Acre Alpine/Slope Affected Alpine/Slope Affected Industrial Special Study Environmental Factors (if any): a. Wetland ~//'~ ~ 1. Developable ',Y~',:: 2. Conservation /~-'~ 3. Preservation Z~' b. Avalanche /'~'~ c. Floodplain d, Seismic Zone (Harding/Lawson) Please indicate below if any of these events have occurred in the last five years on the property. Rezoning Subdivision Conditional Use Zoning Va.riance Enforcement Action For Building/Land Use Permit For Army Corp of Engineers Permit Case Number Case Number Case Number Case Number E. Legal description for advertising. (-: %:: ' Checklist ~0 Copies of Plat Reduced Copy of Plat (8 1/2 x 1 1) U¢~"Certificate to Plat · ~ Aerial Photo · ' Housing Stock Map , Zoning Map Fee Drainage Plan Topo Map 3 Copies Soils Report 4 Copies Pedestrian Wdkways Landscaping Requirements Waiver ¢ Water: / Sewer: 20-003 Back tReY. 9~92) ' ; Private Wells ,~' Private Septic Community Well Community Sys. Public Utility Public Utility MUNICIPALITY OF ANCHORAGE COMMUNITY PLANNING AND DEVELOPMENT P.O. Box 196650 Anchorage, Alaska 99519-6650 PRELIMINARY PLAT APPLICATION OFFICE USE REC'D BY: Please fill in the information requested below. Print one letter or number per block. 1. Vacation Code 2. Tax Identification No. 3. Street Address ~ I,',~1~1',~1 I Ir-:li'la'l~-:14a' 14~1,,'1 I~l,flx.'l~14~'l I I I I 4. NEW abbreviated legal description (T12N R2W SEC 2 LOT 45 OR SHORT SUB BLK 3 LOTS 34). 5. EXISTING abbreviated legal description (T12N R2W SEC 2 LOT 45 OR SHORT SUB BLK 3 LOTS 34) full legal on back page, 6. Petitioner's Name (Last - First) ,4 i.-/i 5..~'. ~,'.¢../ Address City//'~'~'.'/¢0,;' ./~ Phone, ,(,'g .'~ 7. Petitioner's Representative /. ~t.',.'~14.4 I.:fl;,.'l~-I I I I I I I I I I I I I I C ty//"~/('¢/(~' X/~'~' State 8. Petition Area Acreage l (~., 13. FeeS -..~-''2-~/' '~' 9. Proposed 10. Existing 11, Grid Number Number Lots Number Lots 14. Community Council 12. Zone B. I hereby certify that (I am) (I have been authorized to act for) the owner otthe properly described above and that I desire to subdivide it in conformance with Chapter 21 of the Anchorage Municipal Code of Ordinances. I understand that payment of the basic subdivision fee is nonrefundable and is to cover the costs associated with processing this application, that it does not assure approval of the subdivision. I also understand that additional fees may be assessed if the Municipality's costs to process this application exceed the basic fee. I further understand that assigned hearing dates are tentative and may have to be postponed by Planning Staff, Platting Board, Planning Commission, or the Assembly due to administrative reasons. Date: ';~/'~:'f~Z/~'~"~/ Signature' --//'~,t~.~,? '~ ~. . z//- '~'.%/.~ ,?·,f ,~,'~. ' 7,?/",..,. *Agents must provide written proof of auth6rization. ANDERSON ENGINEERING P.O. BOX 240773 ANCHORAGE, ALASKA 99524 February 28, 1994 LanTech, Inc. 440 W. Benson Anchorage, AK 99503 Attention: Tom Dreyer Subject: Proposed Park Ridge Hills Subdivision Dear Tom: We have completed our field excavation and identified areas which will support onsite septic systems for the proposed Park Ridge Hills Subdivision. These areas were identified based on test holes excavated in September of 1993 and February of 1994 along with field data gathered in the past by Alaska Environmental Control Services, Inc. Groundwater elevations have been continuously monitored since last fall and the septic systems were designed based ou the highest water level noted during this time. Soil conditions in this area are characterized by slow percolation rates and _hig~ groundwater. Neither condition is ideal for an onsite septic system. Our designs are therefore limited to three bedroom homes and are either wide trenches or shallow beds depending on .the elevation of the groundwater in the area of the system. Lot lines should be placed so that a minimum of 3 sites are located on each lot. Evergreen Street which fronts the proposed subdivision was upgraded to Municipal Standards in 1983. A copy of the roadway asZbuilt is included for your use. Please let me know if you have additional questions or comments. Sincerely, Michael E. Anderson, P.E. Attachments Park Ridge Hills Subdivision Site No. 1 DESIGN FACTORS: Three Bedroom Home Pere. Rate: 31. to 60 Min./Inch Application Rate: .45 GPD/SF 3' Drain Rock Under Pipe SYSTEM REQUIREMENTS: Wide Trench System 1,000 Gal. Septic Tank Min. 2' Accepting Soil Red. Factor: .58 3 Bdrms. X 150 GPD / .45 GPD/SF = 1,000 SF 1,000 SF / 5' Wide X .58 Reduction Factor = 116' Total Lateral Length Therefore: Construct a Wide Trench System with Two 58' Laterals. Place 3' of Drain Rock Beneath Distribution Pipe. TYPICAL WIDE TRENCH SYSTEM (No Scale) '~'-," NOTE: Remove all Peat/Organics to Underlying Material. Provide 2" of Direct Burial Insulation or a Minitnum of 3' of Cover over the Trench System. Maintain a Minimum of 4' Separation from the Bottom of the Trench to Groundwater. . !:i::'i:;!..: 'i i MUNICIPALITY OF ANCHORAGE . DEPARTMENT OF HEALTH AND ENVIRONMENTAL PROTECTION "' '825 L, Street, Anchorage, Alaska 99501 264-4720 · SOILS LOG - PERCOLATION TEST '~X~ SOILS LOG PERCOLATION TEST PERFORMED FOR: SLOPE ,aL) 2 3 5 10 L P 12 , IF YES, ATWHAT ~ /~[ E DEPTH? 13 14 17 19 20 DATE PERFORMED: q / /,,..~ I{~L~ SITE PLAN Gross Net Depth to Net Reading Dale Time Time Waler Drop ~$,~ TEST RUN BETWEEN '~,-.-~' . FT AND ~ '~' FT Park Ridge Hills Subdivision Site No. lA DESIGN FACTORS: Three Bedroom Home Pert. Rate: 6 to 15 Min./Inch Application Rate: .5 GPD/SF SYSTEM REQUIREMENTS: Shallow Bed System 1,000 Gal. Septic Tank Min. 2' Accepting Soil 3 Bdrms. X 150 GPD / .5 GPD/SF = 900 SF 900 SF / 18' Wide = 50' Long Therefore: Construct a Shallow Bed System, 50' (Length) X 18' (Wide). Distribution Pipe Placed @ 1' Below Original Ground. .......... i ........... ! ........ ! ........ i ......... i ............ i ........... 1 , ~'~ :,~. ~ . ; ' ~ ' . ' ~ : : . · .......................... : i ............... %,a iL v'-m- ; ' .....i ........... i .......... ; ....... i ......... i ........ i ....... ~ ...... i ....... :: i' 7' '· ~ : - ' :, ' :. ~ TYPICAL SHALLOW BED SYSTEM :' ............ ~"~ NOTE: Remove all Peat/Organics to Underly~ng~S Material, "~ '::' "'.' ~'"' Provide 2" of Direct gurial Insulation or a Uinimu~ of 3' of Cover over the Bed System, Maintain a ~inimum of 4' Separation from the Bottom of the Bed to Groundwater, Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street. Anchorage, AlaSka 99502-0650 SOILS LOG m PERCOLATION TEST PERFORMED FOR: LEGAL DESCRIPTION: Srd/SP ~;: ,~:.. ,,.... ........ u. ....... DATE ' c~-,;:::,:, -- ......... ,: -.:. Township, Range, Section: ; ......~. WAS GROUND WATER ENCOUNTERED? SLOPE SITE PLaN S IF YES, AT WHAT / O DEPTH? //0 p E Moniloring? ~ DaI~ Reading ' Date Gross Net Depth to Net Time Time Water Drop '~ ~ ~00 ZO il" i ~/~'~ · '; " ' ""' PERCOLATION RATE__,]Z' (minutes/inch} PERC HOLE DIAMETER _ · "'"','.: · ".":! ~'~T R,,N ~,~E, z ,/z. ~T,,ND 'i ?Z. FT .-,. '.¢.; ? · .. · .. .....Z'~::j,:,t."(:'".:.:':'-.':'-~',':' .: CORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: __ ' )08 (Rev, 4/85} .-. Park Ridge Hills Subdivision Site No. 3 DESIGN FACTORS: SYSTEM REQUIREMENTS: Three Bedroom Home Perc. Rate: 16 to 30 Min./Inch Application Rate: .4 GPD/SF Shallow Bed System 1,000 Gal. Septic Tank Min. 2' Accepting Soil 3 Bdrms. X 150 GPD / .4 GPD/SF = 1,125 SF 1,125 SF / 24' Wide = 48' Long Therefore: Construct a Shallow Bed System, 48' (Length) X 24' (Wide). Distribution Pipe Placed @ 1' Below Original Ground. NOTE: TYPICAL SHALLOW BED SYSTEM Remove all Material. Provide 2" Minimum of 3' of Cover over the Bed System. Maintain a Minimum of 4' Separation from the Bottom of the Bed to Groundwater. Municipality of Anchorage DEPARTMENT OF HEALTH & H. UMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG-- PERCOLATION TEST DATE PE~ Township, Range. Section: SLOPE IMENTS OP' WAS GROUND WATER ENCOUNTERED? IF YES, AT WHAT DEPTH7 Oeplh to W~ler A~rz.~. ~2._ M0nil~rJng? SITE PLAN Reading Date Gross Net Depth to Net 'i-[me Time Water Drop -'~ / ~ I/~-'~; ¥o ~ <'3 '/z * ~ ~?:~ ~ q ¢~" ~/~,, · :" Z7 '" ' "~" PERCOLATION RATE (minutes/inch} PERC HOLE DIAMETER . .... TEST RUN BETWEEN __ FTAND . F'r J'ORMED BY' 4-" ,'~/4-}~*~'/-~ ~'~ 7'"-'~'/uZ'~4z. ,' (-~~TIFY THAT ~HIS TEST WAS P~FORMED I. Municipality of Anchorage DEPARTMENT OF HEALTH & H,?MAN SERVICES 825 '%" Street, Anchorage, Alaska 99502-0650 SOILS LOG -- PERCOLATION TEST PERFORMED FOR: ~EGA/ DESCRIPTION: WAS GROUND WATER ENCOUNTERED? Township, Range, Section: IF YES, AT WHAT DEPTH? rlepth to W,I~- All~- Monitoring? ~ Dale: SLOPE SITE PLAN · Gross Net Depth to Net Heading Date Time Time Water Drop ¢=/ ?/;sh_~ /: ylO ~ .7,, _ ~ z... ~.'-oo ~ -'z ¢,~" ~/6" · TEST RUN BETWEEN C~ FTAND . /OFT :ORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATF_ DATE: ,., :)8 (Rev, 4/85) THAT THIS TE~T WAS PERFORMED IN Park Ridge Hills Subdivision Site No. 4 DESIGN FACTORS: Three Bedroom Home Perc. Rate: 16 to 30 Min./Inch Application Rate: .6 GPD/SF 3' Drain Rock Under Pipe SYSTEM REQUIREMENTS: Wide Trench System 1,000 Gal. Septic Tank Min. 2' Accepting Soil Red. Factor: .58 3 Bdrms. X 150 GPD / .6 GPD/SF = 750 SF 750 SF / 5' Wide X .58 Reduction Factor = 88' Total Lateral Length Therefore: Construct a Wide Trench System with Two 44' Laterals. Place 3' of Drain Rock Beneath Distribution Pipe. ................. ¢ .................................. ¢ ~ ..... ~' ;' ",~,. TYPICAL WIDE TRENCH SYSTEM (No Scale) · '""~ NOTE: Remove all Peat/Organics to Underlying Material. Provide 2" of Direct Burial Insulation or a Minimum of 3' of Cover over the Trench System. Maintain a Minimum of 4' Separation from the Bottom of the Trench to Groundwater. Park Ridge Hills Subdivision Site No. 5 DESIGN FACTORS: SYSTEM REQUIREMENTS: Three Bedroom Home Perc. Rate: 16 to 30 Min./Inch Application Rate: .6 GPD/SF 3' Drain Rock Under Pipe Wide Trench System 1,000 Gal. Septic Tank Min. 2' Accepting Soil Red. Factor: .58 3 Bdrms. X 150 GPD / .6 GPD/SF = 750 SF 750 SF / 5' Wide X .58 Reduction Factor = 88' Total Lateral Length Therefore: Construct a Wide Trench System with Two 44' Laterals. Place 3' of Drain Rock Beneath Distribution Pipe. TYPICAL WIDE TRENCH SYSTEM (No Scale) NOTE: Remove all Peat/Organics to Underlying Material. Provide 2" of Direct Burial Insulation or a Minimum of 3' of Cover over the Trench System. Maintain a Minimum of 4' Separation from the Bottom of the Trench to Groundwater. PERFORMED FOR: Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage. Alaska 99502-0650 SOILS LOG -- PERCOLATION TEST ~ ' /l 'c'- "~ ' "' DATE Township, Range, Section: '~'" WAS GROUND WATER ENCOUNTERED? S L IF YES, AT WHAT O DEPTH? p E SLOPE SITE PLAN Depth to Waler Alter Monitoring? Reading Date Gross Net Depth to Net Time Time Water Drop PERCOLATION RATE Z-~L {minutes/inch) PERC HOLE DIAMETER ~' TEST RUN BETWEEN L~. FT AND ~ FT :.RFORMED BY: I ' ~ ~' ' ;CORDANCE WITH ALL STATE AND MuNICIPal GUIDELINES IN EFFECT ON THIS DATE DATE: ~8 (R~. Park Ridge Hills Subdivision Site No. 9 DESIGN FACTORS: Three Bedroom Home Perc. Rate: 30 to 60 Min./Inch Application Rate: .3 GPD/SF SYSTEM REQUIREMENTS: Shallow Bed System 1,000 Gal. Septic Tank Min. 2' Accepting Soil 3 Bdrms. X 150 GPD / .3 GPD/SF = 1,500 SF 1,500 SF / 24' Wide = 63' Long Therefore: Construct a Shallow Bed System, 63' (Length) X 24' (Wide). Distribution Pipe Placed @ 3' Below Original Ground. ~ ~ . : : ~ .~ :..~ .! . NOTE: TYPICAL SHALLOW BED SYSTEM _". .. Remove all Peat/Organics to Underlying:?"SM'' .......... ,~.~. ..- Material ~ '-' : ' ' Provide 2" of Direct Burial Insulation or Minimum of 3' of Cover over the Bed System. Maintain a Minimum of 4' Separation from the Bottom of the Bed to Groundwater. Municipality of Anchorage DEPARTMENT OF HEALTH & H~UMAN SERVICES 825 "L" Street, Anchorage. Alaska 99502-0550 SOILS LOG-- PERCOLATION TEST WAS GROUND WATER ENCOUNTERED;' Township, Range, Section: S IF YES, AT WHAT I DEPTH? //~ p E M0~it~rin;? Dale: SLOPE SITE PLAN Reading Date Gross Net . Depth to Net Time Time Water Drop ~ ~o ~ ? ~/~" '/z" · '""" 'ERCOLATION RATE 3 7 (minutes/inch) PERC HOLE DIAMETER PERFORMED IN Park Ridge Hills Subdivision Site No. 10 DESIGN FACTORS: Three Bedroom Home Perc. Rate: 31 to 60 Min./Inch Application Rate: .45 GPD/SF Y Drain Rock Under Pipe 3 Bdrms. X 150 GPD / .45 GPD/SF SYSTEM REQUIREMENTS: Wide Trench System 1,000 Gal. Septic Tank Min. 2' Accepting Soil Red. Factor: .58 = 1,000 SF 1,000 SF / 5' Wide X .58 Reduction Factor = 116' Total Lateral Length Therefore: Construct a Wide Trench System with Two 58' Laterals. Place Y of Drain Rock Beneath Distribution Pipe. '~' TYPICAL WIDE TRENCH SYSTEM vT~. ".~' (No Scale) NOTE: Remove all Peat/Organics to Underlying Material. Provide 2" of Direct Burial Insulation or a Minimum of 3' of Cover over the Trench System. Maintain a Minimum of 4' Separation from the Bottom of the Trench to Groundwater. Park Ridge Hills Subdivision Site No. 11 DESIGN FACTORS: Three Bedroom Home Perc. Rate: 16 to 30 Min./Inch Application Rate: .4 GPD/SF 3 Bdrms. X 150 GPD / .4 GPD/SF 1,125 SF / 24' Wide = 48' Long SYSTEM REQUIREMENTS: Shallow Bed System 1,000 Gal. Septic Tank Min. 2' Accepting Soil = 1,125 SF Therefore: Construct a Shallow Bed System, 48' (Length) X (Wide). Distribution Pipe Placed @ 2' Below Original Ground. 24' 211"!t" ~ ~!:, · m,X I ..~ ~.... :.. s~/S'~ ~o,~ ~/~ . TYPICAL SHALLOW BED SYSTEM ~.~ d'~.-~.~,. NOTE: Remove all Peat/Organics to Underlying~o.~,~ Material. uz.,~.~~ Provide 2" of Direct Burial ~nsuiauon or a ~.~ Minimum of 3' of Cover over the Bed System. Maintain a Minimum of 4' Separation from the Bottom of the Bed to Groundwater. PERFORMED FOR:. Municipality of Anchorage DEPARTMENT OF HEALTH & I-[.UMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 ' SOILS LOG -- PERCOLATION TEST DATE PERFORMED: ." Township, Range, Section: .... ~ ..... -" ~:' SLOPE SITE PLAN /5'" WAS GROUND WATER ENCOUNTERED? S IF YES, AT WHAT i ~ DEPTH;' / 'Z. p E Bepm 1~ Water ~er iZi M~il~ring? ~ ~ Balm Gross Net . Depth to Net Reading' Date Time Time Water Drop ,kl o . IO /4 0 (minute~,'inch) PERC HOLE DIAMETER d- FT^ND 5-- ~r ': ' ' i'~'''PERCOLATION RATE ':c:: . .TEST RUN BETWEEN . .. :. -.:.;; ];: ;-..' . · -.:~ :..,f.; ..... .. . · . ~RFORMED BY: :'"~: '/~'~/~'/]J'~ I ~/~',~/t..tLc~ ~¢-~----~¢~/- ~::-r~TlFY THAT THIS TEST WAS PERFORMED IN :CORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: 008 (Rev, 4/85) t /i ! h (ENGINEER'S SEAL) Municipality of Anchorage . , i 825 "L" Street, Anchorage, AlaSka 99502--0650 ~ii..~.',~:~,~t'~L~'.~'~' ¢'"~:~ SOILS LOG-- PERCOLATION TEST ~:l::'~',, -~ -~ -':~;:: C, ~ H~;~ To~.~h~p, .~.g~, s~io.: · SLOPE SITE WAS GROUND WATER ENCOUNTERED? S IF YES, AT WHAT DEPTH? . p E DeCh Io Waler ~r/~ ,,~/_ Monil~ring? . // . /~/~ Gross Net Depth to Net Reading Date Time Time Water Drop ,¢~ ~/~,'/~ /o.'~ - ~, y~ ,, - ~-z /O : ./o z~ 7¢19,, lye', 7 10 11 12 13 14 · ,,V,~: /1 ' : " ' ":' PERCOLATION RATE (minutes/inch) PERO HOLE DIAMETER Park Ridge Hills Subdivision Site No. 12 DESIGN FACTORS: SYSTEM REQUIREMENTS: Three Bedroom Home Perc. Rate: 30 to 60 Min./Inch Application Rate: .3 GPD/SF Shallow Bed System 1,000 Gal. Septic Tank Min. 2' Accepting Soil 3 Bdrms. X 150 GPD / .3 GPD/SF = 1,500 SF 1,500 SF / 24' Wide = 63' Long Therefore: Construct a Shallow Bed System, 63' (Length) X 24' (Wide). Distribution Pipe Placed @ 3' Below Original Ground. NOTE: TYPICAI SHALLOW UED SYSTEM (No Scale) ~'. ' ~, ': "~-, :,..: ", :.;~i - Remove all Peat/Organics to Underlyi~g,"SM Material. Provide 2" of Direct Burial Insulation or Minimnm of 3' of Cover over the Bed System. Maintain a Minimum of 4' Separation from the Bottom of the Bed to Groundwater. PERFORMED FOR: Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street. Anchorage, Alaska 99502-0650 ' SOILS LOG -- PERCOLATION TEST MMENTS lull ~P WAS GROUND WATER ENCOUNTERED;' S IF YES, AT WHAT tz.i OL DEPTH? iX p E M~il~ring? oF ' ' :'""'pERcoLATION RATE "':~.:' . .' . ,~ . TEST RUN BETWEEN .. ~¢'",~."~ '"-,.,.,.'..:,'.. t , J:,;:' DATE PERFOR/~,IED~::' '; L ', Township, Range, Section: SLOPE SITE PLAN Reading Date Gross Nat Depth to Nat Time Time Water Drop ~= I ?/~,/ /,~.'.~o .- /~...¢ /,, ~/¢ ,, ~1~ ,, /~ , ~ ? ~ ¢ ,, ~/~ ,, ~"~'~ (minutes/inch) PEFIC HOLE DIAMETER _ c ~FORMED BY' · ,,~. .., ~.',.- .. ~ / TEST WASP~FORMED CORDANCE WITH ALL S+ATE ANO MUNI~I'~L GUIDELINES IN EFFECT ON THIS DAT~ DAT~ ~ ;/~a/Z~¢ ' ~8 (R~. 4/~) . , ,. ........... .. ,..~ ~ .'~.~..' , . · . .: , . . .':~.:.,~.,%?.~'f.'_~.',:2;..~-- · · ; - . . · .--' . .... Park Ridge Hills Subdivision Site No. 15 DESIGN FACTORS: Three Bedroom Home Perc. Rate: 30 to 60 Min./Inch Application Rate: .3 GPD/SF SYSTEM REQUIREMENTS: Shallow Bed System 17000 Gal. Septic Tank Min. 2' Accepting Soil 3 Bdrms. X 150 GPD / .3 GPD/SF = 1,500 SF 1,500 SF / 24' Wide = 63' Long Therefore: Construct a Shallow Bed System, 63' (Length) X 24' (Wide). Distribution Pipe Placed @ 2' Below Original Ground. NOTE: SHALLOW BED SYSTEM TYPICAL (No Scale) ,., .: ~ .... Remove all Peat/Organics to Underlying'q~Mt:,.., Material, '~" Provide 2" of Direct ~urial Insulation or a Minimum of 3' of Cover over the ~ed System, Maintaia a Mialmum of 4' Separation from the ~ottoa of the Bed to Groundwater. PERFORMED FOR: Municipality of Anchorage DEPARTMENT OF HEALTH & H, UMAN SERVICES 825 "L" Street, Anchorage, AlaSka 99502-0650 ' SOILS LOG -- PERCOLATION TEST Township, Range, Section: SLOPE SITE PLAN WAS GROUND WATER ENCOUNTERED? S IF YES, AT WHAT I ~ DEPTH? /~/ p E nepO~ to Water A~ter &i, ! /~)/& Monitoring? f Dale: Reading Date Gross Net Depth to Net Time Time Water Drop ~ I /o/z/~$ //: ,s- - 7 ,, _ :'; ': '" ' '"" PERCOLATION RATE (minutes/inch) PERC HOLE DIAMETER i .: '47:. "' '~ ' ':' 3 · ..:~.. ,....'. ,- .'." TEST RUN BETWEEN Fl' AND FT '.:: - ' .' -.. ,-,-'.:' :CORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES tN EFFECT ON THIS DATB DATD ~< '~ ~ ~8 (R~. 4/~) Park Ridge Hills Subdivision Site No. 17 DESIGN FACTORS: SYSTEM REQUIREMENTS: Three Bedroom Home Perc. Rate: 31 to 60 Min./Inch Application Rate: .45 GPD/SF 3' Drain Rock Under Pipe Wide Trench System 1,000 Gal. Septic Tank Min. 2' Accepting Soil Red. Factor: .58 3 Bdrms. X 150 GPD / .45 GPD/SF = 1,000 SF 1,000 SF / 5' Wide X .58 Reduction Factor = 116' Total Lateral Length Therefore: Construct a Wide Trench System with Two 58' Laterals. Place 3' of Drain Rock Beneath Distribution Pipe. V .......... i i ................... i ................ '..i ........ ! ..... i ..... i ....... ! i ....... ! ..... i ........ i ......... , ! .... !..''?;~.'2.')i~i~- I /,~ i i~ -~ ~ ................. ~, ! ~ .... ! ~ i ~ ....!: ~:' "' : ' ~';~:'""~~~'~" '~': ''~ . ~, ,, [ ' ' } ' ' : ' ~ ' ,, ,, r< ":: -- ......... '¥,~ ~,};. ~, '". . TYPICAL WIDE TRENCH SYSTEM :,',-',~, ':~:~ : (No Scale) ",:..-'' NOTE: ~emow all Peat/Organics to Underlying Material. Provide 2" of Direct Burial Insulation or a Minimum of 3' of Cover over the Trench System. Maintain a Minimum of 4' Separation frown the Bottom of the Trench to Groundwater. MunicipalHy of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, AlaSka 99502-0650 · SOILS LOG-- PERCOLATION TEST PERFORMED FOR: 2 3 (ENGINEER'5 5 h. AL} Township, Range, Section: SLOPE SITE PLAN WAS GROUND WATER ENCOUNTERED? S IF YES, AT WHAT . OL DEPTH? p E Reading ' Dste Gross Net Depth to Net Time Time Water Drop ~ /~': ~-~ zo 7 ~" ~/~" -PERCOLATION RATE ~""'-~-'-' (mlnute~[nch[ PERC HOLE DIAMETER TEST RUN ~S~WE~N ~/ ~m AND ERFORMEDBY: _ 'A"'¢ ~"~~"' ! '~/'~/~"¢'~ Z~'~//¢}'~'~/'-"~CER~-~'~"IFY THAT THIS TEST WAS PERFORMED iN CCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DAT~ DAT~ ~ Z~ ~ ~ ~8 (R~. 4/~) ~. PERFORMED FOR: Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0550 · SOILS LOG -- PERCOLATION TEST 7 8 .9 10 11 12 13 14 15 16 17 18, 19 20 COMMENTS Township, Range, Section: SLOPE WASGROUND WATER ENCOUNTERED? SITE PLAN IF YES, AT WHAT DEPTH? M0ni~ring? · ' Gross Net Depth to Net Reading 1~,3t e Time Time Water Drop · "'PERCOLATION RATI= ' 'z'~ (minutesJi'nchj PERC HOLE DIAMETER .TEST RUN BETWEEN FT AND FT .....:-.. . ... :~....,:.:'- ~._ ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DA'rY' -~/' ~J; 72-008 (Rev, 4/85} Park Ridge Hills Subdivision Site No. 18 DESIGN FACTORS: Three Bedroom Home Perc. Rate: 31 to 60 Min./Inch Application Rate: .45 GPD/SF 3' Drain Rock Under Pipe SYSTEM REQUIREMENTS: Wide Trench System 1,000 Gal. Septic Tank Min. 2' Accepting Soil Red. Factor: .58 3 Bdrms. X 150 GPD / .45 GPD/SF = 1,000 SF 1,000 SF / 5' Wide X .58 Reduction Factor = 116' Total Lateral Length Therefore: Construct a Wide Trench System with Two 58' Laterals. Place 3' of Drain Rock Beneath Distribution Pipe. i NOTE: Remove all Peat/Organics to Underlying '~'h't~i':'i".' Provide 2" of Direct Burial Insulation or a Minimum of 3' of Cover over the Trench System. Maintain a Minimnm of 4' Separation from the Bottom of the Trench to Groundwater. PERFORMED FOR: Municipality of Anchorage DEPARTMENT OF HEALTH & H. UMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 · SOILS LOG-- PERCOLATION TEST LEGAL DESCRIPTION: 2 3 .9 10 11 12 13 14 15 COMMENTS : " SITE PLAN Township, Range, Section: SLOPE WASGROUND WATER ENCOUNTERED? S IF YES, ATWHAT . OL DEPTH? p E Reading ' D3te Gross Net Depth to Net Time Time Water Drop /do. ,"? "'"'" ~ "'pERcoLATION RATE ~"~' (minute/inch} PERC HOLE DIAMETER . ' - ~:?"':" ' ' 'EST RUN BETWEEN __ FTAND FT PERFORMED BY'. ..:.:..'~ :'" . ~"ZZ~'~ ~ ~"'......:.,... ' 'm~-''~'7~''~'~'~L'' ~'~--~"'~'-'"i~-~TIFY THAT T~IS TEST WAS PERFORMED-- ' ACCORDANCE WITH ALL S:I'ATE AND M~t~I(~i'I~L GUIDELINES IN EFFECT ON THIS DATE. DATE.; ~fE 'c"~/?,3/ ' 72.008 [Rev. 4/85) IN Park Ridge Hills Subdivision Site No. 19 DESIGN FACTORS: SYSTEM REQUIREMENTS: Three Bedroom Home Perc. Rate: 31 to 60 Min./Inch Application Rate: .45 GPD/SF 3' Drain Rock Under Pipe Wide Trench System 1,000 Gal. Septic Tank Min. 2' Accepting Soil Red. Factor: .58 3 Bdrms. X 150 GPD / .45 GPD/SF = 1,000 SF 1,000 SF / 5' Wide X .58 Reduction Factor = 116' Total Lateral Length Therefore: Construct a Wide Trench System with Two 58' Laterals. Place 3' of Drain Rock Beneath Distril~ution Pipe. i ' ~ ........ ; .......... ~ ............... ~ ~ ..... ~ ..... ~ .... ~ ...... ; ......~ ;. ¢ .... ~ .... : ~ ' ~*'~,~.JL,;;? ::'.~ ', ~ .. ..~.. ~,. .;..,:. .... TYPICAL WIDE TRENCH SYSTEM (No Seale) NOTE: Remove all Peat/Organies to Underlying Material. Provide 2" of Direet Burial Insulation or a Minimum of 3' of Cover over the Treneh System. Maintain a Minimum of 4' Separation from the Bottom of the Trench to Groundwater. N 89"49'06" W Z S 89'40'~5" E February 28, 1994 LanTech, Inc. 440 W. Benson Anchorage, AK 99503 ANDERSON ENGINEERING P.O. BOX 240773 ANCHORAGE, ALASKA 99524 RECEIVED MAR 3 1994 Municipality of Anchorage Dept. Health & Human 8ervice~ 5:-q s3 Attention: Tom Dreyer Subject: Proposed Park Ridge Hills Subdivision Dear Tom: We have completed our field excavation and identified areas which will support onsite septic systems for the proposed Park Ridge Hills Subdivision. These areas were identified based on test holes excavated in September of 1993 and February of 1994 along with field data gathered in the past by Alaska Environmental Control Services, Inc. Groundwater elevations have been continuously monitored since last fall and the septic systems were designed based on the highest water level noted during this time. Soil conditions in this area are characterized by slow percolation rates and high groundwater. Neither condition is ideal for an onsite septic system. Our designs are therefore limited to three bedroom homes and are either wide trenches or shallow beds depending on the elevation of the groundwater in the area of the system. Lot lines should be placed so that a minimum of 3 sites are located on each lot. Evergreen Street which fronts the proposed subdivision was upgraded to Municipal Standards in 1983. A copy of the roadway asZbuilt is included for your use. Please let me know if you have additional questions or comments. Sincerely, Michael E. Anderson, P.E. Attachments 'lq Park Ridge Hills Subdivision Site No. I DESIGN FACTORS: Three Bedroom Home Perc. Rate: 31. to 60 Min./Inch Application Rate: .45 GPD/SF 3' Drain Rock Under Pipe 3 Bdrms. X 150 GPD / .45 GPD/SF SYSTEM REQUIREMENTS: Wide Trench System 1,000 Gal. Septic Tank Min. 2' Accepting Soil Red. Factor: .58 = 1,000 SF 1,000 SF / 5' Wide X .58 Reduction Factor = 116' Total Lateral Length Therefore: Construct a Wide Trench SYstem with Two 58' Laterals. Place 3' of Drain Rock Beneath Distribution Pipe. TYPICAL WIDE TRENCH SYSTEM (No Scale) NOTE: Remove all Peat/Organics to Underlying Material. Provide 2" of Direct Burial Insulation or a Minimum of 3' of Cover over the Trench System. Maintain a Minimum of 4' Separation from the Bottom of the Trench to Groundwater. DEPA MUNICIPALITY OF ANCHORAGE RTMENT OF HEALTH AND ENVIRONMENTAL PROTECTION SOILS LOG - PERCOLATION TEST SOILS LOG PERCOLATION TEST PERFORMED FOR; LEGAL DESCRIPTION:_ -- '~L) 1 Lmm) 2 3 4 5 6 7 8 g 10 11 12 13 14 ,.. 15 16 17 18 19 20 I SLOPE ~:'~_: 1' . . · }, .-~ ~. ~. ~:L;~4~'*' ENCOUNTERED? O P E IFYES, ATWHAT ~ /~ / DEPTH? 0~}~ Z ~ ~ SITE PLAN Gross Net Depth to Net Reading Date Time Time Water Drop ;s. TEST RUN BETWEEN '~,~ FT AND ~'~ '~- FT .z/Ro,-~ Trr'o,"~ L~ ~ /~ CERTIFIED BY: Park Ridge Hills Subdivision Site No. lA DESIGN FACTORS: Three Bedroom Home Perc. Rate: 6 to 15 Min./Inch Application Rate: .5 GPD/SF 3 Bdrms. X 150 GPD / .5 GPD/SF 900 SF / 18' Wide = 50' Long SYSTEM REQUIREMENTS: Shallow Bed System 1,000 Gal. Septic Tank Min. 2' Accepting Soil = 900 SF Therefore: Construct a Shallow Bed System, 50' (Length) (Wide). Distribution Pipe Placed @ 1' Below Original Ground. X 18' r~i !0~ i ~ · '. ~ ~ i' ~ ~ ~! ~ :/.~ ~, . "~: : ~: · ...... [ i ......... ! .................. ! ....... i i '~ i~! ;,'"'i'-~~ i'~': ~: : ..... i' i .... ........ ! ................ : i ..... sh/s~i ~,2 ~;';~ ' ; ..... ~. :.; · ......... ~ ...... ~ ...... ~ ......... i .......... ~ i ........... ~ .......... ~ ..... ~ '. ' : : i : : , : '~77~:,..~:~:~ ' TYPICAL SHALLOW BED SYSTEM : -' ...... NOTE: Remove all Peat/Organics to Underlyind;'(SM, '~"~-~, Material '~ ''~,-~' ' ~' '-'~ Provide 2" of Direct Burial Insulation or a Minimum' of 3' of Cover over the Bed System. Maintain a Minimum of 4' Separation from the Bottom of the Bed to Groundwater. Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG -- PERCOLATION TEST PERFORMED FOR: L~I~ ~"~.~ ~rvl/ 5? ~, ,.,:.: ........~:.:-' ,"L_~_._.- DATE PER FOI~IME~t; Township, Range, Section: SLOPE SITE PLAN WAS G ROUND WATER ENCOUNTERED? S 'YES, AT WHAT //'3 / O DEPTH7 / ""' P E O~pth to Water Aft~' 1 /~.../ - Gross Net Depth to Net Reading Date Time Time Water Drop ~/ ?/i~-' ~i.~o -- ~ Yz-' ---- · ' " "" "i'""PERCOLATION RATE--/~" (minutes/inch) PERC HOLE DIAMETER ... ,/~. ¥//~ ,. TEST RUN BETWEEN '"~ Fl' AND FT :-'."i.::;~::' ' " ...;z'~;!?,t:"--::':"'.V:'..':'ov:' .: CORDANCE WITH ALL STATE AND MUNICIP.~L GUIDELINES IN EFFECT ON THIS DATE. DATE: (Rev. 4/85) Park Ridge Hills Subdivision Site No. 3 DESIGN FACTORS: Three Bedroom Home Perc. Rate: 16 to 30 Min./Inch Application Rate: .4 GPD/SF 3 Bdrms. X 150 GPD / .4 GPD/SF 1,125 SF / 24' Wide = 48' Long SYSTEM REQUIREMENTS: Shallow Bed System 1,000 Gal. Septic Tank Min. 2' Accepting Soil = 1,125 SF Therefore: Construct a Shallow Bed System, 48'. (Length) X 24' (Wide). Distribution Pipe Placed @ 1' Below Original Ground. NOTE: TYPICAL SHALLOW BED SYSTEM ,:: ".:. ,:...' :., 'y .... :' .... . Remove all Peat/Organics to Underlying Material. "; ~;;~,~ ;.,;-" ~" of D~rect ~.rml Iasnlat~oa or a ..... ~.. Provide 2" ' ' ' Minimum of 3' of Cover over the Bed System. Maintain a Minimum of 4' Separation from the Bottom of the Bed to Groundwater. =ERFORMEDFOR:, Municipality of Anchorage DEPARTMENT OF HEALTH & H..UMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG -- PERCOLATION TEST WAS GROUND WATER ENCOUNTERED? Township, Range, Secti0ni IF YES, AT WHAT DEPTH? SLOPE SITE PLAN Monitoring? //_-. nap- ' " TEST RUN BETWEEN __ · ...: :~:!:':~:.'?' - .:':"-.' :..,-.,.,/ ..- Reading Date Gross Net Depth to Net Time Time Water Drop ~ ~ ~1~-' ~ : ¢o -- <5 '/z~ ~ z. ~ ~ : ~ ~ q 'l~ " ~/~ " ~3 ~ ~ ~ ~ I ~ '/& ~ ~ " ~ 7 (minutes/inch} PERC HOLE DIAMETER ~" FT AND "~ FT ORDANCE WiTH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATF- DATE: 8 (Rev. 4/85) THAT T. HIS TEST WAS PERFORMED IN - =ERFORMEDFOR: Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG M PERCOLATION TEST MMENTS DATE PER PORw~EH~/ Township, Range, Section: WAS GROUND WATER ENCOUNTERED? S L IF YES, AT WHAT 0 DEPTHS' p E Depth to Water Alta' / i ~oRitoring? (~ rtate: /O Z; ~-~i SLOPE SITE PLAN Reading ' Date Gross Net Depth to Net Time Time Water Drop ~/ ~//~/~'~ -/: ,/o ~ ..7. _ · _ ..:...-. . . . . .........:.. PERFORMED IN ;ORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: ~'/~(~ /~)/ 38 (Rev. 4/85) Park Ridge Hills Subdivision Site No. 4 DESIGN FACTORS: Three Bedroom Home Perc. Rate: 16 to 30 Min./Inch Application Rate: .6 GPD/SF 3' Drain Rock Under Pipe SYSTEM REQUIREMENTS: Wide Trench System 1,000 Gal. Septic Tank Min. 2' Accepting Soil Red. Factor: .58 3 Bdrms. X 150 GPD / .6 GPD/SF = 750 SF 750 SF / 5' Wide X .58 Reduction Factor = 88' Total Lateral Length Therefore: Construct a Wide Trench System with Two 44' Laterals. Place 3' of Drain Rock Beneath Distril~ution Pipe. NOTE: TYPICAL WIDE TRENCH SYSTEM (N---o~ ~) Remove all Peat/Organics to Underlying Material. Provide 2" of Direct Burial Insulation or a Minimum of 3' of Cover over the Trench System. Maintain a Minimum of 4' Separation from the Bottom of the Trench to Groundwater. Park Ridge Hills Subdivision Site No. 5 DESIGN FACTORS: Three Bedroom Home Perc. Rate: 16 to 30 Min./Inch Application Rate: .6 GPD/SF 3' Drain Rock Under Pipe SYSTEM REQUIREMENTS: Wide Trench System 1,000 Gal. Septic Tank Min. 2' Accepting Soil Red. Factor: .58 3 Bdrms. X 150 GPD / .6 GPD/SF = 750 SF 750 SF / 5' Wide X .58 Reduction Factor = 88' Total Lateral Length Therefore: Construct a Wide Trench System with Two 44' Laterals. Place 3' of Drain Rock Beneath .. Distribution Pipe. NOTE:. TYPICAL WIDE TRENCH SYSTEM (No Scale) Remove all Peat/Organics to Underlying Material. Provide 2" of Direct Burial Insulation or a Minimum of 3' of Cover over the Trench System. Maintain a Minimum of 4' Separation from the Bottom of the Trench to Groundwater. PERFORMED FOR: Municipalily of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG m PERCOLATION TEST WAS GROUND WATER ENCOUNTERED? DATE PER~:ORMED: , · Township, Range, Section: SLOPE SITE PLAN S L IF YES, AT WHAT O DEPTH? p E Oepm to Waler A,er Monitoring? ~) Dale: /0 -I' Reading Date Gross Net Depth to Net Time Time Water Drop -,~el c//lt,. 5:/o - & '/z. PERCOLATION RATE TEST RUN BETWEEN . Z"L~L (minutes/inch) PERC HOLE DIAMETER _ t.~ FT AND .., S-- FT ,-r'o ~r-',, ¢ ¢,. :-RFORMED BY: I ¢ c'- ' . ... . gCORDANCE WiTH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DAT~ DATE: ~' ~8 (R~. 4/~) Park Ridge Hills Subdivision Site No. 9 DESIGN FACTORS: Three Bedroom Home Perc. Rate: 30 to 60 Min./Inch Application Rate: .3 GPD/SF SYSTEM REQUIREMENTS: Shallow Bed System 1,000 Gal. Septic Tank Min. 2' Accepting Soil 3 Bdrms. X 150 GPD / .3 GPD/SF = 1,500 SF 1,500 SF / 24' Wide = 63' Long Therefore: Construct a Shallow Bed System, 63' (Length) X (Wide). Distribution Pipe Placed @ 3' Below Original Ground. 24' :" TYPICAL SHALLOW BED SYSTEM (No Scale) NOTE: Remove all Peat/Organics to Material. Provide 2" of Direct Burial Insulation or Minimum of 3' of Cover over the Bed System. Maintain a Minimum of 4' Separation from the Bottom of the Bed to Groundwater. Municipality of Anchorage DEPARTMENT OF HEALTH & H, UMAN SERVICES 825 "L" Street, Anchorage. Alaska 99502-0650 SOILS LOG -- PERCOLATION TEST WAS GROUND WATER . ,~J'_~ ENCOUNTERED? ~ '? ' ' i' :2':~'',~, ,- ' Township, Range, Section: s IF YES, AT WHAT DEPTH? /Z/~ P E liel~ Io Waler Alt~r/~ J ~/~ Moniloring? /x SLOPE SITE PLAN Reading Date Gross Net Depth to Net Time Time Water Drop ~-' 5'0 ~ ~ '/~ -"-/,5 '~ ~ ~ zo ~o ? ~/z~" ,/~" :' 'ii'f.:~-~j' ~ ~''.- .'""A" ,ERCOLATION RATE 3 7 (minutes/inchl PEFIC HOLE DIAMETER ~RFORMED BY: :CORDANCE WITH ALL S+A~E AND MUNI~;'~L GUIDELINES IN EFFECT ON THIS DAT~ DATE' PERFORMED IN Park Ridge Hills Subdivision Site No. 10 DESIGN FACTORS: Three Bedroom Home Perc. Rate: 31 to 60 Min./Inch Application Rate: .45 GPD/SF 3' Drain Rock Under Pipe SYSTEM REQUIREMENTS:- Wide Trench System 1,000 Gal. Septic Tank Min. 2' Accepting Soil Red. Factor: .58 3 Bdrms. X 150 GPD / .45 GPD/SF = 1,000 SF 1,000 SF / 5' Wide X .58 Reduction Factor = 116' Total Lateral Length Therefore: Construct a Wide Trench System with Two 58' Laterals. Place 3' of Drain Rock Beneath Distribution Pipe. : ~....... i ............. ~ ........... ,~ .......... ?~.'~ ~ ~'.' .... ."...~'"".~. ~.~Z..' ~ ...... .................. ........... ......... ........ .... ' ' ~,~, '~. ' , TYPICAL WIDE TRENCH SYSTEM ';'~'-~ (No Scale) " NOTE: Remove all Peat/Organics to Underlying Material. Provide 2" of Direct Burial Insulation or a Minimum of 3' of Cover over the Trench System. Maintain a Minimum of 4' Separatiou from the Bottom of the Trench to Groundwater. Park Ridge Hills Subdivision Site No. 11 DESIGN FACTORS: Three Bedroom Home Perc. Rate: 16 to 30 Min./Inch Application Rate: .4 GPD/SF 3 Bdrms. X 150 GPD / .4 GPD/SF 1,125 SF / 24' Wide = 48' Long SYSTEM REQUIREMENTS: Shallow Bed System 1,000 Gal. Septic Tank Min. 2' Accepting Soil = 1,125 SF Therefore: Construct a Shallow Bed System, 48' (Length) (Wide). Distribution Pipe Placed @ 2' Below Original Ground. X 24' ..... .... i O':'~ ~ O!"! i i .... "'~' ' ": ': ..~ ~..;..~ ~ .... ...... I .: ~ ~.~ ~ ........ ~?~:~ ........ ¢'; ........... ~'. : 'k;"'" X' ' ..... :. .. : : . . : .... : . . ' t>~ ~:J & :'L ;' '5 ~ ' ', ' TYPICAL SHALLOW BED SYSTEM ~:' :,:~?::?. ;~':}, '::. ':~ :: NOTE: Remove all Peat/Orgamcs to Underlymg~.~>o' 4~a~ .%~...: Prowde 2" of D~rect Bumal Insulation or a Minimum of 3' of Cover over the Bed System. Maintain a Minimum of 4' Separation from the Bottom of the Bed to Groundwater. Munlctpallty of Anchorage DEPARTMENT OF HEALTH & H..UMAN SERVICES 825 '%" Street, Anchorage, Alaska 99502-0650 ' SOILS LOG -- PERCOLATION TEST PERFORMED FOR: LEGAL DESCRIPTION: 'PT' 2 3 6 WAS GROUND WATER ENCOUNTERED? IF YES, AT WHAT i 0L DEPTH':? / 'Z. p E DeCh to Water After , MoniL~ring? / ~ Date: /0 Z -75 DATE PERFORMED: ' ... Township, Range, Section: ..... ' ........ SLOPE SITE PLAN RFORMED BY: Gross Net Depth to Net Reading Date Time Time Water Drop '" ' "" ~ERCOLATION RATE EST RUN BETWEEN (minutes'inch) PERC HOLE DIAMETER grAND ~ F~ ;CORDANCE WITH ALL STATE AND MUNICIP,~,L GUIDELINES IN EFFECT ON THIS DATE. DATI=' .. (Rev, 4/85) .-- PERFORMED FOR: Municipality of Anchorage DEPARTMENT OF HEALTH & H, UMAN SERVICES 825 "L" Street, Anchorage. AlaSka 99502-0650 · SOILS LOG-- PERCOLATION TEST WAS GROUND WATER ENCOUNTERED? 8 L IF YES, AT WHAT O DEPTH? p E M0niloring? // rla~ /O. 5 7 10 11.. 12 13 · :', '. (,b-NGiNEER'S SEAL) Township, Range, Section: · SLOPE SITE PLAN 14 15, 16 17 Gross Net Depth to Net Reading Date m~me T~me Water Drop ~ ~ ~1~¢1~ /o : ~ - ~ ,/~ ,, - ~¢ //:~o ~o //~1~,, t/~" · /2,~: II . ' · : ' "" PERCOLATION RATE (minutes/inch) PERC HOLE DIAMETER ~".-~{::~.. -.~ . .~. - . .. . , ': TEST RUN BETWEEN ,~ FTAND ~ FT PERFORMED BY; /4', ~-//~J~,,,~ ,~¢ ' ~'~/~ ~'~ER'TIF' THAT THIS TEST WAS PERFORMED IN 72-008 {Rev. 4/85) Park Ridge Hills Subdivision Site No. 12 DESIGN FACTORS: Three Bedroom Home Perc. Rate: 30 to 60 Min./Inch Application Rate: .3 GPD/SF 3 Bdrms. X 150 GPD / .3 GPD/SF 1,500 SF / 24' Wide = 63' Long Therefore: (Wide). SYSTEM REQUIREMENTS: Shallow Bed System 1,000 Gal. Septic Tank Min. 2' Accepting Soil = 1,500 SF Construct a Shallow Bed System, 63' (Length) X Distribution Pipe Placed @ 3' Below Original Ground. 24' NOTE: TYPICAL SHALLOW BED SYSTEM ~ '.'t-'~ ,~'17 "', .... (No Scale) ~'::.'::~.:~ :.L~:]' ~'. ~;',~,~,':~:'?~' '/ Remove all Peat/Organics to Underlyi~g'~.SM ..":'.-i/ Material. ',,,:,- ' ..-~: .... Provide 2" of Direct Burial Insulation or a Minimum of 3' of Cover over the Bed System. Maintain a Minimum of 4' Separation from the Bottom of the Bed to Groundwater. Municipality of Anchorage DEPARTMENT OF HEALTH & H, UMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 · SOILS LOG -- PERCOLATION TEST ,,vlL ~P Township, Range, Section: SLOPE WAS GROUND WATER ENCOUNTERED? IF YES, AT WHAT DEPTH? Depth to Water ~er ,~ i,( ~ /O]~__ Monitoring? /-~ ~/~ llal~: ..do. SITE PLAN ,:)MMENTS Reading Date Gross Net Depth to Net Time 'lqme Water Drop /'~"-~ ~ ~h" ~/~" ~RFORMED BY: :CORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DAT,F_ DATE: __ 008 (R~, 4t85) · ' · '.'"-..:'.,",.:~':.;:.::.":';'L'::':.:. ' ' ': . "" PERCOLATION RATE (minutes/inch) PERC HOLE DIAMETER Park Ridge Hills Subdivision Site No. 15 DESIGN FACTORS: Three Bedroom Home Perc. Rate: 30 to 60 Min./Inch Application Rate: .3 GPD/SF SYSTEM REQUIREMENTS: Shallow Bed System 1,000 Cal. Septic Tank Min. 2' Accepting Soil 3 Bdrms. X 150 CPD / .3 GPD/SF = 1,500 SF 1,500 SF / 24' Wide = 63' Long Therefore: Construct a Shallow Bed System, 63' (Length) X 24' (Wide). Distribution Pipe Placed @ 2' Below Original Ground. NOTE: TYPICAl, SHALLOW BED SYSTEM ..... "' .......... (No Scale) Remove all Peat/Organics to Underlying%SM~;'.., . ~,. ..... .. .'~':'..: Provide 2" of Direct gurial Insulation or a Minimum of 3' of Cover over the Bed System. Maintain a Minimum of 4' Separation from the Bottom of the Bed to Groundwater. Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 '"L" Street, Anchorage, Alaska 99502-0650 ' SOILS LOG -- PERCOLATION TEST PERFORMED FOR:. LEGAL DE$CmPT~ON'. DATE PERFORMED: Township. Range, Section: WAS GROUND WATER ENCOUNTERED? ¢~;~ S IF YES. AT WHAT I ~3 DEPTH? /] P E n~pth to W~t~r Alt,r ali' ! /~)]~. 1 SLOPE SITE PLAN Gross Net Depth to Net Reading Dam Time Time Water Drop -~ /o/z/9.~ /~: ,S" - ~" - .¢ z_ //:~5; ¢~0 7 '/~ . I1/_.- ~ ~ //~ ~ Z~ /~ '/ '//~" " ' '""'PERCOLATION RATE '" TEST RUN BETWEEN '~ FT AND FT ":-"' ' · '" '""'"'"' :CORDANCE WITH ALL STATE AND MUNICIP~L GUIDELINES IN EFFECT ON THIS DATE. DATE: 208 (R~V. 4/~) Park Ridge Hills Subdivision Site No. 17 DESIGN FACTORS: Three Bedroom Home Perc. Rate: 31 to 60 Min./Inch Application Rate: .45 GPD/SF 3' Drain Rock Under Pipe SYSTEM REQUIREMENTS: Wide Trench System 1,000 Gal. Septic Tank Min. 2' Accepting Soil Red. Factor: .58 3 Bdrms. X 150 GPD / .45 GPD/SF = 1,000 SF 1,000 SF / 5' Wide X .58 Reduction Factor = 116' Total Lateral Length Therefore: Construct a Wide Trench System with Two 58' Laterals. Place 3' of Drain Rock Beneath Distribution Pipe. [' i ........... i : i ............ ! ...... i ~c-:-i., !. .................. ......... jJ ........ ....... / ..... j ..... J ..... .............. TYPICAL WIDE TRENCH SYSTEM ~,,-,' (No Scale) "~.:,." "- NOTE: Remove all Peat/Organics to Underlying Material. Provide 2" of Direct Burial Insulatiou or a Minimum of 3' of Cover over the Trench System. Maintain a Minimum of 4' Separation from the Bottom of the Trench to Groundwater. PERFORMED FOR:. Municipality of Anchorage DEPARTMENT OF HEALTH & H. UMAN SERVICES 825 "L" Street, Anchorage, AlaSka 99502-0650 · SOILS LOG-- PERCOLATION TEST LEGAL DESCRIPTION: 1 7 8 § 10 11 12 13 Township, Range, Section: SLOPE SITE PLAN WAS GROUND WATER ENCOUNTERED? S L IF YES. AT WHAT - O DEPTH? p E Dale: ' Gross Net Depth to Net Reading D3te TTme T~me Water Drop ~ /~: ~ ~ ~ ?N' ~/~ ,, ~ //.'/~ ~ 7 ~ ~' "'PERCOLATION RATE ~"~'-'-' (minute,'inch) PERC HOLE DIAMETER TEST RUN BETWEEN ~/ FT AND ~ FT C. CORDANCE W TH ALL STATE AND MUNICIPAL GUIDELINES IN EFFEOT ON THIS DATF- DATE: .,, ~ ~-) ~t/ -CO8 {Rev. 4/,~5) ;. PERFORMED FOR:, 7 8 .9 10 11 12 13 14 15, 16- 17 18 19 20- Municipality of Anchorage DEPARTMENT OF HEALTH & H..UMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 · SOILS LOG-- PERCOLATION TEST Township, Range, Section: SLOPE WASGROUND WATER ENCOUNTERED~ S L IF YES, AT WHAT . O DEPTH? P E ~iterino? Datc SITE PLAN - Gross Net Depth to . Net Reading' l]2ta Time Time Water Drop '::'"" ' - .T~T RUN B~EEN -- FTAND COMMENTS _ : ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE.. DATE: (Rev. 4/85) IN Park Ridge Hills Subdivision Site No. 18 DESIGN FACTORS: Three Bedroom Home Perc. Rate: 31 to 60 Min./Inch Application Rate: .45 GPD/SF 3' Drain Rock Under Pipe SYSTEM REQUIREMENTS: Wide Trench System 1,000 Gal. Septic Tank Min. 2' Accepting Soil Red. Factor: .58 3 Bdrms. X 150 GPD / .45 GPD/SF = 1,000 SF 1,000 SF ! 5' Wide X .58 Reduction Factor = 116' Total Lateral Length Therefore: Construct a Wide Trench System with Two 58' Laterals. Place 3' of Drain Rock Beneath Distribution Pipe. ..... i i i i ii .... ....... ....... ........ .............. ~ ........ ', i ~ i~.~ .... i~....i '~.! ~, ~: .... .... ~...?.'/!%.i'i.~i..."~i-;..~:~i: i ~ ........... ! ...... i ...... i ..... i'"'. ~'"': ..... i : :, I ~, i ~ ¢~i-,i'i':':~ ~-~: i ':. i~, i ...... ~. ............ ~ ........ ~ .......... ......... ~ ...... : .... i : ~ .......... ~ ..... ~ ..... ~ .... ~ ~ : ~ : ~ ~ · ~' TYPICAL WIDE TRENCH SYSTEM ~}?~.~.t ~.-~.~. ~.' . (No Scale) ~':.':::-,"%,,~- ~ ..,..--"~.,..'; .... NOTE: Remove all Peat/Organics to Underlying ~a~te~ml, Provide 2" of Direct Burial Insulation or a Minimum of 3' of Cover over the Trench System. Maintain a Minimum of 4' Separation from the Bottom of the Trench to Groundwater. PERFORMED FOR: Municipality o! Anchorage DEPARTMENT OF HEALTH & hUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 · SOILS LOG-- PERCOLATION TEST 1 2 3 6 7 8 .9 10 11 12 13 14 15 16 17 18- 20- COMMENTS 1:~ jL],~/..l...5 Township, Range, Section: - SLOPE WASGROUND WATER ENCOUNTERED? SITE PLAN S L Ii= YES, AT WHAT ,. O DEPTH? P E ~Dnitoring? Dal~' · Gross Net Depth to Net Reading· Date Time Time Water Drop ~" PERCOLATION RATE (minute~/[nch} PERC HOLE DIAMETER __ .TEST RUN BETWEEN . FT AND FT ^CCO.O^NC~ W,'rH ^'' S:rAT~ ^N~ MON:&';~L ~UlDE~IN~S'N E~.EOT ON T.lS DA'~ ~^~' pERFORMED IN 72-008 {Re¥, 4165} ,"' Park Ridge Hills Subdivision Site No. 19 DESIGN FACTORS: Three Bedroom Home Perc. Rate: 31' to 60 Min./Inch Application Rate: .45 GPD/SF 3' Drain Rock Under Pipe SYSTEM REQUIREMENTS: Wide Trench System 1,000 Gal. Septic Tank Min. 2' Accepting Soil Red. Factor: .58 3 Bdrms. X 150 GPD / .45 GPD/SF = 1,000 SF 1,000 SF / 5' Wide X .58 Reduction Factor = 116' Total Lateral Length Therefore: Construct a Wide Trench System with Two 58' Laterals. Place 3' of Drain Rock Beneath Distril~ution Pipe. TYPICAL WIDE TRENCH SYSTEM (No ;~cale) . NOTE: Remove all Peat/Organics to Underlying Material. Provide 2" of Direct Burial Insulation or a Minimum of 3' of Cover over the Trench System. Maintain a Minimum of 4' Separation from the Bottom of the Trench to Groundwater. RECEIVED Municipality o! ^nchorafle Health & Human ServJoes DESIGN FACTORS: Park Ridge Hills Subdivision Site No. 19 Three Bedroom Home Perc. Rate: 31 to 60 Min./Inch Application Rate: .45 GPD/SF 3' Drain Rock Under Pipe SYSTEM REQUIREMENTS:· Wide Trench System 1,000 Gal. Septic Tank Min. 2' Accepting Soil Red. Factor: .58 3 Bdrms. X 150 GPD / .45 GPD/SF = 1,000 SF 1,000 SF / 5' Wide X .58 Reduction Factor = 116' Total Lateral Length Therefore: Construct a Wide Trench System with Two 58' Laterals. Place 3' of Drain Rock Beneath Distril~ution Pipe. · : ~ :' ............ : ~ ~ ' '.~- ~ ..... - -.. ~z ¢'~'' -,'" ' ........ i ........... ~ ........... ? ........... ] .......... : .......... ! ......... i ........... ~ ........ i .......... ~ ....... i .......... : ............. ~ : : ~ ~ · ,~'~'~ o~' :. ~' ",~.' ,... '~ : ...... ! .......... ! i i i ~ ~ i ~.~?'.~,;~-T:;'~ ~"'"':: ..... :~"' :"'~-:~, ........ : ~ ...... ' ................ ' ........ : ~ ......... · : ~ ,r~, '?',~' ,.''~ ~ . ~ ~ ~) NOTE: Remove all Peat/Organics to Underlying Material. Provide 2" of Direct Burial Insulation or a Minimum of 3' of Cover over the Trench System. Maintain a Minimum of 4' Separation from the Bottom of the Trench to Groundwater. I B HILLS C LOT 2 ' PAR~ ~'~'5/ / / / '~ ~ ~ / / CERTIFICATE OF OWNERSHIP end DEDICA~ON ~ j ~ LOT 14 ~ ~ ~ ~ LOT 12 (~ h~y c~fy ~ t (we) hold ~e ~eln specified p~pe~y Intere~ j ~ I 123,533 sq,ft. I ', NO~ ~;~ ~ ~ ~ms~ 2 836 ~cres ~ NOTARY~DGEMENT ~ ~ % ~ : ~ ~ NOTARY ACK~T ~ ~ ~ ) ~ J S * ~ow p:s~c c*P fLUS, ACCEPTANCE OF DEDICATION TAX CERTIFICATION LOTS 1.2.3.4 ~¢¢~ m~'g ~ TOM DTi00i270